background image

19

9. TROUBLESHOOTING

If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the list below to know where on 
the unit the problem occurs.

LED flashes GREEN (double blink). 

• Thermistor error. 

Replace the thermistor kit.

LED flashes AMBER. 

• Damper error. 

Go to point 10.

WARNING

A few diagnosis procedures may require the unit to be in operation while proceeding. Open the unit door and 
bypass its magnetic switch by putting the door white magnet on it. Be careful with moving and/or live parts.

!

P

ROBLEMS

P

OSSIBLE

 

CAUSES

Y

OU

 

SHOULD

 

TRY

 

THIS

1. The error code E1 is 

displayed on Altitude or 
Deco-Touch wall control 
screen.

• The wires may be in reverse position.

• The wires may be broken.
•  The wires may have a bad connection.
• 

The unit is not compatible with 
Altitude wall control (Constructo).

• Ensure that the color coded wires have been connected to their appropriate 

places.

• Inspect every wire and replace any that are damaged.
• Ensure the wires are correctly connected.
• Refer to unit spec. sheet for control compatibility.

2. 

There is no outside 
temperature displayed 
on Altitude wall control 
screen                    .

• Unit is on error and integrated control 

LED flashes (GREEN or AMBER).

• 

The unit thermistor is defective 
(integrated control LED flashes 
GREEN).

NOTE:  At its very start-up or after a power failure, it takes some minutes before 

the outside temperature appears on screen. The delay duration depends 
on which operation mode the wall control is set. The shortest delay is 
obtained when the wall control is set on MIN or MAX in VENT Mode.

• Check if unit is operating.

• Replace the unit thermistor.

3. Altitude or Deco-Touch 

wall control screen 
alternates between 
normal display and E3 or 
E4 appears on screen.

• 

The Altitude or Deco-Touch wall 
control needs to be reset.

• 

The Altitude or Deco-Touch wall 
control is defective.

4. On Altitude wall control, 

there is an important 
difference between 
temperature displayed 
and real temperature.

• Exterior air intake port is blocked.
• 

The unit thermistor is defective
(integrated control LED flashes 
GREEN).

• The unit damper has been blocked 

or broken (integrated control LED 
flashes AMBER and unit is OFF).

• Motor won’t turn.

• Clean the exterior air intake port.
• Replace the unit thermistor.

• Check for the proper operation of the unit damper; replace if necessary.

• Confirm that the motor is running, if not refer to point 9.

5. 

Unit does not work 
(no LED is lit on the 
integrated control).

• The transformer may be defective.
• The circuit board may be defective.

• The unit is unplugged.
• The unit door is opened.
• A fuse is blown.
• Wrong control connections.

• Check for 24 VAC on J8-1 and J8-2.

• Plug the unit.
• Close unit door.
• Inspect fuse on circuit board (refer to wiring diagram F1 on page 16).
• Try the integrated control (see Section 4.1 on page 13).

6. 

The damper actuator 
does not work or rotates 
continuously.

•  The damper actuator or the integrated 

damper port mechanism may be 
defective (integrated control LED 
flashes AMBER and unit is OFF).

• The circuit board or the transformer 

may be defective.(integrated control 
LED flashes AMBER and unit is OFF)

• Unplug the unit. Disconnect the main control and the optional controls(s) (if 

need be). Wait 10 seconds and plug the unit back. Check if the damper opens. 
If not, use a mulltimeter and check for 24 VAC on J12-1 and J12-2 (in electrical 
compartment). If there is 24 VAC, replace the entire port assembly. 

  NOTE:  It is normal to experience a small delay (7-8 seconds) before detecting 

the 24 VAC signal at starting-up. This signal will stay during 17-18 
seconds before disappearing.

•  If there is no 24 VAC, check for 24 VAC between J8-1 and J8-2. If there is 24 VAC 

replace the circuit board, and if there is no 24 VAC, change the transformer.

NO  C  NC   I   OC OL  Y    R   G   B

VE0097 

• Unplug the unit. Disconnect the main control 

and the optional(s) control(s) (if need be). 
Jump G and B terminals. Plug the unit back 
and wait about 10 seconds. If the motor runs 
on high speed and the damper opens, the 
circuit board is not defective.

• Reset the Altitude or Deco-Touch wall 

control by pressing simultaneously 
on both keys for 8 second (as shown 
at right). Then, 

unplug the unit for 

30 seconds. Plug the unit back.

• If the problem is not solved, replace the Altitude or Deco-Touch wall control.

B

OTH

 

DURING

SEC

.

VQ0048A

A

LTITUDE

VQ0062

D

ECO

-T

OUCH

Содержание HRV CONSTRUCTO 1.5ES

Страница 1: ...PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA AND THE US EPA THEY MEET ENERGY STAR REQUIREMENTS ONLY WHEN USED IN CANADA INSTALLER MAN...

Страница 2: ...r connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or cleaning this unit it is recommended to wear safety...

Страница 3: ...5 2 EXHAUST DUCTED SYSTEM 9 3 5 3 SIMPLIFIED INSTALLATION 10 3 6 CONNECTING THE DUCTS TO THE UNIT 11 3 7 INSTALLING THE EXTERIOR HOODS 12 3 8 CONNECTING THE DRAIN 12 13 3 8 1 HRV UNITS 12 3 8 2 ERV UN...

Страница 4: ...CYCLES MINUTES EXTENDED DEFROST CYCLES CELCIUS C FAHRENHEIT F DEFROSTING OPERATION TIME BETWEEN EACH DEFROST CYCLES DEFROSTING OPERATION TIME BETWEEN EACH DEFROST CYCLES 5 23 10 60 10 30 15 5 10 30 1...

Страница 5: ...INCREASED LOW SPEED ELECTRICAL SUPPLY 120 V 60 HZ 120 V 60 HZ 120 V 60 HZ 120 V 60 HZ 120 V 60 HZ POWER CONSUMPTION 160 WATTS 195 WATTS 200 WATTS 160 WATTS 195 WATTS 17 432 mm 17 438 mm 6 152 mm Powe...

Страница 6: ...austed from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to the cold air return or the supply duct of the furnace If required bathroom fans and...

Страница 7: ...panel on the side of the unit Close to an exterior wall so as to limit the length of the insulated flexible duct to and from the unit Close to a drain If no drain is close by use a pail to collect run...

Страница 8: ...e choice for the main exhaust duct End branches Each end branch will have to transport an air flow of 70 cfm 140 divided by 2 Table above indicates a 5 duct Recommended air flow 75 cfm maximum air flo...

Страница 9: ...point 3 5 1 above FRESH AIR DISTRIBUTION 3 5 2 EXHAUST DUCTED SYSTEM AS ILLUSTRATED IN SECTION 2 2 There are two methods for connecting the unit to the furnace METHOD 1 SUPPLY SIDE CONNECTION Cut an o...

Страница 10: ...accordance with all applicable codes and standards Please refer to your local building code CAUTION If using Method 2 make sure the furnace blower operation is synchronized with the unit operation Se...

Страница 11: ...collar Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it completely Fasten in place the vapor barrier using the port strap included in unit parts bag To d...

Страница 12: ...CAUTION A drain tubing included must be installed for all HRV units For ERV units it is not required however it is recommended for climates where the outside temperature typically remains below 25 C 1...

Страница 13: ...ns off and the booting sequence is done NOTE No command will be taken until the unit is fully booted 4 1 2 SETTING EXTENDED DEFROST The unit is factory set to normal defrost In cold region it may be n...

Страница 14: ...ve been made insert the terminal connector in the electrical compartment front face NOTE For information about the operation of the wall controls refer to the user guide VD0278 TERMINAL CONNECTOR LOCA...

Страница 15: ...CTOR THERMOSTAT TERMINALS FOUR WIRES TWO WIRES heating only FURNACE 24 VOLT TERMINAL BLOCK TWO WIRES COOLING SYSTEM NO C NC I OC OL Y R G B W R G Y W R Y R G Y C THERMOSTAT TERMINAL 4 WIRES 2 WIRES he...

Страница 16: ...ional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 ICP BK Y R G W W nc Motor capacitor Fan motor GN GN BN B...

Страница 17: ...m Adjust the fresh air balancing damper until the FRESH air flow is approximately the same as the EXHAUST air flow If FRESH air flow is less than EXHAUST air flow then go back and adjust the exhaust b...

Страница 18: ...2 00601 4 00887 2 00601 4 14 Diffuser 60822 60822 60822 60822 60822 60822 15 Filter kit 60800 60800 60800 60799 60800 60800 60800 16 Core 60802 60801 60803 16582 60802 60801 60803 17 Door latches and...

Страница 19: ...rol LED flashes GREEN The unit damper has been blocked or broken integrated control LED flashes AMBER and unit is OFF Motor won t turn Clean the exterior air intake port Replace the unit thermistor Ch...

Страница 20: ...ction 6 Wiring Diagram Check if the fuse F1 is intact If all the readings correspond to the right voltage values the circuit board is not defective If one or both readings are different change the cir...

Отзывы: