PAGE 3 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected]   

06081

6%2)3).$5342)%3

inStallation GUiDe

ep3 SerieS

wirinG

GND

INPUT

+24V

CH2

CH1/PWM

4-20mA

0-10V

       ALARM C

ONT

AC

TS

POWER 

SOURCE

Digital Input

(Contact Closure)

4-20mA PROCESS METER

BRANCH

TRAP/

FILTER

20-45psi

Regulator

+

-

Analog Out

(0-5/0-10/4-20mA)

Common

AIR COMPRESSOR

Current/voltage Control, Current Output Example

 Input switch settings same as example 1

• Output jumper set to 4-20mA

GND

INPUT

+24V

CH2

CH1/PWM

4-20mA

0-10V

       ALARM C

ONT

AC

TS

POWER 

SOURCE

BRANCH

PWM CONTACT

TRAP/

FILTER

20-45psi

Regulator

AIR COMPRESSOR

+

-

PWM Control Example

• Input switch set to "PWM"
• Tri-State jumper set to "ON"

GND

INPUT

+24

V

CH2

CH1/PWM

4-20mA

0-10V

       AL

ARM C

ONT

AC

TS

POWER 

SOURCE

BRANCH

TRI-STATE CONTACTS

CH1

OR

CH2

OR

TRAP/

FILTER

20-45psi

Regulator

AIR COMPRESSOR

+

-

+

-

Subtrac

t

Pr

essur

e

Add P

ressur

e

Tri-state Control Example

• Input switch set to "TRI-STATE"
• Tri-State jumper set to "ON"

Current/voltage Control, Voltage Output Example

GND

INPUT

+24V

CH2

CH1/PWM

4-20mA

0-10V

       ALARM C

ONT

AC

TS

POWER 

SOURCE

Digital Input

(Contact Closure)

0-10V PROCESS METER

BRANCH

TRAP/

FILTER

20-45psi

Regulator

+

-

Analog Out

Common

AIR COMPRESSOR

+

-

• 

Input switch set to voltage (0-5VDC or 0-10VDC)

• Input volt jumper set to either 0-5VDC or 0-10VDC
• Input switch set to 4-20mA
• Output jumper set to 0-10VDC

Содержание EP3 Series

Страница 1: ...1 2 digit LCD back light Minimum Tubing Length 15 feet Port Connection 1 8 id poly tubing Media Connection Clean dry air or inert gas Not for use with oxygen service or combustible gases ForshortertubingrunsuseP NAA45PneumaticCapacitor EMCConformance EN61000 6 3ClassB 2001 EN61000 6 1 2001 EN61000 3 2 2000 EN 61000 3 3 2001 EMCTestMethods IEC61000 4 2 2001 04 IEC61000 4 3 2001 IEC61000 4 4 2001 IE...

Страница 2: ...IGURATION INPUT User selectable current 4 20mA or VOLTAGE 0 5 0 10V Tri state PWM OUTPUT STANDARD 0 20psig OUTPUT OPTION 4 20mA 0 10V Feedback status for branch pressure SETTINGS User programmable Tristate Timing travel time Min 5 seconds Max 600 seconds Default 60 seconds PWM Min pulse setting 0 01 0 6 seconds Full Scale FS scale point user programmable 0 25psi Zero user programmable 0 25psig Aft...

Страница 3: ...ILTER 20 45psi Regulator AIR COMPRESSOR PWMControlExample Input switch set to PWM Tri State jumper set to ON GND INPUT 24V CH2 CH1 PWM 4 20mA 0 10V ALARM CONTACTS POWER SOURCE BRANCH TRI STATE CONTACTS CH1 OR CH2 OR TRAP FILTER 20 45psi Regulator AIR COMPRESSOR Subtract Pressure Add Pressure Tri stateControlExample Input switch set to TRI STATE Tri State jumper set to ON Current voltageControl Vol...

Страница 4: ...wer cycling the EP If you power cycle before 10 seconds your settings will be erased and the setpoint will default to previous setting The device s internal counters measure the contact closure time with 100Hz resolution Note If Tristate input is to be operated by a triac output an AC relay is required to provide a dry contact closure to the EP3 input AnalogOutput The output is generated from the ...

Отзывы: