inStallation GUiDe

ep3 SerieS

Auto 

 

Manual 

GND 

INPUT 

24V 

CH2 

CH1/PWM 

 

OPERATION 

MODE 

TRISTATE 

ALARM 

P-LOSS   MAN 

 

INPUT VOLTAGE 

0-10V    0-5V 

 

TRI-PULL-UP 

ON  OFF 

OUTPUT 

4-20mA   0-10V 

ALARM 

OUTPUT 

4-20mA/0-10V 

 
Tristate Timing 
Network 
FS Point 
Zero 
RUN 

 
 

4-20mA 
Voltage 
Tristate 

PWM 

Network 

Control 

 

SETTING 

INPUT

Subtrac

Pr

es

su

re

 

Add Pressur

e

JUMPER/SLIDE SWITCH CONFIGURATION:

INPUT:

 

User selectable current (4-20mA) or VOLTAGE (0-5/0-10V), Tri-state, PWM

OUTPUT STANDARD:

  0-20psig

OUTPUT OPTION:

 

4-20mA, 0-10V

 

 

Feedback status for branch pressure

SETTINGS:

  User programmable Tristate Timing–travel time

 

 

Min...5 seconds

 

 

Max...600 seconds

 

 

Default...60 seconds

 

PWM

 

 

Min pulse setting 0.01-0.6 seconds

 

 

Full Scale (FS) scale point user programmable 0-25psi

 

 

Zero user programmable 0-25psig

After desired settings have been selected, move slide switch to the run position

MODE: 

Auto for normal operation or Manual to adjust pressure

OPTIONS: 

Analog output 4-20mA or 0-10V (branch pressure status)

 

Vent on power failure

 

Cover (Use option 2 from ordering table)

confiGuration

Содержание EP3 Series

Страница 1: ...1 2 digit LCD back light Minimum Tubing Length 15 feet Port Connection 1 8 id poly tubing Media Connection Clean dry air or inert gas Not for use with oxygen service or combustible gases ForshortertubingrunsuseP NAA45PneumaticCapacitor EMCConformance EN61000 6 3ClassB 2001 EN61000 6 1 2001 EN61000 3 2 2000 EN 61000 3 3 2001 EMCTestMethods IEC61000 4 2 2001 04 IEC61000 4 3 2001 IEC61000 4 4 2001 IE...

Страница 2: ...IGURATION INPUT User selectable current 4 20mA or VOLTAGE 0 5 0 10V Tri state PWM OUTPUT STANDARD 0 20psig OUTPUT OPTION 4 20mA 0 10V Feedback status for branch pressure SETTINGS User programmable Tristate Timing travel time Min 5 seconds Max 600 seconds Default 60 seconds PWM Min pulse setting 0 01 0 6 seconds Full Scale FS scale point user programmable 0 25psi Zero user programmable 0 25psig Aft...

Страница 3: ...ILTER 20 45psi Regulator AIR COMPRESSOR PWMControlExample Input switch set to PWM Tri State jumper set to ON GND INPUT 24V CH2 CH1 PWM 4 20mA 0 10V ALARM CONTACTS POWER SOURCE BRANCH TRI STATE CONTACTS CH1 OR CH2 OR TRAP FILTER 20 45psi Regulator AIR COMPRESSOR Subtract Pressure Add Pressure Tri stateControlExample Input switch set to TRI STATE Tri State jumper set to ON Current voltageControl Vol...

Страница 4: ...wer cycling the EP If you power cycle before 10 seconds your settings will be erased and the setpoint will default to previous setting The device s internal counters measure the contact closure time with 100Hz resolution Note If Tristate input is to be operated by a triac output an AC relay is required to provide a dry contact closure to the EP3 input AnalogOutput The output is generated from the ...

Отзывы: