5.0 Commissioning

11

CE-1-11/00

5.1

Commissioning the System

Before starting to commission the system check

the following:

a) All ducting is in place and secured.

b) The wiring is secure and correctly connected.

c) The trap is in position, charged and will

enable efficient removal of condensate.

d) The unit is mounted appropriately in a

position not susceptible to movement or

damage.

The scope of the commissioning procedure

comprises:

1. Balancing the two airflows to achieve

maximum heat exchanger efficiency.

2. Adjusting the two airflows to obtain the overall

airflow rates and the individual terminal air flow

rates as specified on the air change schedule.

3. An airflow meter must be used to set the

correct airflows.

NOTE:

The supply air terminal device is

directional and incorporates a deflector plate.

Ensure that the deflector plate is correctly

positioned so that the active part of the

terminal device is discharging to the room.

4. Set the control switch (NBSW or PCSW) to

normal speed or set the humidistat (HS6) at

maximum and check that air is flowing in the

correct direction at each terminal point.

5. Standard ceiling terminals type EV100 and

SV100 are adjusted by turning the central screw

and are locked in the “set” position by the

locknut.

Содержание HR100R

Страница 1: ...CE 1 11 00 HR100R Mini Air Handling Unit For Ducted Ventilation With Heat Recovery Installation and Servicing Instructions Please leave these instructions with the user...

Страница 2: ...CE 1 11 00 2...

Страница 3: ...CE 1 11 00 3 1 0 Introduction 4 2 0 Site Requirements 5 3 0 Installation 6 4 0 Electrical 10 5 0 Commissioning 11 6 0 Maintenance 12 7 0 Optional Extras 13 8 0 Notes 14 Section Page Contents...

Страница 4: ...involving internal bathrooms and meets building regulation requirements for this application A two speed motor provides for constant low rate ventilation with a boost speed option Fresh pre warmed air...

Страница 5: ...ers in the vicinity of excessive levels of airborne oil or grease 7 If the ceiling diffusers are installed in a room containing a fuel burning appliance the installer must ensure that air replacement...

Страница 6: ...or blockboard 19mm preferred This board should be raised enough to facilitate the mounting of the unit above joist level 6 The unit must be positioned so that the condensate outlet can be trapped and...

Страница 7: ...es it is necessary to lift the floor coverings at first floor level above the terminal positions to gain access to the terminal housings to secure and seal the duct and fittings 12 Fix in position all...

Страница 8: ...and 45 diversions and branches are accomplished with flexible fittings QTB90 QTB45 and QTET The duct is a push fit into the socket of the connector and fittings 23 Once assembled the joints are secure...

Страница 9: ...se of flexible ducting should be limited to an absolute minimum If used it should be fully stretched in order to minimse pressure loss 29 Offer the unit on to the mounting surface ensuring that it is...

Страница 10: ...ow Earth 1 2 1 0 2 Continuous Normal Speed Continuous Boost Speed VCON100 Manual Normal to Boost Speed Switching and ON OFF Control NBSW and PCSW Manual Normal to Boost Speed Control HS6 Automatic Nor...

Страница 11: ...two airflows to obtain the overall airflow rates and the individual terminal air flow rates as specified on the air change schedule 3 An airflow meter must be used to set the correct airflows NOTE The...

Страница 12: ...on experienced and according to the following procedure 1 Isolate the mains power supply 2 Remove the four securing screws from either end of the cover 3 Remove the cover 4 Remove the heat exchanger f...

Страница 13: ...in 6m lengths Ref IFD100 Thermally insulated ducting in 6m lengths Ref PFD100 PVC ducting in 6m lengths Quicktube 100mm rigid plastic ducting can also be used in conjunction with the HR100R unit For...

Страница 14: ...8 0 Notes 14 CE 1 11 00...

Страница 15: ...CE 1 11 00 15...

Страница 16: ...CE 1 11 00 Vent Axia Ltd Fleming Way Crawley West sussex RH10 9YX www vent axia com Comp No 370666 Iss C 0310...

Отзывы: