E54C3C Installation Guide

WARNING

LOSS OF CONTROL

∙  Assure that the system will reach a safe state during and after a control path failure.
∙  Separate or redundant control paths must be provided for critical control functions.
∙  Test the effect of transmission delays or failures of communication links.

1

∙  Each implementation of equipment using communication links must be individually 

and thoroughly tested for proper operation before placing it in service.

Failure to follow these instructions may cause injury, death or equipment damage.

1

For additional information about anticipated transmission delays or failures of the link, refer to 

NEMA ICS 1.1 (latest edition). 

Safety Guidelines for the Application, Installation, and Maintenance 

of Solid-State Control

 or its equivalent in your specific country, language, and/or location.

Control system design must consider the potential failure modes of control paths and, for 

certain critical control functions, provide a means to acheive a safe state during and after a 

path failure. Examples of critical control functions are emergency stop and over-travel stop.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Product may use multiple voltage/power sources. Disconnect ALL sources before

 servicing.
•  Use a properly rated voltage sensing device to confirm that power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
•  Current transformer secondaries must be shorted or connected to a burden at all times.
•  Products rated only for basic insulation must be installed on insulated conductors.
•  Replace all doors, covers and protective devices before powering the equipment.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and 

operation of this electrical equipment and installations, and has received safety 

training to recognize and avoid the hazards involved.  

NEC Article 100

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

DANGER

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment 
must control conductive pollution and the possibility of condensation or high humidity. 
Consider the enclosure, the correct use of ventilation, thermal properties of the equipment, 
and the relationship with the environment. Installation category:  CAT II or CAT III.  Provide 
a disconnect device to disconnect the meter from the supply source. Place this device in 
close proximity to the equipment and within easy reach of the operator, and mark it as the 
disconnecting device. The disconnecting device shall meet the relevant requirements of 
IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US and Canada, 
disconnecting fuse holders can be used. Provide overcurrent protection and disconecting 
device for supply conductors with approved current limiting devices suitable for protecting the 
wiring. If the equipment is used in a manner not specified by the manufacturer, the protection 
provided by the device may be impaired.

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION

NOTE: This equipment has been tested by the manufacturer and found to 

comply with the limits for a class B digital device, pursuant to part 15 of 

the FCC Rules. These limits are designed to provide reasonable protection 

against harmful interference when the equipment is operated in a 

residential environment. This equipment generates, uses, and can radiate 

radio frequency energy and, if not installed and used in accordance with 

the instruction manual, may cause harmful interference to radio 

communications. This device complies with part 15 of the FCC Rules. 

Operation is subject to the following two conditions:

   

(1) This device may not cause harmful interference, and

   

(2) this device must accept any interference received, including

   

      interference that may cause undesired operation.

   Modifications to this product without the express authorization of the 

manufacturer nullify this statement. 

Installation Guide

Power Monitoring

TM

TM

The safety of any system incorporating this equipment is the responsibility of the 

assembler of the system.

Product Overview

The E54C3C energy meter works on a on a single-phase, three-phase, or three-phase + neutral network with 
partial metering and reset functions. The meter requires 1 Amp or 5 Amp current transformers. Data values are 
instantly accessible using either the local display or the communications network. The E54C3C is equipped with 
Modbus communication via RS-485. It provides four-quadrant energy measurements with one configurable 
digital input, one configurable digital output, and up to four tariffs.

Important:  COM.Protection is a mode that prevents changes to any meter setting related to energy 
measurement, such as wiring configuration, through Modbus communication. This mode is enabled by default. 
To allow configuration over Modbus, first disable COM.Protection via the configuration menu on the display. 
Refer to the Configuration section of this guide.

E54C3C

Energy Meter, Modbus Communication

Specifications

POWER SUPPLY

Measured Voltage

100 to 277 V

LN

; 173 to 480 V

LL

 ± 20%

Frequency

50/60 Hz ± 10%

Voltage Impedance

3 MΩ

Wire Size

24 to 14 AWG (0.2 to 2.5 mm

2

)

Terminal Block Torque

4.4 in-lb (0.5 N-m) max.

CURRENT INPUTS

Nominal Current

1 A or 5 A

Measured Current

5 mA to 6 A

Withstand

10 A continuous; 20 A @ 10 sec/hr

Frequency

50/60 Hz ± 10%

Impedance

<0.3 mΩ

Burden

<0.024 VA @ 10 A

Wire Size

18 to 10 AWG (0.8 to 6 mm

2

)

Terminal Block Torque

7.0 in-lb (0.8 N-m) max.

DIGITAL INPUT

   Type

Type 1 (IEC 61131-2)

Maximum Input

40 Vdc, 4 mA

 Voltage Off

0 to 5 Vdc

Voltage On

11 to 40 Vdc

Nominal Voltage

24 Vdc

Isolation

3.75 kV RMS

Wire Size

25 to 16 AWG (0.14 to 1.5 mm

2

)

Terminal Block Torque

4.4 in-lb (0.5 N-m) max.

DIGITAL OUTPUT

Type

SPST N.O. (Form A)

Maximum Input

5 to 40 Vdc, 50 mA

Output Resistance

0.1 to 50 Ω

Wire Size

25 to 16 AWG (0.14 to 1.5 mm

2

)

Terminal Block Torque

4.4 in-lb (0.5 N-m) max.

MEASUREMENT ACCURACY

Real Energy for x/1A Current Input

Class 1 conforming to IEC 62053-21 and IEC 61557-12  

(PMD Sx):  I

max

=1.2 A, l

n

=1 A, and I

st

=0.002 A

Class B conforming to EN 50470-3: I

max

=1.2 A, l

n

=1 A, I

min

=0.01 A, and 

I

st

=0.002 A

Reactive Energy for x/1A Current Input

Class 2 conforming to IEC 62053-23 and IEC 61557-12  

(PMD Sx):  I

max

=1.2 A, l

n

=1 A, and I

st

=0.003 A

Real Energy for x/5A Current Input

Class 0.5S conforming to IEC 62053-22 and IEC 61557-12 (PMD SD): 

I

max

=6 A, l

n

=5 A, and I

st

=0.005 A

Class C conforming to EN 50470-3: I

max

=6 A, l

n

=5 A, I

min

=0.05 A, and 

I

st

=0.005 A

Reactive Energy for x/5A Current Input

Class 2 conforming to IEC 62053-23 and IEC 61557-12  

(PMD Sx):  I

max

=6 A, l

n

=5 A, and I

st

=0.015 A

MODBUS COMMUNICATION

Number of Ports

1

Parity

Even, Odd, None

Baud Rate

9600, 19200, 38400

Isolation

4 kV RMS

Wire Size

24 to 14 AWG (0.2 to 2.5 mm

2

)

Terminal Block Torque

4.4 in-lb (0.5 N-m)

OPERATING CONDITIONS

   Operating Temperature Range

-25 to 55 °C (-13 to 131 °F) (5% to 95% RH non-condensing)

   Storage Temperature Range

-40 to 85 °C (-40 to 185 °F)

   Altitude of Operation

< 2000 m

Mounting Location

Not suitable for wet locations. For indoor use only.

COMPLIANCE INFORMATION

Approvals

CE; UL 61010-1; IEC/EN 61010-1; IEC 62053-31

Housing

IP40 front panel, IP20 casing, Pollution Degree 2, IK08 impact rating

MID

2004/22/EC compliance

Specifications (cont.)

Dimensions

3.5”

(90 mm)

4.0”

(102 mm)

2.7”

(69 mm)

2.5”

(64 mm)

3.4”

(87 mm)

1.8”

(45 mm)

OK

ESC

ZL0131-0G              Page 1 of 8                          ©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]                                                          0818 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

EAV71194-04

ZL0131-0G              Page 2 of 8                          ©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]                                                          0818 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

EAV71194-04

E54C3C