Monitor ISM/xL™ Hardware Guide 

23 

SN#:1B3414

    

Edit

Save  

  

Pxxx

 

This screen will then 
display: 

 

SN#:1B3414:

 This is 

        

 

the Serial Number of the sensor that was enrolled 
into this input number. 
Pressing the keypad right arrow button will display 
the

 

SVN:0 TMP:

 

IN:

 

screen for editing. The 

Del

‘ button can also be pressed to remove the 

sensor and another sensor could be programmed 
for this input number if desired.

 

 

Equipment/Pseudo Point Selections for Wireless V2  

Module Trouble

 (E011), ensure this is set to detect: 

 

Module Bus connection to V2 module failure. 

 

V2 module failure. 

 

V2 module has not received any sensor signal for X 
amount of time (

AllSVN

). 

Module Battery Low

 (E012), ensure this is set so 

‘Senor Low Battery’ will be detected. 

Module Program Edit

 (E013) can be optionally set to 

detect when the sensor settings have been changed. 
This alert will not re-set until there have not been any 
further program changes for one hour. 

LCD Keypad Status 

 

Enter ‘Status’ at the system’s LCD keypad. 

 

Press the keypad’s right arrow key until 

App 

(Application Module) displays. Press the keypad 
button under it. 

 

When 

Wireless2

 or 

WL2

 displays, press the button 

under 

Yes

 

Keypad left and right arrow keys can be pressed to 
scroll through the input numbers and V2 module 
conditions. 

Input Number Status 

 

The input number range associated with the V2 will 
display and the input’s condition e.g. 

009

Ok

 

It can also display the following for an input: 

  ‘

NoSvn

‘ No Supervision. A sensor supervision signal 

failure. The input will appear in point status as a 
tamper.   

  ‘

Lobat

‘ Low senor battery. This will generate a 

module or pod low battery alert. If the sensor’s 
battery was replaced, the sensor’s reset button on 
its printed circuit board must be pressed. 

  ‘

Not Enrolled

‘ A sensor is not programmed to 

this input. The input will appear in point status as a 
tamper. Delete the input if it will not be used. 

  ‘

NoRcv

‘ No Receiver detected. V2 module 

malfunction. 

  ‘

PtTmp

‘ Input sensor tamper. The input will appear 

in point status as a tamper. 

V2 Module Status 

 

After scrolling through all the V2 input conditions, the 
condition of the V2 module will display: e.g. 

Pod

Ok

.  

 

It can also display the following for a module: 

  ‘

NoSvn

‘ The V2 module is not communicating on the 

module bus. 

  ‘

NoSen

‘ The V2 module has not received 

communication from its sensors, based on the 
supervision delay period set for the V2 module 
(

AllSVN

). 

 

Module Status will display the V2 module in tamper 
for either of these conditions.  

V2 Test Menus 

 

Log on to the system LCD keypad as a Service 
User. 

 

Select ‘

Test

‘ from the Menu and 

App 

 WL2

 or 

Wireless2.

 

Check      (X.Xx)

Signal 

Scan 

 

This screen will display: 

 

(X.Xx)

 indicates the V2 

firmware version number.    

 

 

Signal

‘ selects a sensor signal strength menu.  

xxx

 < > 

Si 

>

 

3 OK

   

Signal 014 of 21 

 

Pressing ‘

Signal

‘ will 

 display 

this 

screen: 

 

xxx

 represents an        

 

  input sensor number on the V2 module. 
 

< > 

keypad left and right arrow keys can be pressed 

to scroll through the input numbers. 

 

Si

(gnal)

 

>

 3 OK

 

is an example of the V2 receiver 

getting an adequate signal strength from the sensor. 

xxx

 < > 

Si 

>

 

4 Weak

 

Signal 001 of 21 

 

This screen is an example 

  of the V2 receiver getting 

an inadequate signal from 
the sensor.        

 

 

The second line in both screens displays the actual 
signal strength measured on a scale of 000 to 021 
(maximum). 

 

If a sensor has not been enrolled in an input 

number, 

Not Enrolled

 will display on the top line. 

 

Scan

‘ selects an RF scanning menu. 

 

When ‘

Scan

’ is pressed the screen will display 

 ‘ 

Waiting...

’ to receive an RF transmission from 

any sensor. NOTE: if this screen never changes, it is 
possible the V2 module is not working properly. 

SN#:1B3414 LEARN 

AA BB 

 

If this screen displays 

when a signal is received, 
it is from a sensor that has 

 

  not been enrolled in the system, indicated by 

LEARN. SN#:1B3414

 is the sensor’s unique serial 

number.  

SN#:1B3414*P#xxx 

AA BB 

 

If this screen displays 
when a signal is received, 
it is from a sensor that is 

 

  enrolled in the system, indicated by 

P#xxx

 where 

xxx

 is the input number. 

 

Either an asterisk or a blank will display after a 
sensor’s serial number as it toggles every time a 
transmission from a different sensor is received. 

 

In either screen, ‘

AA BB

‘ is changing data that can 

be ignored. It is for internal Engineering use only. 

Содержание ISM/xL

Страница 1: ...Monitor ISM xL Hardware Guiderev1 1...

Страница 2: ......

Страница 3: ...odules 32 Version 1 Door Module 32 Version 2 Door Module 33 Multi Door Controller 34 Elevator Lift Modules 35 Communication Modules 42 Printer 42 IP Module V3 43 MONITOR System Reference Topics 45 Add...

Страница 4: ...r Guide Specific installation and programming instructions produced for each module by part number are referenced at the beginning of each module s section in this manual VEREX Technology 5201 Explore...

Страница 5: ...22 0375 rev1 1 Monitor ISM xL Hardware Guide 1 Part 1 Monitor ISM System Hardware...

Страница 6: ...INLET Use plastic 3 4 in bushings P N 364 5100 to insert in knockouts before bringing in cables Metal Enclosure Main Control Board TB1 TB4 TB2 TB3 TB6 1 4 3 2 1 2 TB9 TB8 TB7 TB10 TB16 TB13 TB12 TB11...

Страница 7: ...Red and Black NOTE This is Bus power and must not be overloaded Piezo sounder is one volume only and not adjustable There is no Bus communications LED indicator on the PCB board as whether the LCD dis...

Страница 8: ...ole paper clip example Reader back Raised Area wall plug screw anchor wall plug screw anchor Hole cut in drywall for reader back raised area Mounting On Drywall WARNING Insert wall anchors FIRST befor...

Страница 9: ...entry Key Sequence Command login only Access momentary unlock of door 1 login Turn area off 1 0 login Turn all areas off 2 login Turn area to stay mode 3 login Turn area on 3 0 login Turn all areas on...

Страница 10: ...ess area without using card enter 001 1234 for user 001 with pin 1234 Using Duress Pin at Arming Station A Duress Pin reversing last 2 digits of a user s pin entered on the keypad to transmit a potent...

Страница 11: ...for a Module negative BUS connection or input point common connection E g this black could be used to connect input 1 and 2 s common connection A local power supply s negative connection can be connec...

Страница 12: ...output driven device E g electronic siren with built in driver Input 1 e g Main entrance door contact Programmed and wired as normally open with 2 2K end of line resistor Input 2 e g Motion detector a...

Страница 13: ...key and then one of these keys will silence the arming tone f function key 1 2 or f Output control Pressing 1 can turn on output 1 and 2 can turn on output 2 depending on configurations Repeat to turn...

Страница 14: ...s on Output 2 is a standard output that turns on 12VDC when it is enabled It has a low current rating of 25mA to trigger e g a low current relay Input points can be configured as normally closed or op...

Страница 15: ...alarm fire burglary When the area is in alarm output 1 will trigger and supply power to run the siren The maximum number of Suite Security Modules that can be connected to one Main Panel is 60 and is...

Страница 16: ...e 10 outputs with Annunciator Output Board 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 LED 9 LED 10 LED 11 LED 12 LED 13 LED 14 LED 15 LED 16 O P9 TB1 TB2 0V O P10 0V O P11 0V O P12 0V O P13 O P14 O P15 O P16 0V...

Страница 17: ...rd with the 8 pt Expander the pod is configured with 16 outputs and outputs 1 and 2 on the board can be programmed Outputs 3 to 8 must be skipped as they do not exist Programming for the card would th...

Страница 18: ...ber of input points for the number of sensors being used Do not assign outputs as there are none Turn on tamper and all other settings may remain defaulted Exit the Module programming and then go back...

Страница 19: ...help screen what module the point you are at is connected to E g screen displays 002 module 2 Wireless RF module p013 016 input point range 13 to 16 S 10097 5 digit module address Outputs do not show...

Страница 20: ...Cnt56DB5 door window contact and its address 014 input 14 80 02 4 sensor transmit codes Press XESC escape to return to the TEST screen Press Signal Activate a sensor Screen indicates signal strength...

Страница 21: ...mper Radio Antennas Interconnection Radio Receiver Board Interface Board Valid Decode LED Decode LED Diagnostic LEDs See NA Module Notes 1 4 3 2 Plastic base cable inlet knockouts Back knockout Side k...

Страница 22: ...d the box tamper is disabled Diagnostic LEDs Yellow LED Green LED Condition Description 0 to 9 pulses to indicate module serial number 5 digit value On for 1 second per serial number digit Module Seri...

Страница 23: ...is jumper out 1 4 3 2 Box Tamper Spring Interconnection Data Send to Interface board LED 1 or 2 Receiver Jumper Position 1 Position 2 1 2 Interface Board Radio Receiver Board Receiver 1 Receiver 2 Eur...

Страница 24: ...eceiver Board Version Radio Brd Tamper Spring Radio Antennas Decode LED See Module notes Radio Brd Tamper Spring TX RX Transmit Receive to Interface Brd LEDs New Zealand Australia Ensure the location...

Страница 25: ...correct The repeater module is used to increase the range of transmitting and receiving signals Mounting for the Repeater is the same as the Receiver as it is in the same plastic enclosure Follow the...

Страница 26: ...the Director software and sent to the panel If the circuit type sensor type and name have been programmed into the system with the LCD keypad and Save is pressed the next screen below will display If...

Страница 27: ...V2 Module Status After scrolling through all the V2 input conditions the condition of the V2 module will display e g Pod Ok It can also display the following for a module NoSvn The V2 module is not c...

Страница 28: ...card With jumper settings illustrated inputs can be wired class A A short between the 2 loops wired between normally open connections alarm Either loop opening tamper Most commonly used to monitor wa...

Страница 29: ...ot normal point in alarm It could also be used to make alpha numeric labels that can have the LEDs turn on next to them for various area point indications E g Area 1 ON Area 2 STAY When the diagram is...

Страница 30: ...n LED Green LED Green LED Yellow LED Yellow LED Yellow LED LED position IDs on face correspond with those on PIN strip All LEDs are RED except as shown MANUFACTURING FLOOR AREA Using the Graphic Map M...

Страница 31: ...en yellow black Tamper Pins TX RTS RX CTS 12V 0V 0V CTS RTS RX TX Printer F1 1 2 AMP P N 342 3356 Module Bus Data A Data B 12V 0V red green yellow black F2 1 AMP P N 342 3350 1 4 3 2 red green yellow...

Страница 32: ...g NOTE A Vigil Concentrators can be any of a number of varied types of modules used in a Vigil System Similar to the Modules used with a MONITOR System Module Programming The Smart Vigil Module is cap...

Страница 33: ...ble conc1 with the cursor under this box press LCD keypad left or right arrow keys press any key number to make the box a to enable the conc T is it necessary to test a seismic connected to this conce...

Страница 34: ...7 3 27 37 7 67 77 C 28 36 C 60 68 28 38 68 78 29 37 61 69 29 29 69 69 30 38 62 70 30 30 70 70 4 31 39 8 63 71 C 31 41 C 71 81 32 40 64 72 O 32 42 O 72 82 N 33 43 N 73 83 C 34 44 C 74 84 35 45 75 85 36...

Страница 35: ...L B will do a printer port loop back test the same as the HSC loop back test on the HSC Printer module discussed later in this manual to test printer hardware integrity Smart Vigil Concentrator Tests...

Страница 36: ...D Data 1 Clock Ground 0V Data 0 Door Unlock Relay Auxiliary Relay Reader Reader 2 DOOR ACCESS MODULE Reader Connection Example HID Thin Line II Proximity Reader yellow blue vilolet not used Auxiliary...

Страница 37: ...0mA min 200mA with all 4 relays and their indicator LEDs energized Remember to add reader current Example readers are 110mA X 2 220mA Two readers per each door would be 440mA This board s total curren...

Страница 38: ...ng at least 18 AWG wire Do not connect anything else to the earth ground Connect the Module Bus cable shields together inside each cabinet and only connect the shield to earth ground at the ISM panel...

Страница 39: ...pply P N 110 5560 ence Side terference Side and electric TXMRs ONLY Run cables in conduit between boxes Run cables in conduit between boxes 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 3 3 1 3 1 1...

Страница 40: ...s on the Elevator Module NOTE Floor Selection Relay Wiring Floor relays must be wired in the same relative order for all elevators such as lowest to highest as accessed from each specific cab Remember...

Страница 41: ...B4 TB9 TB7 TB3 TB2 TB13 TB14 TB11 TB12 TB16 TB15 0V Neg 0V Neg Fire Bypass RS485 Reader Connections for reader runs over 500 ft See following Wiegand to RS485 Interface Board Reader Voltage Jumper Mod...

Страница 42: ...2 1 4 3 2 1 4 3 2 1 1 2 1 2 1 2 3 2 1 3 2 1 4 5 6 3 2 1 4 5 3 2 1 4 5 Elev1 2 Data 1 5 12 VDC Spare Common TB1 TB10 TB4 TB9 TB7 TB3 TB2 TB13 TB14 TB11 TB12 TB16 TB15 0V Neg 0V Neg Fire Bypass Module B...

Страница 43: ...meters connect to these isolator board terminal blocks 9 and 7 installed on Elevator Cab roof NOTE Maximum length of cable allowed for 485 operation may be lower due to cable capacitance characterist...

