www.vents-us.com
12
CONNECTION OF SEVERAL VENTILATORS IN SERIES
Connection of the ventilators in series enables controlling all the connected ventilators by the first ventilator and the common remote control. For
connection of several in series follow the diagram below. Connect the second ventilator with the third ventilator in the same way, etc. Maximum 10 ventilators
may be connected in series.
For electric installations use a power cable with the minimum wire cross section 0.5 mm
2
and a control cable with the minimum wire cross section 0.25
mm
2
. The cables are not included in the delivery set.
The cable must be rated for operation in an alternating current power supply with the country-specific mains voltage.
Disconnect the power cord while connecting the second, third, etc. ventilator in series.
INPUT
OUTPUT
L
G
D
N
L
G
D
N
INPUT
OUTPUT
L
G
D
N
L
G
D
N
1~100-230 V/50-60 Hz
Power cable
to the next ventilator
Control cable
to the next ventilator
to the ground
terminal
to the ground
terminal
to the ground
terminal
to the ground
terminal