E50F2A, E50F5A Installation Guide

NV Name

NV 

Num.

Function 

Block

Type

Units

Log 

Point 

Index

Propagation Control

Description

Configuration 

Property 

Name

Control 

Type

ENERGY
nvoRealEnergy

97

TotalRealEnergy SNVT_elec_wh_f

Wh

257

cpAllEnergy

Throttle

Real Energy Consumption (floating point value)

nvoRealEnergyInt

47

Meter

SNVT_elec_kwh_l

kWh, Scaled

1

cpAllEnergy

Throttle

Real Energy Consumption (integer value)

nvoReactEnergy

45

Meter

SNVT_elec_wh_f

VARh

311

cpAllEnergy

Throttle

Reactive Energy Consumption  (floating point value)

nvoRctEnergyInt

48

Meter

SNVT_elec_kwh_l

kVARh, Scaled 29

cpAllEnergy

Throttle

Reactive Energy Consumption (integer value)

nvoAppEnergy

46

Meter

SNVT_elec_wh_f

Vah

309

cpAllEnergy

Throttle

Apparent Energy Consumption (floating point value)

nvoAppEnergyInt

49

Meter

SNVT_elec_kwh_l

kVAh, Scaled

27

cpAllEnergy

Throttle

Apparent Energy Consumption (integer value)

nvoRealEnergyPhA 50

Meter

SNVT_elec_wh_f

Wh

341

cpAllEnergy

Throttle

Real Energy Consumption, Phase A (floating point value)

nvoRealEnergyPhB 51

Meter

SNVT_elec_wh_f

Wh

343

cpAllEnergy

Throttle

Real Energy Consumption, Phase B (floating point value)

nvoRealEnergyPhC 52

Meter

SNVT_elec_wh_f

Wh

345

cpAllEnergy

Throttle

Real Energy Consumption, Phase C (floating point value)

nvoRlEnrgyPhAInt

53

Meter

SNVT_elec_kwh_l

kWh, Scaled

47

cpAllEnergy

Throttle

Real Energy Consumption, Phase A (integer value)

nvoRlEnrgyPhBInt

54

Meter

SNVT_elec_kwh_l

kWh, Scaled

49

cpAllEnergy

Throttle

Real Energy Consumption, Phase B (integer value)

nvoRlEnrgyPhCInt

55

Meter

SNVT_elec_kwh_l

kWh, Scaled

51

cpAllEnergy

Throttle

Real Energy Consumption, Phase C (integer value)

nviEnergyReset

34

Meter

SNVT_switch

-

-

-

-

Clears all energy accumulators to 0. To reset, set the state 

field to 1 and the value field to greater than 0.

nvoEnrgyResetCnt

93

Meter

SNVT_count

-

cpEnrgyResetCnt Heartbeat

Count of energy accumulator resets.

nvoIntEnrgScale

95

Meter

SNVT_count_inc

-4  0.0001
-3  0.001
-2  0.01
-1  0.1
0  1.0
1  10.0
2  100.0
3  1000.0
4  10000.0

-
-
-
-
-
-
-
-
-

None

-

Scale factor for integer energy network variables. This 

value is an integer between -4 and 4. Multiply integer 

energy values by 10 to the power of this variable. For 

example, if this variable returns -2, multiply integer 

energy accumulators by 10

-2

 (0.01).  Only recalculated 

when meter configuration is changed, so this value may 

be read infrequently.

POWER
nvoRealPower

98

TotalRealPower

SNVT_power_f

W

261

cpAllPower

Throttle

Total Instantaneous Real Power

nvoReactivePower 56

Meter

SNVT_power_f

VAR

263

cpAllPower

Throttle

Total Instantaneous Reactive Power

nvoApparentPower 57

Meter

SNVT_power_f

VA

265

cpAllPower

Throttle

Total Instantaneous Apparent Power

nvoRealPowerPhA 58

Meter

SNVT_power_f

W

275

cpAllPower

Throttle

Real Power, Phase A

nvoRealPowerPhB 59

Meter

SNVT_power_f

W

277

cpAllPower

Throttle

Real Power, Phase B

nvoRealPowerPhC

60

Meter

SNVT_power_f

W

279

cpAllPower

Throttle

Real Power, Phase C

nvoReactPowerPhA 61

Meter

SNVT_power_f

VAR

319

cpAllPower

Throttle

Reactive Power, Phase A

nvoReactPowerPhB 62

Meter

SNVT_power_f

VAR

321

cpAllPower

Throttle

Reactive Power, Phase B

nvoReactPowerPhC 63

Meter

SNVT_power_f

VAR

323

cpAllPower

Throttle

Reactive Power, Phase C

nvoAppPowerPhA

64

Meter

SNVT_power_f

VA

313

cpAllPower

Throttle

Apparent Power, Phase A

nvoAppPowerPhB

65

Meter

SNVT_power_f

VA

315

cpAllPower

Throttle

Apparent Power, Phase B

nvoAppPowerPhC

66

Meter

SNVT_power_f

VA

317

cpAllPower

Throttle

Apparent Power, Phase C

Network Variables

Содержание E50F2A

Страница 1: ...ions This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interfer...

Страница 2: ...acteristics Back lit blue LCD Terminal Block Screw Torque 0 37 ft lb 0 5 N m nominal 0 44 ft lb 0 6 N m max Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Mounting Rail T35 35 mm DIN Rail per EN...

Страница 3: ...ions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Pulse Contact Inputs 10 So...

Страница 4: ...onfigurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive an...

Страница 5: ...CAT III 50 60 Hz Alarm Output Pulse Input LON FT Shield SERVICE X2 A X1 X2 B X1 X2 C X1 IA IB IC X2 X1 X2 X1 X2 X1 kWh 1234 5 Product Diagrams E50F5A Alarm Energy Two5 characterrows ofdisplaytext Topr...

Страница 6: ...rd 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ular System Type display as on the User Interface or as QNAN in the LON variables Supported System Types CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty I...

Страница 8: ...1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black White Black X1 X2 X1 X2 X1 X2 L1 L2 X2 X1 A B C N A B C White Black X1 X2 X1 X2 X1 X2 Diagram3 1 PhaseDir...

Страница 9: ...NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125VDCto300VDC ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For select...

Страница 10: ...e Setup screens return to SETUP B ToEntertheCT CurrentTransducer outputvoltageandCTsizeranges 1 Press to go to the CT SZ screen and through the digits Use or to select the CT size in amps default is 1...

Страница 11: ...r the short circuit current at the connection point All pulse inputs outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to ha...

Страница 12: ...Voltage Line to Line HZ HZ Frequency KSh KVAh Accumulated Apparent Energy KQh KVARh Accumulated Reactive Energy KPh KWh Accumulated Real Energy PLOSS PLOSS Phase Loss LOWPF LOWPF Low Power Factor Err...

Страница 13: ...erage of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A K...

Страница 14: ...B C Voltage Out of Range Current Out of Range Not used on E50Fx devices A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V O...

Страница 15: ...Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Wiring Diagrams section Set this value before setting the system voltage to establish the proper range of Sys...

Страница 16: ...ts To Setup p 1 S PWR SPLOS Back IMBAL 0 25 Next VOLTS 0 10 Set Phase Loss VOLTS Phase Loss Voltage Phase Loss Voltage Threshold in percent of system voltage Any phase as configured by the System Type...

Страница 17: ...oad these files separately Note If using resource files install them before importing the device template into a network Resources Available for Downloading The following instructions are written for...

Страница 18: ...and alarm configuration The second tab for configuration of the device is the Propagation Settings tab which includes configuration properties that control propagation heartbeat throttle etc Settings...

Страница 19: ...file exists and select the file 3 Press the Open button FormattingPowerCorrectly LonMark Resource Files before version 13 04 set the default format in the U S for network variables of the type SNVT_p...

Страница 20: ...Source of CP Values select LNS database Press Finish to complete commissioning Synchronization While Device is Commissioned and Online 1 Right click on the device in LonMaker and select Commissioning...

Страница 21: ...gin is not open right click on it and select Plugins Veris E50 Download Log from the context menu If it is already open click on the Data Logging tab 2 Expand the LOG INFO section 3 Press the RESET LO...

Страница 22: ...is OffNet the Data Logging tab will not be visible To show this tab click the Help menu and select Advanced Force Toggle Logging Visible 3 Expand the LOG SETUP section using the arrows on the right s...

Страница 23: ...To get only a specific amount of the newest records select the Fixed Amount of latest entries option and enter the desired amount in the textbox The log can hold 5760 records but both options stop dow...

Страница 24: ...r of them ConfiguringtheDevice All of the user defined configuration properties are implemented as configuration network variables so that they can be set as either configuration properties or as inpu...

Страница 25: ...y Throttle Real Energy Consumption Phase B integer value nvoRlEnrgyPhCInt 55 Meter SNVT_elec_kwh_l kWh Scaled 51 cpAllEnergy Throttle Real Energy Consumption Phase C integer value nviEnergyReset 34 Me...

Страница 26: ...0 Reset no more frequently than every 10 seconds VOLTAGE nvoAvgLLVoltage 73 Meter SNVT_volt_f Volt 269 cpAllVoltage Throttle Average Line to LineVoltage nvoAvgLNVoltage 74 Meter SNVT_volt_f Volt 271...

Страница 27: ...of range Bit 4 Phase B Current out of range Bit 5 Phase C Current out of range Bit 6 Frequency out of the range of 45 to 65 Hz or insufficient voltage to determine frequency Bit 7 Internal data bus c...

Страница 28: ...uble write first of the values saved from the previous cycle and then the present values If the read condition is not removed the meter continues to write the log data as it normally would This bit is...

Страница 29: ...ion Guide NV Name NV Num Function Block Type Units Log Point Index Propagation Control Description Configuration Property Name Control Type nviLogRequestLen 32 Meter SNVT_count Number of Records retri...

Страница 30: ...its UCPTdisplayUnits UCP_Type_4 w o resource files SNVT_count ref 13 R W Meter Function Block 0 1 1 IEEE Screen Display Units 0 IEC U V P Q S 1 IEEE VLL VLN W VAR VA cpCtPriRatio UCPTctPriRatio UCP_Ty...

Страница 31: ...ore than the number of updates specified is queued to be sent out in any 1 second period the excess updates are delayed until the next second to reduce network traffic This configuration property is p...

Страница 32: ...each power factor output network variable has its own independent throttle counter that resets to the value specified by this CP after it has been propagated cpFrequency SCPTminSndT 28 R W nvoFrequen...

Страница 33: ...e provided as a column in the network variable table above cpLoggingPoint3 UCPTlogPoint3 UCP_Type_15 w o resource files SNVT_count ref 25 R W Meter Function Block See description nvoPresRealDmnd 325 S...

Страница 34: ...ersions lower than 13 04 have the default format in the U S for SNVT_power_f variables in Btu hr See the section on Formatting Power Correctly The data displayed is inaccurate Incorrect setup values V...