3
with an external sensor which should be placed (embedded)
into the floor between two heating cable loops, near the floor
surface. Temperature can be regulated by the floor sensor or
the room sensor. A combination mode is also available where
both sensors are used. The floor sensor can then be used to
limit the floor temperature (below the set maximum limit), the
room sensor is used for regulating temperature according to the
set value.
If the heat indication symbol is shown in the display, it means
the thermostat is heating, but the symbol is not directly linked
(synchronized) to the relay controlling the power to the heating
cable.
The thermostat is turned on and off by using the ON/OFF
button. When turned off the settings will be remembered. The
thermostat will also remember its' settings if the power supply
fails (no time limit, EEPROM backup).
2. TECHNICAL DATA
Rated voltage
220-240V
Own consumption
< 2 W