6

C. SETUP 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR 
MAINTENANCE. 

 

ACCESSING THE CONTROL SETTINGS – (Fig. 5 and 6) 

1. 

Loosen the screw in the bottom of the grille and remove the front grille. 

2. 

Carefully pull the inner cap from the centre of the fan away from the chassis.  

3. 

Adjust the settings as outlined below.  

 

TRICKLE SPEED SELECTION (6l/s or 9l/s) – (Fig. 8) 

In normal running mode the fan can extract at either 6l/s (22m

3

/h) or 9l/s (32m

3

/h) flow rate. The 

fan will boost to 15l/s (54m

3

/h) when the LS connection is switched.  

  Factory set at 

6l/s

 (22m

3

/h). (Fig.9) 

  Remove jumper connector (JP1) if 

9l/s

 (32m

3

/h) extract flow rate is required. (Fig.9) 

 

 

BOOST SPEED SELECTION (Fig. 9) 

(443175A - Timer, 443176A - Humidistat-Timer and 443177A - Humidistat-Pullcord models only)

  

The fan has two boost speed settings for different installation requirements: 

 

  Max speed: Dip switch 2 in the ‘OFF’ position. (Fig.10) 

  15l/s speed: Dip switch 2 should be in the ‘ON’ position. (Factory set) (Fig.10) 

 
Dip switch 1 should be in the ‘ON’ position for constant trickle mode.  

 

 
 

 

TIMER ADJUSTMENT (T, TP, HT & HTP MODELS) (FIG. 8) 

BEFORE ADJUSTING THE TIMER, SWITCH OFF THE MAINS SUPPLY. TIMER SHOULD 
ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION 

IMPORTANT NOTE:- ON THE 

TP & HTP

 MODELS ONLY THIS ADJUSTS THE OVERRUN 

TIME FOR THE PULLCORD OPERATION.  ON 

T

 

&

 

HT

 MODELS THE TIMER IS ACTIVATED 

VIA THE LS CONNECTION. 

 

1. 

Remove the fan grille. The overrun timer is factory set to approximately  
15 minutes. This timer period can be adjusted between approximately 3-30 
minutes by altering the adjuster on the control PCB. 

2. 

To REDUCE the operating time, use a small screwdriver to turn the adjuster Fig.8. 
CLOCKWISE.  

3. 

To INCREASE the operating time, use a small screwdriver to turn the adjuster 
Fig.8. ANTI-CLOCKWISE. 

4. 

Replace the fan grille. 

 

 

 

 

Содержание Centra Lo-Carbon SELV HT

Страница 1: ...distat Timer HT 443177A Humidistat Timer Pullcord HTP 447128A Timer Pullcord TP PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Centra Lo Carbon SELV IPX7 FAN...

Страница 2: ...2...

Страница 3: ...irect water spray for prolonged periods of time H Where ducted Fans are used to handle moisture laden air a condensation trap should be fitted Horizontal ducts should be arranged to slope slightly dow...

Страница 4: ...hin reach of a person using a fixed bath or shower i e in a nearby wall However the fan must not be placed where it could be submerged in water or regularly exposed to direct water spray e g from a sh...

Страница 5: ...the holes in the fan back plate Drill plug and screw into position 3 Fix exterior grille into position with the louvres positioned downwards Note The grille must comply with the standard requirements...

Страница 6: ...y The fan has two boost speed settings for different installation requirements Max speed Dip switch 2 in the OFF position Fig 10 15l s speed Dip switch 2 should be in the ON position Factory set Fig 1...

Страница 7: ...during the overrun time period the timer will reset the countdown timer back to the preset value There is no way of switching the fan back to trickle manually D SERVICING AND MAINTENANCE WARNING THE...

Страница 8: ...g 5 Removing the grille for wiring and setting the controls 1 Loosen screw 2 Pull grille slightly away from bottom edge 3 Push grille upwards until clear from the fan chassis N L 1 Phase Supply 220 24...

Страница 9: ...on 15l s speed boost Dip switch 2 should be in the ON position Fig 6 Accessing the control settings Fig 7 Removing the front grille panel for cleaning Dip switch Fig 8 Trickle speed selection and T HT...

Страница 10: ...Notes...

Страница 11: ...ogy Control Factor CTRL 0 95 0 65 0 65 0 95 Control Typology Clock Control Local Demand Control Local Demand Control Clock Control Declared Max Internal External Leakage Rates for BVUs or carry over f...

Страница 12: ...ctive the product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Has...

Отзывы: