7
Unit technical data
Parameter
VUT
350 H
VUT
500 H
VUT
530 H
VUT
600 H
VUT
1000 H
VUT
2000 H
Unit supply voltage, 50 Hz [V]
1~ 230
Total unit power [W]
260
300
300
390
820
1300
Total unit current [A]
1,2
1,32
1,32
1,72
3,6
5,68
Max. air capacity, m
3
/h
350
500
530
600
1200
2200
PRM
1150
1100
1100
1350
1850
1150
Sound pressure level at 3 m distance [dB(A)]
24-45
28-47
28-47
32-48
60
65
Transported air temperature [°C]
from -25 up
to +55
from -25 to +50
from -25 to
+55
from -25 to +40
Casing material
aluzinc
Insulation
25 mm mineral wool
50 mm mineral wool
Extract filter
G4
Supply filter
F7
G4(F7)*
G4(F7)*
Replaceable filter G4*
SF VUT 350-600 H G4
SF VUT 1000
H G4
SF VUT 2000
H G4
Replaceable filter F7*
SF VUT 350-600 H F7
SF VUT 1000
H F7
SF VUT 2000
H F7
Summer block* VL VUT 350 H
VL VUT 500-600 H
VL VUT1000
H
VL VUT2000
H
Connected air duct diameter [mm]
Ø125
Ø150
Ø160
Ø200
Ø250
Ø315
Weight [kg]
45
49
49
54
85
96
Heat recovery efficiency, %
up to 78
up to 88
up to 88
up to 85
up to 88
up to 87
Heat exchanger type
cross flow
Heat exchanger material
Aluminium
*extra summer blocks and sets of replaceable filters are optional extras and can be purchased separately.
Содержание VUT 1000 H