background image

3. INSTALLATION (

CONT

D

)

3.5 I

NSTALLING

 

THE

 D

UCTWORK

 

AND

 

THE

 

REGISTERS

9

S

TALE

 

AIR

 

EXHAUST

 

DUCTWORK

:

• Install registers in areas where contaminants are produced: Kitchen, bathrooms, laundry room, etc.
• Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.
• Install the kitchen register at least 4 feet (1.2 m) from the range.
• If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400 ft/min. (122 m/min), then 
  the register type is too small. Replace with a larger one.

F

RESH

 

AIR

 

DISTRIBUTION

 

DUCTWORK

:

• Install registers in bedrooms, dining room, living room and basement.
• Install registers either in the ceiling or high on the walls with air flow directed towards the ceiling.
  (The cooler air will then cross the upper part of the room, and mix with room air before descending to occupant level.)
• If a register must be floor installed, direct the air flow up the wall.

WARNING

Never install a stale air exhaust register in a room where there is a combustion device, such as a gas furnace, a 
gas water heater or a fireplace. 

!

CAUTION

The ductwork is intended to be installed in compliance with all local and national codes that are applicable.

3.5.1 F

ULLY

 D

UCTED

 S

YSTEM

 

(

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 2.1)

S

TALE

 

AIR

 

EXHAUST

 

DUCTWORK

:

Same as for Fully Ducted System, described on point 3.5.1 above)

F

RESH

 

AIR

 

DISTRIBUTION

:

3.5.2 E

XHAUST

 D

UCTED

 S

YSTEM

 

(

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 2.2)

There are two methods for connecting the unit to the furnace:

M

ETHOD

 1: S

UPPLY

 

SIDE

 

CONNECTION

• Cut an opening into the furnace supply duct at least 18 inches (0.5 m) 
  from the furnace.
• Connect this opening to the fresh air distribution port of the HRV/ERV 
  (use metal duct, see illustration at right).
• Make sure that the HRV/ERV duct forms an elbow inside the furnace ductwork.
• If desired, interlock (synchronize) the furnace blower operation with 
  the HRV/ERV operation. (See Section 5).

WARNING

When performing duct connection to the furnace, installation must be done in accordance with all applicable 
codes and standards. Please refer to your local building code.

!

CAUTION

When performing duct connection to the furnace supply duct, this duct must be sized to support the additional 
airflow produced by the ERV/HRV. Also, use a metal duct. It is recommended that the ERV/HRV is running when the 
furnace is in operation in order to prevent backdrafting inside ERV/HRV.

VJ0084

M

ETAL

 

DUCT

M

INIMUM

18’’ (0.5 

M

)

M

ETHOD

 2: R

ETURN

 

SIDE

 

CONNECTION

• Cut an opening into the furnace return duct not less than 10 feet (3.1 m)
  from the furnace (

A

+

B

).

• Connect this opening to the fresh air distribution port of the HRV/ERV 
  (see illustration at right).

 

NOTE:  For Method 2, it is not essential that the furnace blower runs when the unit is 

in operation, but we recommend it. If desired, synchronize the furnace blower 
operation with the HRV/ERV operation. (See Section 5).

B

A

VJ0085

A+B= 

NOT

 

LESS

 

THAN

 10’ (3.1 

M

)

Содержание HRV CONSTRUCTO 1.5ES

Страница 1: ...PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA AND THE US EPA THEY MEET ENERGY STAR REQUIREMENTS ONLY WHEN USED IN CANADA INSTALLER MAN...

Страница 2: ...r connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or cleaning this unit it is recommended to wear safety...

Страница 3: ...5 2 EXHAUST DUCTED SYSTEM 9 3 5 3 SIMPLIFIED INSTALLATION 10 3 6 CONNECTING THE DUCTS TO THE UNIT 11 3 7 INSTALLING THE EXTERIOR HOODS 12 3 8 CONNECTING THE DRAIN 12 13 3 8 1 HRV UNITS 12 3 8 2 ERV UN...

Страница 4: ...CYCLES MINUTES EXTENDED DEFROST CYCLES CELCIUS C FAHRENHEIT F DEFROSTING OPERATION TIME BETWEEN EACH DEFROST CYCLES DEFROSTING OPERATION TIME BETWEEN EACH DEFROST CYCLES 5 23 10 60 10 30 15 5 10 30 1...

Страница 5: ...INCREASED LOW SPEED ELECTRICAL SUPPLY 120 V 60 HZ 120 V 60 HZ 120 V 60 HZ 120 V 60 HZ 120 V 60 HZ POWER CONSUMPTION 160 WATTS 195 WATTS 200 WATTS 160 WATTS 195 WATTS 17 432 mm 17 438 mm 6 152 mm Powe...

Страница 6: ...austed from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to the cold air return or the supply duct of the furnace If required bathroom fans and...

Страница 7: ...panel on the side of the unit Close to an exterior wall so as to limit the length of the insulated flexible duct to and from the unit Close to a drain If no drain is close by use a pail to collect run...

Страница 8: ...e choice for the main exhaust duct End branches Each end branch will have to transport an air flow of 70 cfm 140 divided by 2 Table above indicates a 5 duct Recommended air flow 75 cfm maximum air flo...

Страница 9: ...point 3 5 1 above FRESH AIR DISTRIBUTION 3 5 2 EXHAUST DUCTED SYSTEM AS ILLUSTRATED IN SECTION 2 2 There are two methods for connecting the unit to the furnace METHOD 1 SUPPLY SIDE CONNECTION Cut an o...

Страница 10: ...accordance with all applicable codes and standards Please refer to your local building code CAUTION If using Method 2 make sure the furnace blower operation is synchronized with the unit operation Se...

Страница 11: ...collar Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it completely Fasten in place the vapor barrier using the port strap included in unit parts bag To d...

Страница 12: ...CAUTION A drain tubing included must be installed for all HRV units For ERV units it is not required however it is recommended for climates where the outside temperature typically remains below 25 C 1...

Страница 13: ...ns off and the booting sequence is done NOTE No command will be taken until the unit is fully booted 4 1 2 SETTING EXTENDED DEFROST The unit is factory set to normal defrost In cold region it may be n...

Страница 14: ...ve been made insert the terminal connector in the electrical compartment front face NOTE For information about the operation of the wall controls refer to the user guide VD0278 TERMINAL CONNECTOR LOCA...

Страница 15: ...CTOR THERMOSTAT TERMINALS FOUR WIRES TWO WIRES heating only FURNACE 24 VOLT TERMINAL BLOCK TWO WIRES COOLING SYSTEM NO C NC I OC OL Y R G B W R G Y W R Y R G Y C THERMOSTAT TERMINAL 4 WIRES 2 WIRES he...

Страница 16: ...ional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 ICP BK Y R G W W nc Motor capacitor Fan motor GN GN BN B...

Страница 17: ...m Adjust the fresh air balancing damper until the FRESH air flow is approximately the same as the EXHAUST air flow If FRESH air flow is less than EXHAUST air flow then go back and adjust the exhaust b...

Страница 18: ...2 00601 4 00887 2 00601 4 14 Diffuser 60822 60822 60822 60822 60822 60822 15 Filter kit 60800 60800 60800 60799 60800 60800 60800 16 Core 60802 60801 60803 16582 60802 60801 60803 17 Door latches and...

Страница 19: ...rol LED flashes GREEN The unit damper has been blocked or broken integrated control LED flashes AMBER and unit is OFF Motor won t turn Clean the exterior air intake port Replace the unit thermistor Ch...

Страница 20: ...ction 6 Wiring Diagram Check if the fuse F1 is intact If all the readings correspond to the right voltage values the circuit board is not defective If one or both readings are different change the cir...

Отзывы: