Caution! - Do not make
CAL.L
and
CAL.H
the same value as the
controller will not work correctly and could cause the furnace or oven
to overheat.
3.8.5
Changing the Calibration, Low Temperature -
CAL.L
l
Start at the home display.
l
Hold the Page Key for 1.5 seconds to access the Setup Menu.
l
Press the Page key until
CL.St
is displayed.
l
Press the up or down Arrow keys to display the current cal-
ibration offset.
l
If a password is required to access
C.CL2
, enter the password
using the up and down Arrow keys and press the Page key to
accept. You will be returned to
CL.St
.
l
Use the up and down Arrow keys to scroll to
C.CL2
.
l
Press the Page key to access
CAL.L
.
l
Press the up or down Arrow keys to change the offset value.
l
The value will then be stored without any further input.
Once
C.CL2
has been selected as the customer calibration type, it is possible to start
from the home display and go to
CAL.L
directly (or any of the other settings in
C.CL2
)
and enter the password at this point when calibration adjustment is required again.
3.8.6
Changing the Calibration, Low Temperature Offset -
OFS.L
l
Start at the home display.
l
Hold the Page Key for 1.5 seconds to access the Setup Menu.
l
Repeatedly press the Page key until
CL.St
is displayed.
l
Press the up or down Arrow keys to display the current cal-
ibration offset.
l
If a password is required to access
C.CL2
, enter the password
using the up and down Arrow keys and press the Page key to
accept. You will be returned to
CL.St
.
l
Use the up and down Arrow keys to scroll to
C.CL2
.
l
Press the Page key twice to access
OFS.L
.
l
Press the up or down Arrow keys to change the offset value.
l
The value will then be stored without any further input.
3.8.7
Changing the Calibration, High Temperature -
CAL.H
l
Start at the home display.
l
Hold the Page Key for 1.5 seconds to access the Setup Menu.
l
Repeatedly press the Page key until
CL.St
is displayed.
l
Press the up or down Arrow keys to display the current cal-
ibration offset.
l
If a password is required to access
C.CL2
, enter the password
using the up and down Arrow keys and press the Page key to
accept. You will be returned to
CL.St
.
l
Use the up and down Arrow keys to scroll to
C.CL2
.
l
Press the Page key three times to access
CAL.H
.
l
Press the up or down Arrow keys to change the offset value.
31