E34 Series Installation Guide

TM

1. BACnet MS/TP mode

The first three options are discussed previously. 

The DeviceID_Offset parameter is used to assign Device_IDs on power-up or on restart until they have been overwritten via 
BACnet.  Enter your desired value here and click 

Submit.

 The new value is first used at the next power-up or system restart. Valid 

Device_ID numbers range from 1 to 4194303. Since the numbers assigned during discovery are the sum of the Offset and the 
Modbus address (which can be any value from 1 to 247), the Offset values entered in the GUI must be no larger than 4194057.

The E34E gateway creates a BACnet virtual router and separate BACnet devices for each 42-channel meter panel behind this virtual 
router, allowing the devices to be discoverable and independently accessed via BACnet, even if the virtual router is connected by 
MS/TP, using a single MAC address. To use this product with MS/TP, the BACnet system must support the discovery and use of a 
BACnet router on the MS/TP trunk and any devices beyond it. This virtual router creates an exclusive BACnet network on which 
the meter’s BACnet devices reside. This network must have a BACnet network number that is different from any other networks in 
the entire BACnet enterprise. When multiple E34E products are added anywhere in the enterprise, each one must have a unique 
network number. If an exclusive value in this field is not set, communication conflicts in the BACnet system may occur.

Enter a non-conflicting value here and click 

Submit

. Valid network numbers range from 1 to 65534; if other values are entered, 

the network number defaults to 5. The new value is first used at the next power-up or system restart. If using an external BACnet 
router to connect the E34E as an MS/TP device, it is recommended that the router also be restarted after the E34E has completed 
discovery, when the network number is changed.  

The next field for the BACnet MS/TP protocol mode is the MSTP_Max_Master, which allows this value to be set prior to using 
BACnet software to access the E34E. The default value of 127 works regardless of the addresses the MS/TP network uses, but 
selecting a lower value may optimize the network. Do not set this value lower than the highest address on the network. To set this 

Gateway Configuration 
(cont.)

Содержание E34 Series

Страница 1: ...ng an RS 485 Modbus protocol E34E models also incorporate Ethernet with support for BACNet IP Modbus TCP and SNMP protocols and include BACnet MS TP serial capability and a sturdy metal enclosure The...

Страница 2: ...ference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment to an outlet on a circuit d...

Страница 3: ...Rate DIP switch selectable 9600 19200 38400 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position plug in connector TX TX SHIELD TX...

Страница 4: ...ons E34E Models FCC part 15 Class A EN6100 6 4 EN61326 1 Class A Conducted and Radiated Immunity EN 61000 6 2 and EN 61326 1 See Configuration section for details The E34 must be installed in an appro...

Страница 5: ...wledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Table of Contents Dimensions 6 Product Diagrams 7 Data Outputs 9 Blink Codes for Status LED 10 Installation 11 Wiring 15 Configu...

Страница 6: ...emarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Dimensions E34ABaseBoard 7 3...

Страница 7: ...L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Product Diagrams Dimensions cont 28 MeterCTAdapterAssem...

Страница 8: ...r 3 Control power fuse 600 Vac 500 mA time lag factory replaceable 4 Alive LED E34A models Red green amber LEDs Blink codes are described in the Blink Codes for Status LED section of this document 5 V...

Страница 9: ...2 or 3 channels that are adjacent in the panel to a logical meter referred to in the point map as a logical circuit that provides accurate multi phase measurement totals Map these logical circuits by...

Страница 10: ...ents Current multi phase average and per phase Current phase angle per branch Real power kW multi phase total and per phase Apparent power kVA multi phase total and per phase Power factor multi phase...

Страница 11: ...ons Read understand and follow the instructions before installing this product Turn off all power supplying equipment before working on or inside the equipment Product may use multiple voltage power s...

Страница 12: ...kets placed on the two sides for vertical mounting If desired you can move the brackets from the sides to the ends of the housing Loosen the screws on the sides of the E34 that hold the brackets in pl...

Страница 13: ...eherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Installation cont EQUIPMENT DAMAGE Do not use CTs with current mode outputs Failure to follow this instruction can r...

Страница 14: ...able ties are included with the product for strain relief on the E34A28 and E34E28 Insert the strain relief device into one of the available holes on the adapter board Figure 7A Gather all current sen...

Страница 15: ...f Treat all measurement circuits and CT connections as energized live Failure to follow these instructions will result in death or serious injury DANGER ESD SENSITIVE DEVICES Observe handling precauti...

Страница 16: ...being monitored without exceeding the limit For higher voltages e g 480 V line to line this must be supplied from a source that is 277 Vac or less It could be a separate source or a transformer can be...

Страница 17: ...Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Figure13 1 Connect 2 wire or 4 wire Modbus RS 485 daisy chain network Figures 14 and 15...

Страница 18: ...rated for the installation HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying equipment before working on or inside the equipment Use a properly rated voltage sensing device...

Страница 19: ...etwork must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 network If an address is selected that conflicts with another devi...

Страница 20: ...heVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installa...

Страница 21: ...gisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM DO NOT USE ZERO 1...

Страница 22: ...lying equipment before working on or inside the equipment Product may use multiple voltage power sources Disconnect ALL sources before servicing Use a properly rated voltage sensing device to confirm...

Страница 23: ...nd the E34E if they are not already connected Secure a ferrite filter included around the Ethernet cable to ensure the device meets emission requirements E34E 2 Temporarily change the IP address of th...

Страница 24: ...ris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation...

Страница 25: ...net mask Enterstatic IPaddress Entersubnet mask f Click OK 3 Open a PC web browser and enter the IP address of the E34E default address is 192 168 1 24 to access the GUI If this is the first time logg...

Страница 26: ...et BBMD device d Click the Update IP Settings button The E34E changes its settings e Click the System Restart button and wait for the E34E to fully initialize The GUI will connect when the E34E is ins...

Страница 27: ...tocols the product communicates with The E34E supports five protocols some of which can operate simultaneously The table below shows which protocols are supported in each mode Protocol Mode Primary Pr...

Страница 28: ...e MAC address To use this product with MS TP the BACnet system must support the discovery and use of a BACnet router on the MS TP trunk and any devices beyond it This virtual router creates an exclusi...

Страница 29: ...addresses on the MS TP network The final field for the BACnet MS TP mode is RTC_Control which selects which protocol BACnet or Modbus has write access to the RTC If 0 BACnet is selected the RTC is set...

Страница 30: ...atever values are entered here must also be used in the MIB browser or SNMP access software to communicate with this device The Read_Community string is used to enable reading data The Write_Community...

Страница 31: ...m 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID number that is unique throughout the entire enterprise Sin...

Страница 32: ...Data Sharing WriteProperty B DS WP B K 1 10 BIBB Data Sharing WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2...

Страница 33: ...e Object_name property The E34E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specific application writ...

Страница 34: ...rs and to the data set under Modbus address 2 or BACnet device identified as Node_2 in the GUI For each panel data is arranged under six tree branches The Configuration branch contains all writable co...

Страница 35: ...sswords to help prevent unauthorized access to device settings and information Disable unused ports services and default accounts where possible to minimize pathways for malicious attacks Place networ...

Страница 36: ...control system provides the capability to Manage connections through managed interfaces consisting of appropriate boundary protection devices such as proxies gateways routers firewalls and encrypted...

Страница 37: ...zation or contact your network administrator for example maximum password age or history policies DefaultPasswordandUserAccounts Accessing the GUI for the First Time with Firmware Version 1 027 or Hig...

Страница 38: ...TLS certificate recommended and most secure mode Once this mode is selected the user can drag and drop their own SSL Certificate and Private Key files into their respective fields If the Private Key...

Страница 39: ...rd tab Enter the new alphanumeric complex password in the Password and Confirm Password fields Click Confirm to save the changes To confirm the changes click the Logout button and access the GUI with...

Страница 40: ...your network administrator to determine a responsible method of disposal Dispose the device according to the legislation of the country Some regulatory organizations include The United States Environm...

Страница 41: ...ufficient biasing on the Modbus bus Modbus physical specification calls for 450 650 biasing This is usually provided by the master The main board has a slow flashing amber light E34A models One or mor...

Страница 42: ...Guide TM China RoHS Compliance Information Environment Friendly Use Period EFUP Table SJ T11364 O GB T 26572 X GB T 26572 This table is made according to SJ T 11364 O indicates that the concentration...

Отзывы: