NOTE:  This product is factory calibrated. The typical CO

2

 sensor calibration interval 

is 5 years, depending on specific site installation factors. As of the date of this 
document, compliance with ANSI/ASHRAE 62-2001 requires minimum on-site 
accuracy verification intervals of 6 months or per the building operation and 
maintenance manual. Accuracy verification should be performed using either a 
comparison to a known reference or the CO

2

 gas calibration kit available from Veris 

Industries as model AA01.

WARNING:  CO

2

 sensor calibration requires a gas calibration kit. Performing calibration 

without a gas kit will cause erroneous readings. Consult factory for calibration kit.

Select 0 ppm Cal Gas option.

4.  

Continue flowing gas through the sensor. Estimated calibration time is 5 minutes. 

5.  

Unit returns to run mode when calibration is complete.

















CWL

CDL

for cdl/cwl devIce wIth Pear-

ShaPed SenSor

Remove cover to the device.

1.  

Connect hose to plastic port located on sensing module and flow gas (Nitrogen) O  

2.  

ppm CO

2

 gas through the sensor.

















Connect hose here

CWL

CDL

NITROGEN

GAS

Regulator

Valve









Push and hold plus and minus buttons for 5 seconds to enter Calibration mode. At 

3.  

each menu option, use the arrow to change values. Push enter for next option.

E

X X

R

X

X

X X X X

S

A L

I

X

X X

X

X

X X

X

Displays serial number

Displays model number

Range is -5 to 5

°

C , 

0.1

°

C increment

Range is -10 to 10%,
0.1% increment

Options are Yes/No

Options are None, 0, 400

Unit will automatically return to run 
mode when calibration is complete.

CWL ONLY