Страница 44: ...or Isolator Board P N 641 9036 Elevator Isolator Board P N 641 9036 Cabinet Frame Tamper Switch SEE NOTES J 5 J 4 J 3 J 2 J 1 J 6 J 7 J 8 J 5 J 4 J 3 J 2 J 1 J 6 J 7 J 8 J 5 J 4 J 3 J 2 J 1 J 6 J 7 J...

Страница 45: ...ired Spare GND Lug Move as required Shipped as pre wired for 2 elevator cab systems to add 16 floors when 3 additional relay boards are added to this box To change to a single elevator cab system and...

Страница 46: ...art the printer Press Save Printer Specifications Type RS232 serial 80 columns or more Data Setup 1 start bit 1 stop bit 8 data bits no parity baud rate selectable recommend 1200 hardware handshake Pr...

Страница 47: ...C Orange RS232 RX SIP Yellow RS485 B Dir Sftwr Blue RS232 TX SIP Green RS485 A Director Sftwr Red Black Neg GND These 4 mounting holes for new V3 brd installation adhesive stand offs These 3 mounting...

Страница 48: ...DSR TX TX RI RI CD CD TB16 1 4 3 2 3 1 2 RX RX Main Panel 2 motherboard Main Panel 3 motherboard TB15 TB14 TB15 TB14 TB15 TB14 V3 IP Interface Module Connections at Monitor Motherboard When installin...

Страница 49: ...ert into free serial port on the specific PC NOTE The A and B connections are one to one DB9 insert into free serial port on the specific PC Previous Version RS485 Converter P N 11 0343 12V 0V Data B...

Страница 50: ...46 Monitor ISM xL Hardware Guide 22 0375 rev1 1...

Страница 51: ...22 0375 rev1 1 Monitor ISM xL Hardware Guide 47 Part 2 Monitor xL System Hardware Please Note Modules in the previous Monitor ISM System section are also compatible with the Monitor xL System...

Страница 52: ...the control box Secure the 12V 7 0Ah battery with the securing bracket p n 232 2605 and screws from the supplied accessories kit For a 17Ah battery bracket order kit 250 3617 during service heat sink...

Страница 53: ...Modem Expansion Socket World Wide Modem 7 5 6 8 0V Line Failure 9 3 1 2 4 Output 8 Output 7 Output 6 Output 5 Output 4 Output 3 Output 2 Output 1 To REDCARE Unit 01 1 2 3 2 vertical Jumpers in 1 2 Ou...

Страница 54: ...ons S005 03 Field 2 Parallel STU 8OP Supports Line Fail yes no Default no UK ACPO yes Field 3 Parallel STU 8OP Line Fail Negative Polarity yes no Default no Positive Polarity Enable Equipment failure...

Страница 55: ...V OUT 12V 0V Wiegand 1 4 3 2 5 6 D1 D0 1 4 3 2 5 6 A B 0V OUT 12V 0V 0V PT1 PT2 Keypad Terminal Block Wiring Module Bus Module Bus Output Input 1 Input 2 Common Wiegand Reader Data 1 and 0 No reader L...

Страница 56: ...ux r e d b l a c k y e l l o w g r e e n Module Bus SNAPP 5 digit serial number to program in Module Programming XXXXX Not used Tamper Spring Rear Tamper on back of board P1 IN Disables Wire short to...

Страница 57: ...2 3 1 2 3 1 2 TB6 TB7 TB8 TB9 P5 P4 P3 P2 This unjumpered connector for factory use only Do not jumper Relay LEDs turn on when relays activated Turn on off with P5 test jumper in Processor OK LED with...

Страница 58: ...tamper spring to fit inside the cap The cap will insert in the metal cabinet s tamper spring knock out hole Complete securing the metal cabinet to the mounting surface Rear Tamper on back of board Mom...

Страница 59: ...he system will ignore battery monitoring IMPORTANT This jumper must be left OUT for battery monitoring OUT Module Bus SNAPP VBUS VBUS Main Control Unit MASTER P4 P5 in SLAVE P4 in P5 out SNAPP only P4...

Страница 60: ...ing resistor will need to be installed across A and B communication terminals of the last module on the bus cable If necessary add a second resistor at the panel end module bus A and B if it is confir...

Страница 61: ...transmitted because there is no resistor If the device is triggered in an on guard armed state an alarm condition is transmitted because there is no resistor Form C Single Resistor EOL Normally Open...

Страница 62: ...th MS Windows or any other terminal emulation program that you may be familiar with Note Ensure you have the specific modem with you and a suitable modem cable for connecting it to the PC This must be...

Страница 63: ...y to be used with a system panel You can unplug the modem and shut down the HyperTerminal program when ready To shut down HyperTerminal open the File menu and select Exit If prompted to save your chan...

Страница 64: ......

Страница 65: ......

Страница 66: ...N3459...

Отзывы: