background image

13

www.vents-us.com

Air flow diagram for Frigate HRV/ERV 80/120/100/150 R (EC) in recirculation mode

(the swivel service panel is conventionally not shown)

SPEED CONTROL

FUSE 1

FUSE 2

MED

LOW

STANDBY

1 2 3 4 5 6 7 8 9 101112

FUSE

FUSE

AIR SUPPLIED TO ROOM

STALE AIR FROM ROOM

FRESH AIR FROM OUTSIDE

UTILIZED EXHAUST AIR

Air flow diagram for Frigate HRV/ERV 80/120/100/150 R (EC) L in recirculation mode

(the swivel service panel is conventionally not shown)

SPEED CONTROL

FUSE 1

FUSE 2

MED

LOW

STANDBY

1 2 3 4 5 6 7 8 9 101112

FUSE

FUSE

AIR SUPPLIED TO ROOM

STALE AIR FROM ROOM

FRESH AIR FROM OUTSIDE

UTILIZED EXHAUST AIR

The removable service panel enables repair and maintenance works.
Access to the control unit for mounting and connection is made through the removable front panel of the control unit. The power and 
earth cables are connected to the control unit via the cable glands.

Modifications of heat recovery cores:

• 

HRV

 heat recovery core transfers sensible heat energy (temperature) from one air stream to another. The heat energy extracted from 

the indoor air is transferred to the incoming fresh air, thus increasing or decreasing its temperature. The air streams remain fully isolated 
from each other. This heat recovery core is made of polystyrene. Heat recovery minimizes ventilation heat losses and saves heating costs 
in cold seasons and air conditioning costs in summer.
• 

ERV

 heat recovery core transfers sensible heat energy (temperature) and latent heat energy (humidity) from one air stream to another. 

The latent heat energy (humidity) is transferred in the same way as the temperature. As the opposite air streams have different temperature 
and humidity, they also have different surface vapor pressure. The vapor pressure difference enables transfer of the vapor pressure. 
The main advantage of the energy recovery cores is the ability to recover humidity (latent energy). This energy recovery is possible 
during the air conditioning and air heating seasons. During the air conditioning season, the incoming air from outside is dehumidified 
and cooled down. That significantly reduces operating load for the air conditioners. During the heating season the heat recovery core 
performs reverse and the incoming air from outside is humidified and heated. The heat recovery technology cuts high expenses for air 
humidification and air heating.
The energy recovery core is based on polymer membrane. The membrane enables transfer of the water molecules hence they have high 
dielectric constant and small sizes. The water vapor extracted from the humid air is condensed on the cold membrane surface. Water 
condensation takes place at temperatures above the dew point. The liquid water molecules are moved through the membrane. The 
humidity concentration differential between the warm and cold air streams enables this movement process. The humidity is vapored 
away from the membrane surface and is absorbed by the dry air stream. Microbes cannot get through the membrane as their size is 
much bigger compared to water molecules. Bacteria, fungi, mould and microbes cannot reproduce on the membrane material. Microbes 
die on the membrane surface within several hours. The ultra thin membrane serves to decrease air speed in the heat recovery core and 
increases high heat and humidity recovery efficiency.

The temperature difference between the supply and extract air streams leads to condensate formation. It is collected in the drain pan 
and is removed through the drain pipe. 

Содержание ERV 100

Страница 1: ...Heat and energy recovery air handling unit USER S MANUAL HRV 80 R EC L HRV 100 R EC L HRV 120 R EC L HRV 150 R EC L ERV 80 R EC L ERV 100 R EC L ERV 120 R EC L ERV 150 R EC L...

Страница 2: ...ons Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as con...

Страница 3: ...ONTACT THE SELLER DO NOT DIRECT THE AIR FLOW PRODUCED BY THE UNIT TOWARDS OPEN FLAME OR IGNITION SOURCES IN CASE OF CONTINUOUS OPERATION OF THE UNIT PERIODICALLY CHECK THE SECURITY OF MOUNTING USE THI...

Страница 4: ...REE OPERATION OF THE UNIT USER S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT THE PAYMENT DOCUMENT AND THE USER S MANUAL WITH THE PURCHASE DATE STAMP TO REDUCE THE RIS...

Страница 5: ...ses summer gardens and other spaces with high humidity Due to the ability to save heating energy by means of energy recovery the unit is an important element of energy efficient premises The unit is a...

Страница 6: ...rigate ERV 100 Frigate ERV 100 R Frigate ERV 100 EC L Frigate ERV 100 R EC Frigate ERV 120 L Frigate ERV 120 R Frigate ERV 120 EC L Frigate ERV 120 R EC Frigate ERV 150 Frigate ERV 150 R L Frigate ERV...

Страница 7: ...7 16 47 16 47 16 17 9 1 2 91 16 47 8 3 13 16 9 1 2 20 13 16 Frigate HRV ERV 80 R EC 91 16 87 16 43 4 291 16 251 16 47 16 17 3 16 9 1 2 47 8 3 13 16 8 1 4 20 13 16 Frigate HRV ERV 120 EC L 95 8 9 315 1...

Страница 8: ...5 8 9 43 16 9 16 3015 16 347 8 20 1 16 13 16 511 16 47 8 3 9 16 23 7 8 12 3 8 Frigate HRV ERV 100 150 EC L 95 8 91 8 45 8 11 13 16 45 8 21 3 8 273 4 313 4 25 1 8 11 13 16 47 8 Frigate HRV ERV 100 150...

Страница 9: ...ology minimizes heating costs during the cold season Assembly drawing for Frigate HRV ERV 80 and air flow diagram in heat recovery mode SPEED CONTROL FUSE 1 FUSE 2 MED LOW STANDBY 1 2 3 4 5 6 7 8 9101...

Страница 10: ...ry mode SPEED CONTROL FUSE 1 FUSE 2 MED LOW STANDBY 1 2 3 4 5 6 7 8 9101112 FUSE FUSE AIR SUPPLIED TO ROOM STALE AIR FROM ROOM FRESH AIR FROM OUTSIDE UTILIZED EXHAUST AIR Supply fan Supply filter Extr...

Страница 11: ...act filter Swivel service panel Control unit Extract fan Cross flow heat recovery core Condensate drain pipe Assembly drawing for Frigate HRV ERV 100 150 EC and air flow diagram in heat recovery mode...

Страница 12: ...E SPEED CONTROL FUSE 1 FUSE 2 MED LOW STANDBY 1 2 3 4 5 6 7 8 9101112 FUSE FUSE AIR SUPPLIED TO ROOM STALE AIR FROM ROOM Supply fan Recirculation damper Supply filter Backdraft damper Swivel service p...

Страница 13: ...ent temperature and humidity they also have different surface vapor pressure The vapor pressure difference enables transfer of the vapor pressure The main advantage of the energy recovery cores is the...

Страница 14: ...est performance of the unit and to minimize turbulence induced air pressure losses while mounting connect a straight air duct section on both sides of the unit Minimum straight air duct length equal t...

Страница 15: ...ge system using metal plastic or rubber hoses While laying the hoses provide the slope downwards min 3 Prior to commissioning the unit make sure the water runs smoothly in the sewage system otherwise...

Страница 16: ...fuses 3 15A glass 5x20 and 0 5A glass 5x20 They are used for overload protection in case of an overload or a short circuit To replace the fuse disconnect the ventilation unit from power supply replace...

Страница 17: ...the high speed mode and runs for the set time 5 Switch A switch is recommended for the polluted indoor air areas When the switch contacts are closed the unit goes to the high speed mode Open the switc...

Страница 18: ...of activated LOW speed mode editing of this parameter will result in change of the low speed setting both for the supply and extract fans To display or change this parameter press KEY1 and set a requ...

Страница 19: ...ensor short circuit 3 temperature sensor breakout The letter indicates no alarm n or available alarm Y Example 1 Y fire alarm activation If the fire alarm panel is disconnected it means that the contr...

Страница 20: ...frost mode the extract fan runs in high speed the supply fan is off and vice versa according to the signaling from the outdoor temperature sensor The temperature conditions for this mode are described...

Страница 21: ...rs in the reverse order Multiple cleaning is allowed until the filters get mechanically worn out For new filters of the type stated in the technical data please contact to the Product Seller Turn the...

Страница 22: ...rs some dust may accumulate inside the fans and reduce the fan performance and supply air flow Clean the fans with a soft cloth brush or using compressed air Do not use water aggressive solvents or sh...

Страница 23: ...ventilation system components Clean or replace the air ducts diffusers louver shutters grilles or other ventilation system components Low supply air temperature Clogged extract filter Clean or replace...

Страница 24: ...RFORMANCE Some states do not allow the exclusion or limitations of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal...

Страница 25: ...25 www vents us com...

Страница 26: ...26 HRV ERV 80 100 120 150 R EC L www vents us com...

Страница 27: ...e unit _____________________________________ is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician...

Страница 28: ...VUSA172 1EN 06...

Отзывы: