background image

Wiring Requirements

CAT 5 Cable

Thermostat Cable

The Remote Sensor should be connected to the thermostat using 
two conductor thermostat cable (18-24 gauge) or solid conductor 
CAT 5, CAT 5e, or CAT 6 type network communication cable. This is 
an unshielded cable with four twisted pairs of 24 gauge solid wire. 
The cable length should not exceed 250 feet.  

IMPORTANT:  Do not run sensor wiring in the same conduit as the 
24VAC thermostat wiring.  Electrical interference may cause the 
sensor to give incorrect temperature readings.

Remote Sensor

Circuit Board

The  connection  between  the  Remote  Sensor  and  the 
thermostat must be wired per the connection diagram. 
Only  two  conductors  are  used,  therefore  the  extra 
conductors should be cut from each end of the cable to 
prevent shorting.  Follow the color coding as shown.

WARNING

Turn off power to the thermostat before wiring.  Death 
or injury from electric shock could result.

Sensor Wiring

Secure the Remote Sensor top cover to the wall plate 
using the supplied standard or tamper proof screws.

OVERRIDE

RS

RS-GND

RS+5

OVERRIDE

Sensor Assembly

NOTE:  All sensor wiring 
must  be  in  compliance 
with  all  applicable  local 
and national codes.

Air Temperature vs.

Temperature Resistance

REMOTE SENSOR

with OVERRIDE BUTTON

MODEL

©Venstar Inc. 8/11          

P/N 88-941     Rev. 1

F

C

-20
-10

0

10
20
30
40
50
60
70
80
90

100

110

120

Air Temperature

Ohms 

Resistance in

-28.9

106926

-23.3

80485

-17.8

61246

-12.2

47092

-6.7

36519

-1.1

28558

4.4

22537

10

17926

15.6

14356

21.1

11578

26.7

9398

32.2

7672

37.8

6301

43.3

5203

48.9

4317

Thermostat

REMOTE/
OUTDOOR

White +

Black -

Remote Sensor

Circuit Board

ACC-TSENWB

Отзывы: