5.6 Signal connection for setting the ouput voltage
The unit has one-analog input: terminals
“
E1
”
/
“
GND
”
(Analog In 1).
At this input the potentiometer mounted in the cover for setting the output voltage is connected
(potentiometer outside). Voltage supply is made by terminal A1 (+10 V).
Alternatively the setting of the output voltage can be made by an external signal (0...10 V). For this
disconnect the potentiometer and isolate the connecting cables.
Operation with built-in potentiometer
(at delivery)
Operation with external setting signal
(0...10 V)
A
E1
GND
0-10 V
10 k
30.11.2009
v_ext_pot_p-et.vsd
A
E1
GND
Eingang
Input
0...10 V
30.11.2009
v_ext_0_10V_p-et.vsd
Attention!
Never apply line voltage to analog inputs!
5.7 Output voltage 0 - 10 V (A1 = Analog Out 1)
Connection to terminals
“
A1
”
-
“
GND
”
=
“
Analog Out 1
”
(I
max
10 mA).
It is not permissible to connect outputs of several devices to each other!
The function of the signal output A1 (Analog Out 1) can be determined by
DIP8
.
DIP 8 =
|
OFF
|
Constant v 10 V for external potentiometer (factory setting)
DIP 8 =
|
ON
|
0 - 10 V
≙
modulation 0 - 100 %
•
Proportional the internal control of modulation with consideration
“
n-min
”
and
“
n-max
”
setting.
•
For enable
“
OFF
”
it goes
not back to
“
0 V
”
.
•
For motor fault the output signal remains for a slave controller (
“
Master-Slave
”
combination).
5.8 Voltage supply for external devices (+24V, GND)
There is an integrated power supply for external devices, e.g. a sensor. Te24 V, output voltage
tol/- 20%. max. load current
F
Technical data.
It is not permissible to connect outputs of several devices to each other!
In case of overload or short circuit (24 V
–
GND), the external power supply is shut down (multi-fuse).
The device performs a
“
Reset
”
and continues operation.