INSTALLATION GUIDE

ENERCEPT

®

  

H8035/H8036

Networked Power Transducer (Modbus RTU)

US Patent No. 6,373,238

Installer’s Specifications 

Input Voltage 

208 to 480 VAC

Number of Phases Monitored 

1 or 3

Frequency 

50/60 Hz

Maximum Primary Current 

100/300/400/800/1600/2400 A continuous per phase

CT case isolation 

600 VAC

Internal isolation 

2000 VAC rms 

Operating temp. range 

0° to 60°C (32° to 122°F) (<95%RH, non-condensing)

Storage temp. range 

-40° to 70°C (-40° to 158°F)

Accuracy 

±1% of reading from 10% to 100% of the rated current*

Output Type 

RS-485, 2-wire plus common

Baud Rate 9600

Protocol 

Modbus RTU

* Accuracy specified with conductors centered in the CT window.

QUICK INSTALL 

Disconnect and lock out power before installation.

1.  Set the address switches located on the bottom of the CT.

2.  Connect the voltage leads to the source to be monitored.

3.  Snap the CT onto the conductor (observe color matching).

4.  Connect the Modbus wires (observe polarity).

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
•  Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE:  This equipment has been tested by the manufacturer and found 

to comply with the limits for a class A digital device, pursuant to part 
15 of the FCC Rules. These limits are designed to provide reasonable 
protection against harmful interference when the equipment is 
operated in a commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if not installed and 
used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in 
a residential area is likely to cause harmful interference in which case 
the user will be required to correct the interference at his own expense. 
Modifications to this product without the express authorization of 
Veris Industries nullify this statement. 

CAUTION

RISK OF EQUIPMENT DAMAGE

• 

Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with 

high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives, 

Adjustable Frequency Drives) or similar sources, as these may permanently damage the 

product.

Failure to follow these instructions can result in overheating and permanent 

equipment damage.

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must 
control conductive pollution and the possibility of condensation or high humidity. Consider the 
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship 
with the environment. Installation category:  CAT II or CAT III

Содержание ENERCEPT H8035

Страница 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Страница 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Страница 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Страница 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Страница 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Страница 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Страница 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Страница 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Страница 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Страница 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...

Отзывы: