VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System – User Guide V1.0
21
7.4.1.4.
Low Capacity Alarm
This allows the user to enable the channel relay to indicate a battery
relate fault
Digital Out Normally Open
The relay closes when a fault is indicated.
Digital Out Normally Low
The relay opens when a fault is indicated.
7.4.2. IO Channel 2
7.4.2.1.
Analog Input 0-32V
This allows the user to enable an analog input level for triggering alarms
from external sources (door switches, solid state relays, etc.).
7.4.2.2.
Digital Input Alarm if < 1V
This allows the user to enable a digital input logic levels that is less than 1
volt to trigger an alarm from external sources (door switches, solid state
relays, etc.).
7.4.2.3.
Digital Input Alarm if > 2V
This allows the user to enable a digital input logic levels that is greater
than 2 volt to trigger an alarm from external sources (door switches, solid
state relays, etc.).
7.4.3. System Voltage
Allows the user to select whether the system operates at 12 V or 24 V.