E50F2A, E50F5A Installation Guide

Configuration Properties (cont.)

CP Name

Type

NV Num.

R/W

Applies To

Range

Default Value

Description

cpPhaseLossImbal

UCPTphLossImbal 
(UCP_Type_10 w/o 

resource files)

(SNVT_count ref.)

19

R/W

“Meter” Function 

Block

1 - 99 (%)

25(%)

Phase Loss Imbalance Threshold in percent. For 

a 3-phase Y(3+N) system (type 40), both Line 

to Neutral and Line to Line voltages are tested. 

In a 3-phase delta system (type 31), only the 

Line to Line voltages are examined. In a single 

split-phase (2+N) system (type 12), just the 

Line to Neutral voltages are compared.

cpDemSubintLen

UCPTDemSubintLen 
(UCP_Type_11 

w/o resource files) 

(SNVT_count ref.)

20

R/W

“Meter” Function 

Block

0, 10 - 32767 

(seconds)

900 (seconds)

Sub-Interval Length in seconds. For sync-to-

comms, set this to 0 and use nviDemSubintRes 

to externally restart the sub-interval.

cpDemSubintCnt

UCPTDemSubintCnt
(UCP_Type_1 w/o 

resource files) 

(SNVT_count ref.)

21

R/W

“Meter” Function 

Block

1 - 6

1

Number of Sub-Intervals per Demand Interval. 

Sets the number of sub-intervals that make 

a single demand interval. For block demand, 

set this to 1. 

PROPAGATION CONTROL
cpMaxNvSntPerSec UCPTnvUpdtLimit 

(UCP_Type_2 w/o 

resource files) 

(SNVT_count)

29

R/W

“Meter” Function 

Block

0 - 65535

10

Limits the total number of updates sent out per 

second for network variables in the following 

categories: Energy, Power, Voltage, Current, 

Power Factor, Frequency, Pulse Counters, 

Startup Count, and Alerts. If more than the 

number of updates specified is queued to be 

sent out in any 1 second period, the excess 

updates are delayed until the next second 

to reduce network traffic. This configuration 

property is provided to give rough burst 

control. The number of packets sent per 

second will vary based on the connection 

types (ACK, UNACK, etc.) and updates from 

other network variables that are not controlled 

by this configuration property.

cpAllEnergy

SCPTminSndT

1

R/W

All energy output 

network variables

0 - 1 hour, 

49 minutes, 

13 seconds, 

500ms (6553.5 

seconds)

15 seconds

Throttle for all energy output network variables. 

After propagation of a network variable, 

updates to the same network variable are 

blocked for the time set by this configuration 

property. The configuration property is shared, 

but each energy output network variable has 

its own independent throttle counter that 

resets to the value specified by this CP after it 

has been propagated.

cpAllPower

SCPTminSndT

2

R/W

All power output 

network variables

0 - 1 hour, 

49 minutes, 

13 seconds, 

500ms (6553.5 

seconds)

15 seconds

Throttle for all power output network variables. 

After propagation of a network variable, 

updates to the same network variable are 

blocked for the time set by this configuration 

property. The configuration property is shared, 

but each power output network variable has 

its own independent throttle counter that 

resets to the value specified by this CP after it 

has been propagated.

cpAllVoltage

SCPTminSndT

3

R/W

All voltage output 

network variables

0 - 1 hour, 

49 minutes, 

13 seconds, 

500ms (6553.5 

seconds)

15 seconds

Throttle for all voltage output network 

variables. After propagation of a network 

variable, updates to the same network 

variable are blocked for the time set by this 

configuration property. The configuration 

property is shared, but each voltage output 

network variable has its own independent 

throttle counter that resets to the value 

specified by this CP after it has been 

propagated.

Содержание E50F2A

Страница 1: ...ions This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interfer...

Страница 2: ...acteristics Back lit blue LCD Terminal Block Screw Torque 0 37 ft lb 0 5 N m nominal 0 44 ft lb 0 6 N m max Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Mounting Rail T35 35 mm DIN Rail per EN...

Страница 3: ...ions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Pulse Contact Inputs 10 So...

Страница 4: ...onfigurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive an...

Страница 5: ...CAT III 50 60 Hz Alarm Output Pulse Input LON FT Shield SERVICE X2 A X1 X2 B X1 X2 C X1 IA IB IC X2 X1 X2 X1 X2 X1 kWh 1234 5 Product Diagrams E50F5A Alarm Energy Two5 characterrows ofdisplaytext Topr...

Страница 6: ...rd 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ular System Type display as on the User Interface or as QNAN in the LON variables Supported System Types CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty I...

Страница 8: ...1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black White Black X1 X2 X1 X2 X1 X2 L1 L2 X2 X1 A B C N A B C White Black X1 X2 X1 X2 X1 X2 Diagram3 1 PhaseDir...

Страница 9: ...NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125VDCto300VDC ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For select...

Страница 10: ...e Setup screens return to SETUP B ToEntertheCT CurrentTransducer outputvoltageandCTsizeranges 1 Press to go to the CT SZ screen and through the digits Use or to select the CT size in amps default is 1...

Страница 11: ...r the short circuit current at the connection point All pulse inputs outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to ha...

Страница 12: ...Voltage Line to Line HZ HZ Frequency KSh KVAh Accumulated Apparent Energy KQh KVARh Accumulated Reactive Energy KPh KWh Accumulated Real Energy PLOSS PLOSS Phase Loss LOWPF LOWPF Low Power Factor Err...

Страница 13: ...erage of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A K...

Страница 14: ...B C Voltage Out of Range Current Out of Range Not used on E50Fx devices A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V O...

Страница 15: ...Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Wiring Diagrams section Set this value before setting the system voltage to establish the proper range of Sys...

Страница 16: ...ts To Setup p 1 S PWR SPLOS Back IMBAL 0 25 Next VOLTS 0 10 Set Phase Loss VOLTS Phase Loss Voltage Phase Loss Voltage Threshold in percent of system voltage Any phase as configured by the System Type...

Страница 17: ...oad these files separately Note If using resource files install them before importing the device template into a network Resources Available for Downloading The following instructions are written for...

Страница 18: ...and alarm configuration The second tab for configuration of the device is the Propagation Settings tab which includes configuration properties that control propagation heartbeat throttle etc Settings...

Страница 19: ...file exists and select the file 3 Press the Open button FormattingPowerCorrectly LonMark Resource Files before version 13 04 set the default format in the U S for network variables of the type SNVT_p...

Страница 20: ...Source of CP Values select LNS database Press Finish to complete commissioning Synchronization While Device is Commissioned and Online 1 Right click on the device in LonMaker and select Commissioning...

Страница 21: ...gin is not open right click on it and select Plugins Veris E50 Download Log from the context menu If it is already open click on the Data Logging tab 2 Expand the LOG INFO section 3 Press the RESET LO...

Страница 22: ...is OffNet the Data Logging tab will not be visible To show this tab click the Help menu and select Advanced Force Toggle Logging Visible 3 Expand the LOG SETUP section using the arrows on the right s...

Страница 23: ...To get only a specific amount of the newest records select the Fixed Amount of latest entries option and enter the desired amount in the textbox The log can hold 5760 records but both options stop dow...

Страница 24: ...r of them ConfiguringtheDevice All of the user defined configuration properties are implemented as configuration network variables so that they can be set as either configuration properties or as inpu...

Страница 25: ...y Throttle Real Energy Consumption Phase B integer value nvoRlEnrgyPhCInt 55 Meter SNVT_elec_kwh_l kWh Scaled 51 cpAllEnergy Throttle Real Energy Consumption Phase C integer value nviEnergyReset 34 Me...

Страница 26: ...0 Reset no more frequently than every 10 seconds VOLTAGE nvoAvgLLVoltage 73 Meter SNVT_volt_f Volt 269 cpAllVoltage Throttle Average Line to LineVoltage nvoAvgLNVoltage 74 Meter SNVT_volt_f Volt 271...

Страница 27: ...of range Bit 4 Phase B Current out of range Bit 5 Phase C Current out of range Bit 6 Frequency out of the range of 45 to 65 Hz or insufficient voltage to determine frequency Bit 7 Internal data bus c...

Страница 28: ...uble write first of the values saved from the previous cycle and then the present values If the read condition is not removed the meter continues to write the log data as it normally would This bit is...

Страница 29: ...ion Guide NV Name NV Num Function Block Type Units Log Point Index Propagation Control Description Configuration Property Name Control Type nviLogRequestLen 32 Meter SNVT_count Number of Records retri...

Страница 30: ...its UCPTdisplayUnits UCP_Type_4 w o resource files SNVT_count ref 13 R W Meter Function Block 0 1 1 IEEE Screen Display Units 0 IEC U V P Q S 1 IEEE VLL VLN W VAR VA cpCtPriRatio UCPTctPriRatio UCP_Ty...

Страница 31: ...ore than the number of updates specified is queued to be sent out in any 1 second period the excess updates are delayed until the next second to reduce network traffic This configuration property is p...

Страница 32: ...each power factor output network variable has its own independent throttle counter that resets to the value specified by this CP after it has been propagated cpFrequency SCPTminSndT 28 R W nvoFrequen...

Страница 33: ...e provided as a column in the network variable table above cpLoggingPoint3 UCPTlogPoint3 UCP_Type_15 w o resource files SNVT_count ref 25 R W Meter Function Block See description nvoPresRealDmnd 325 S...

Страница 34: ...ersions lower than 13 04 have the default format in the U S for SNVT_power_f variables in Btu hr See the section on Formatting Power Correctly The data displayed is inaccurate Incorrect setup values V...

Отзывы: