background image

6%2)3).$5342)%3

H8186-CB

INSTALLATION GUIDE

Z204062-0E 

page 8 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected] 

 

06081

BACnet Protocol Implementation Conformance Statement

Date:    

August 2, 2007

Vendor Name:    

Veris Industries

Product Name:   

BACnet Communications Board for  

 

 

H81xx Energy Meter

Product Model Number:    

H8186-CB

Applications Software Version:  

1

    

Firmware Revision:  

1.09

BACnet Protocol Revision:  

2

Product Description:   

Provides BACnet MS/TP connectivity to  

 

 

the Veris H81xx Energy Meter

BACnet Standardized Device Profile (Annex L): 

BACnet Application Specific Controller (B-ASC)

List all BACnet Interoperability Building Blocks Supported (Annex K): 

DS-RP-B, DS-RPM-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B 

Segmentation Capability:

Segmentation not supported

Standard Object Types Supported:
 

No dynamic Creation or Deletion supported

 

No proprietary properties or object types

 

Device Object:

 

 

Optional Properties Supported:

 

 

 

Max_Master, Max_Info_Frames, Description, Location

 

 

Writable Properties:

 

 

 

Object_Identifier, Max_Master, Location

 

 

Property Range Restrictions:

 

 

 

Location (limited to 64 characters)

 

Analog Input Object:

 

 

Optional Properties Supported:

 

 

  

Description

 

 

No Writable Properties.

 
 

Analog Value Object:

 

 

Optional Properties Supported:

 

 

 

Description

 

 

Writable Properties:

 

 

 

Only the Present_Value is writable.

 

 

Property Range Restrictions:

 

 

 

1)  Only the value 0.0 may be written to the Present_Value 

 

 

 

 

of AV1.  This action will clear the kWh-Accumulator in the 

 

 

 

 

H81xx Energy Meter.

 

 

 

2)  Although a REAL (i.e. floating point) value, writing the 

 

 

 

 

Present_Value of AV2 is an alternative method  of changing 

 

 

 

 

the Device_Instance.  This value may be written in the range 

 

 

 

 

0-4194302.  Any fractional value will be truncated (eg. 57.234

 

 

 

 

will be written as 57).

Data Link Layer Options:

MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400

Device Address Binding:

Static device binding is not supported. (No client functionality is included).

Networking Options:

None

Character Sets Supported:

ANSI X3.4 

bacnet Protocol

Archived Document

Содержание H8126-CB

Страница 1: ...UJPOT 0QFSBUJPO PG UIJT FRVJQNFOU JO B SFTJEFOUJBM BSFB JT MJLFMZ UP DBVTF IBSNGVM JOUFSGFSFODF JO XIJDI DBTF UIF VTFS XJMM CF SFRVJSFE UP DPSSFDU UIF JOUFSGFSFODF BU IJT PXO FYQFOTF PEJmDBUJPOT UP UI...

Страница 2: ...for 2 wire or 4 wire communications CAUTION Danger of Explosion if battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Dispose of used batteri...

Страница 3: ...daisy chain The RS 485 interface will support daisy chains that fall within the specifications shown below Baud Rate Maximum Distances 1 16 Devices 17 32 Devices 9600 10000 ft 3048 m 4000 ft 1219 m 1...

Страница 4: ...TX RX TX TX TX SHLD TX RX TX RX TX MASTER SLAVE ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 TX RX RX ALIVE SHLD TX RX TX RX TX TX TX SHLD TX RX TX RX TX TX SHLD RX RX TX TX SHLD TX RX TX RX TX SHIELD RX RX TX TX M...

Страница 5: ...TION SLOTS 4 Insert the communication terminal onto the RS 485 communication terminals 5 If the demand subinterval feature is used wire into the end of the demand subinterval terminal 6 Replace the vo...

Страница 6: ...Network Address DIP switches for each Network address See Selecting the network Address NETWORK ADDRESS DIP SWITCHES on pages 2 3 for instruction on setting the switches 32 33 34 35 36 37 38 39 40 41...

Страница 7: ...Input Object 14 Voltage Phase A Phase B Volts_AB VOLTS Analog Input Object 15 Voltage Phase B Phase C Volts_BC VOLTS Analog Input Object 16 Voltage Phase A Phase C Volts_AC VOLTS Analog Input Object 1...

Страница 8: ...t Optional Properties Supported Max_Master Max_Info_Frames Description Location Writable Properties Object_Identifier Max_Master Location Property Range Restrictions Location limited to 64 characters...

Отзывы: