38
FP15 & FP15A Waterloo - Installation and Operation Manual
6.3.5.1
Option #1 - Installation directly on the floor
•
A 2.00 R value for the hearth extension is required. The non-combustible hearth extension floor area
must extend at least 32" (813 mm)
(B)
in front of the hearth.
•
The joint between the hearth extension and the fireplace
(E)
, for the entire width of the floor
protection, must be protected by a bent and continuous piece of sheet metal (not included).
•
An 84" clearance between the fireplace base and the ceiling
(A)
must be respected.
MINIMUM MEASUREMENTS
A
84" (2134 mm)
B
32" (813mm)
E
2" (51 mm)
NOTE
The floor under the fireplace should match or exceed the height of the floor protection.