for cde devIce wIth Pear-ShaPed
SenSor
Connect hose to plastic port located on sensing module.
1.
Connect hose here
Start flowing (Nitrogen) 0 ppm Gas (0 ppm only).
2.
NITROGEN
GAS
Regulator
Valve
Push and hold down calibration button until the LED illuminates.
3.
Push and hold down calibration button
Green LED
Continue flowing gas through the sensor until the LED is off - estimated Calibration
4.
time is 5 minutes.
for cwe devIce wIth Pear-ShaPed
SenSor
Connect hose to plastic port located on sensing module.
1.
Connect hose here
Start flowing (Nitrogen) 0 ppm Gas (0 ppm only).
2.
NITROGEN
GAS
Regulator
Valve
Push and hold down calibration button until the LED illuminates.
3.
Push and hold down calibration button
Green LED
Continue flowing gas through the sensor until the LED is off - estimated Calibration
4.
time is 5 minutes.