VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System – User Guide V1.0
47
IO1
Function Control
Values 0,1,2,3,4
Read
Group 40 Variation 2
16bit Analog with
flag
Direct Operate
Group 41 Variation 2
16bit Analog with
flag
Direct Op Value
0 Analog
1 Digital Input Alarm if < 1v
2 Digital Input Alarm if > 2v
Low Capacity Alarm
3 Digital Out NC
4 Digital Out NO
IO2
Function Control
Values 0,1,2
Read
Group 40 Variation 2
16bit Analog with
flag
Direct Operate
Group 41 Variation 2
16bit Analog with
flag
Direct Op Value
0 Analog
1 Digital Input Alarm if < 1v
2 Digital Input Alarm if > 2v
9.1.3.7.
Binary Output Status Point
Point
Description
State
Value
State
Value
0 Battery Data Reset
Session has Data
0x81
Data Empty
0x01
1 Battery LVD Status
LVD is enabled
0x81
LVD disabled
0x01
2 Battery Test Enable
Test is enabled
0x81
Test is disabled
0x01
3 Battery Start Test
Test running
0x81
Test not running
0x01
9.1.3.8.
Binary Output Write to Points
Binary output points can be written to directly using Group 10 variation 01, using
Qualifier 0x00 (8 bit index and range).
Points must be written to individually, using matching start and stop values,
followed by the binary value "1" or "0" (See DNP_IEE-1815-2023 11.9.4.6)