E50F2A, E50F5A Installation Guide

Manually Setting the Meter Time Using the Plugin

1.  If the plugin is not open, right-click on it and select “Browse…” from the context menu. If it is already open, click on the 

“Network Variables” tab.

2.  Press the “STATUS” button on the left.

3.  To set the meter time from the computer’s time, press the “SYNC TO PC TIME” button.

4.  To set the meter time to a custom time, modify the custom time (field below the current time) and press the “SET TO CUSTOM 

[TIME]” button.

Configuring the Data Log (E50F5A only)

The E50F5A meter includes a data logging feature that holds 5760 time stamped records for 3 meter parameters. The logging 
interval is fixed to the demand subinterval length, which can be anywhere between 10 seconds and 9 hours. The default logging 
interval is 15 minutes (900 seconds), which allows for 60 days of data stored in the log. This data can be downloaded to a CSV file 
on a computer using the plugin.

The log can be set up in either Single Shot Mode or Continuous Mode (default is Continuous Mode).  In Single Shot Mode, the meter 
records data until the buffer is full. When the buffer is full, the meter stops recording new readings and retains the 5760 records it 
has already saved. In Continuous Mode, the meter continues to record data as long as it is operating. The log buffer can only hold 
5760 records at a time, however, so once the meter reaches 5760 records the oldest is deleted each time a new record is saved. 
Once full, therefore, the buffer will always hold the most recent 5760 records.

Setting up the log

1.  If the plugin is not open, right-click on it and select “Plugins”-> “Veris E50 Download Log” from the context menu. If it is 

already open, click on the “Data Logging” tab.

2.  If the device is not online, has not been commissioned, or the LonMaker Management Mode is OffNet, the “Data Logging” tab 

will not be visible. To show this tab, click the “Help” menu and select Advanced->”Force Toggle Logging Visible.” 

3.  Expand the “LOG SETUP” section using the arrows on the right side of the header.

4.  To get the current setting from the meter or the database, press the “GET PRESENT SETTINGS” button.  If the configuration 

properties on the device do not match the database, a prompt  appears to choose which values to load. The database may 

contain zeros for the points to log when a device is first created, since the E50 device template does not contain defaults for 

these configuration properties (to prevent defaults from the device template conflicting with factory defaults stored on the 

device). When first configuring logging, if the device is online (or soft offline), choose to get values from the device.

5.  Select the three points to log (drop-down lists give log point indices corresponding to the Configuration Property table of this 

guide, the names of the network variables the data points correspond to, and descriptions of each).

6.  Choose to enable or disable the log, and which logging mode to use (continuous or single shot).

7.  When finished making changes, press the “APPLY SETTINGS” button. If the device is online (or soft offline), commissioned, and 

the LonMaker mode is OnNet, the configuration property settings are applied to both the network database and the device. If, 

however, the above conditions are not met, the configuration property settings are written to the database only. A dialog box 

appears when the write is finished, stating where the values were written to. If values were not written to the device (database 

only), the device must be resynchronized to the database at a later time. See the “Configuration Property Resynchronization” 

section below. 

8.  If the logging interval (Demand Subinterval Length) was not set to the right value while configuring the meter using the 

“METER SETUP” tab (“Device Configuration Instructions” section above), perform the following steps. Otherwise the log has 

been successfully configured.

9.  Switch to the “METER SETUP” tab of the log. 

10. Press the “GET PRESENT SETTINGS” button to get all of the current settings.  

11. Under the “OTHER SETTINGS” section, change the demand subinterval length to the desired logging interval (keeping in mind 

that demand is also affected).

Using the LNS Plugin 

(cont.)

Содержание E50F2A

Страница 1: ...ions This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interfer...

Страница 2: ...acteristics Back lit blue LCD Terminal Block Screw Torque 0 37 ft lb 0 5 N m nominal 0 44 ft lb 0 6 N m max Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Mounting Rail T35 35 mm DIN Rail per EN...

Страница 3: ...ions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Pulse Contact Inputs 10 So...

Страница 4: ...onfigurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive an...

Страница 5: ...CAT III 50 60 Hz Alarm Output Pulse Input LON FT Shield SERVICE X2 A X1 X2 B X1 X2 C X1 IA IB IC X2 X1 X2 X1 X2 X1 kWh 1234 5 Product Diagrams E50F5A Alarm Energy Two5 characterrows ofdisplaytext Topr...

Страница 6: ...rd 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ular System Type display as on the User Interface or as QNAN in the LON variables Supported System Types CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty I...

Страница 8: ...1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black White Black X1 X2 X1 X2 X1 X2 L1 L2 X2 X1 A B C N A B C White Black X1 X2 X1 X2 X1 X2 Diagram3 1 PhaseDir...

Страница 9: ...NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125VDCto300VDC ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For select...

Страница 10: ...e Setup screens return to SETUP B ToEntertheCT CurrentTransducer outputvoltageandCTsizeranges 1 Press to go to the CT SZ screen and through the digits Use or to select the CT size in amps default is 1...

Страница 11: ...r the short circuit current at the connection point All pulse inputs outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to ha...

Страница 12: ...Voltage Line to Line HZ HZ Frequency KSh KVAh Accumulated Apparent Energy KQh KVARh Accumulated Reactive Energy KPh KWh Accumulated Real Energy PLOSS PLOSS Phase Loss LOWPF LOWPF Low Power Factor Err...

Страница 13: ...erage of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A K...

Страница 14: ...B C Voltage Out of Range Current Out of Range Not used on E50Fx devices A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V O...

Страница 15: ...Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Wiring Diagrams section Set this value before setting the system voltage to establish the proper range of Sys...

Страница 16: ...ts To Setup p 1 S PWR SPLOS Back IMBAL 0 25 Next VOLTS 0 10 Set Phase Loss VOLTS Phase Loss Voltage Phase Loss Voltage Threshold in percent of system voltage Any phase as configured by the System Type...

Страница 17: ...oad these files separately Note If using resource files install them before importing the device template into a network Resources Available for Downloading The following instructions are written for...

Страница 18: ...and alarm configuration The second tab for configuration of the device is the Propagation Settings tab which includes configuration properties that control propagation heartbeat throttle etc Settings...

Страница 19: ...file exists and select the file 3 Press the Open button FormattingPowerCorrectly LonMark Resource Files before version 13 04 set the default format in the U S for network variables of the type SNVT_p...

Страница 20: ...Source of CP Values select LNS database Press Finish to complete commissioning Synchronization While Device is Commissioned and Online 1 Right click on the device in LonMaker and select Commissioning...

Страница 21: ...gin is not open right click on it and select Plugins Veris E50 Download Log from the context menu If it is already open click on the Data Logging tab 2 Expand the LOG INFO section 3 Press the RESET LO...

Страница 22: ...is OffNet the Data Logging tab will not be visible To show this tab click the Help menu and select Advanced Force Toggle Logging Visible 3 Expand the LOG SETUP section using the arrows on the right s...

Страница 23: ...To get only a specific amount of the newest records select the Fixed Amount of latest entries option and enter the desired amount in the textbox The log can hold 5760 records but both options stop dow...

Страница 24: ...r of them ConfiguringtheDevice All of the user defined configuration properties are implemented as configuration network variables so that they can be set as either configuration properties or as inpu...

Страница 25: ...y Throttle Real Energy Consumption Phase B integer value nvoRlEnrgyPhCInt 55 Meter SNVT_elec_kwh_l kWh Scaled 51 cpAllEnergy Throttle Real Energy Consumption Phase C integer value nviEnergyReset 34 Me...

Страница 26: ...0 Reset no more frequently than every 10 seconds VOLTAGE nvoAvgLLVoltage 73 Meter SNVT_volt_f Volt 269 cpAllVoltage Throttle Average Line to LineVoltage nvoAvgLNVoltage 74 Meter SNVT_volt_f Volt 271...

Страница 27: ...of range Bit 4 Phase B Current out of range Bit 5 Phase C Current out of range Bit 6 Frequency out of the range of 45 to 65 Hz or insufficient voltage to determine frequency Bit 7 Internal data bus c...

Страница 28: ...uble write first of the values saved from the previous cycle and then the present values If the read condition is not removed the meter continues to write the log data as it normally would This bit is...

Страница 29: ...ion Guide NV Name NV Num Function Block Type Units Log Point Index Propagation Control Description Configuration Property Name Control Type nviLogRequestLen 32 Meter SNVT_count Number of Records retri...

Страница 30: ...its UCPTdisplayUnits UCP_Type_4 w o resource files SNVT_count ref 13 R W Meter Function Block 0 1 1 IEEE Screen Display Units 0 IEC U V P Q S 1 IEEE VLL VLN W VAR VA cpCtPriRatio UCPTctPriRatio UCP_Ty...

Страница 31: ...ore than the number of updates specified is queued to be sent out in any 1 second period the excess updates are delayed until the next second to reduce network traffic This configuration property is p...

Страница 32: ...each power factor output network variable has its own independent throttle counter that resets to the value specified by this CP after it has been propagated cpFrequency SCPTminSndT 28 R W nvoFrequen...

Страница 33: ...e provided as a column in the network variable table above cpLoggingPoint3 UCPTlogPoint3 UCP_Type_15 w o resource files SNVT_count ref 25 R W Meter Function Block See description nvoPresRealDmnd 325 S...

Страница 34: ...ersions lower than 13 04 have the default format in the U S for SNVT_power_f variables in Btu hr See the section on Formatting Power Correctly The data displayed is inaccurate Incorrect setup values V...

Отзывы: