Connect the switch according to the wiring diagram (see page 12).
Place the executive part of the switch into the mounting box.
Secure the executive part of the switch by means of two screws (included in the delivery set).
Cover the executive part of the switch with the decorative front panel and secure the panel by pressing the panel surface over
the latches until they snap in place.
CONDENSATE DRAINAGE
DO NOT CONNECT SEVERAL DRAIN PIPES FROM SEVERAL AIR HANDLING
UNITS TO ONE U-TRAP! DIRECT CONDENSATE DRAINAGE OUTSIDE WITHOUT
CONNECTION TO SEWAGE SYSTEM IS NOT ALLOWED.
The unit must be connected to a drainage system. Connect the drain pipe, the U-trap (not included in the standard delivery set) and
the sewerage system with metal, plastic or rubber pipes. The pipes must be installed at the minimum downward gradient of 3°. The
recommended U-trap sizes are given in the table:
Unit model
Minimum dimensions, [mm]
А
B
VUT 350 … 600 H
120
60
VUT 1000 … 2000 H
200
110
Before starting the unit fill the system with water and check that the U-trap is always filled with water. Make sure that the water drain-
age is correct. Wrong connection to sewage system may result in condensate accumulation inside the unit.
The condensate drainage system is designed for operation at the ambient temperature above 0 °C!
If the ambient temperature is below 0 °C, the condensate drainage system must be heat insulated and pre-heated.
Drain pipe
U-trap
Sewage system
1°.. 3
°
A
B
1°.. 3
°