6%2)3).$5342)%3
inStallation GUiDe
ep3 SerieS
Auto
Manual
GND
INPUT
24V
CH2
CH1/PWM
OPERATION
MODE
TRISTATE
ALARM
P-LOSS MAN
INPUT VOLTAGE
0-10V 0-5V
TRI-PULL-UP
ON OFF
OUTPUT
4-20mA 0-10V
ALARM
OUTPUT
4-20mA/0-10V
Tristate Timing
Network
FS Point
Zero
RUN
4-20mA
Voltage
Tristate
PWM
Network
Control
SETTING
INPUT
+
-
Subtrac
t
Pr
es
su
re
Add Pressur
e
JUMPER/SLIDE SWITCH CONFIGURATION:
INPUT:
User selectable current (4-20mA) or VOLTAGE (0-5/0-10V), Tri-state, PWM
OUTPUT STANDARD:
0-20psig
OUTPUT OPTION:
4-20mA, 0-10V
Feedback status for branch pressure
SETTINGS:
User programmable Tristate Timing–travel time
Min...5 seconds
Max...600 seconds
Default...60 seconds
PWM
Min pulse setting 0.01-0.6 seconds
Full Scale (FS) scale point user programmable 0-25psi
Zero user programmable 0-25psig
After desired settings have been selected, move slide switch to the run position
MODE:
Auto for normal operation or Manual to adjust pressure
OPTIONS:
Analog output 4-20mA or 0-10V (branch pressure status)
Vent on power failure
Cover (Use option 2 from ordering table)
confiGuration