E54C3C Installation Guide

E54C3C Installation Guide

Product Diagram

A.  Digital input
B.  Digital output
C.  RS-485 communications port
D.  Communications LED
E.  Display for measurement and configuration
F.  1 A or 5 A current transformer input
G.  Cancellation

H. Confirmation
I.   Selection
J.  Voltage inputs
K.  Energy pulse LED (5000 flashes per kWh)
L.  Status LED (on/off/error)
M.  Locking points 
N.  Lockable covers

OK

ESC

M

N

5000      /kWh

ON

C/- DI

OK

ESC

Reset

Config

C DO

N.C.

N.C.

0V

D0/- D1/+

RS485

O

S2 

S1 

S1 

S2 

S1 

S2 

(I1) 

(I2) 

(I3) 

Vn

V3

V2

V1

J

L

A

G

F

E

D

C

B

H

K

I

Installation

1.  Disconnect power prior to the installation. Use a properly rated voltage sensing device to ensure power is off.

2.  Install the meter onto standard DIN rail as shown.

Click!

3.  Wire the meter (see the Wiring section).

4.  Reconnect power to the meter.

5.  Configure the meter (see the Configuration section).

Wiring

For all terminals, apply the correct torque (see below).

V1, V2, V3, N

24 to 14 AWG (0.2 to 2.5 mm

2

)

4.4 in-lb (0.5 N-m) max.

DI, DO, C, C/-

25 to 16 AWG (0.14 to 1.5 mm

2

)

4.4 in-lb (0.5 N-m) max.

I1, I2, I3

18 to 10 AWG (0.8 to 6 mm

2

)

7.0 in-lb (0.8 N-m) max.

Modbus RS-485 24 to 14 AWG (0.2 to 2.5 mm

2

)

4.4 in-lb (0.5 N-m) max.

Digital Input, Digital Output, and Communications Wiring

Digital output wiring is not polarity sensitive.

D0 = A’ / Rx-, A / Tx-

D0 = B’ / Rx+, B / Tx+

0 V

-

-/+ +/-

+

Load

Modbus RS-485

11 to 40 Vdc    5 to 40 Vdc

C

DIn

C

DOut

+

RS-485

0V

S

D0/- D0/+

S

CT Wiring

Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator. Use fuses/circuit 
breakers that are rated for the installation voltage and sized for the available fault current. A fuse for neutral is required if the 
source neutral is not grounded.

1 Phase

1 Phase, 2-Wire, L-N   

             1 Phase, 2-Wire, L-L     

     1 Phase, 3-Wire, L-L-N

Shorting 

Block

Fuses and 

Disconnect

S1

S2

≤ 480 V L-L 

V1 V2 V3 Vn

(I1)

(I3)

(I2)

L1
L2

Shorting 

Block

Fuses and 

Disconnect

V1 V2 V3 Vn

(I1)

(I3)

(I2)

S1

S2

≤ 277 V L-N

L

N

Shorting 

Block

Fuses and 

Disconnect

S1

S2

S1

S2

≤ 277 V L-N
≤ 480 V L-L

L1
L2

N

V1 V2 V3 Vn

(I1)

(I3)

(I2)

1 Phase, 4-Wire, Multi-L with N, 2 CTs      

1 Phase, 4-Wire, Multi-L with N, 3 CTs

Shorting 

Block

Fuses and 

Disconnect

V1 V2 V3 Vn

(I1)

(I3)

(I2)

S1

S2

S1

S2

≤ 277 V L-N

L

N

Shorting 

Block

Fuses and 

Disconnect

V1 V2 V3 Vn

(I1)

(I3)

(I2)

S1

S2

S1

S2

S1

S2

≤ 277 V L-N

L

N

ZL0131-0G              Page 3 of 8                          ©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]                                                          0818 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

EAV71194-04

ZL0131-0G              Page 4 of 8                          ©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]                                                          0818 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

EAV71194-04

Отзывы: