6   VELUX

®

Setting options/ Indications / Troubleshooting

Setting options via slide switch SW1

SW 1/1 = ON

Maintenance monitoring is ON. (Factory setting).
When the monitoring is activated, the green operation LED flashes for 10 seconds. If SW 1/1 is 

switched OFF again during these 10 seconds, the activation is cancelled.
When maintenance is due (every 12 months), the maintenance alarm is activated. The alarm is indi-

cated in the break-glass point only: An acoustic alarm (continuous) sounds and the yellow error LED 

is on (constant light). 
To show that there is no error, the green operation LED in the break-glass point remains on. There is 

NO indication in the control unit. 
The "Maintenance" indication is saved for several days if the mains and battery voltages have been 

disconnected, and is active again once the mains or battery voltages have been re-established. The 

control unit is still working correctly. A reset can only be carried out by qualified personnel.

SW 1/1 = OFF

Maintenance monitoring is OFF.

SW 1/2 = ON

Transmission of alarm is interrupted after 3 minutes.

SW 1/2 = OFF

Transmission of alarm as long as there is an alarm. (Factory setting).

Setting options via slide switch SW2

SW 2/1 = ON

Alarm triggered because of an error indication from either the circuit of motor, smoke detector and/

or break-glass point or because of high temperatures.

SW 2/1 = OFF

No alarm triggered. The error is only shown via LEDs. (Factory setting).

SW 2/2 = ON

Motors only OPEN the staircase smoke exhaust as long as the button on the ventilation switch is 

pressed and held (dead-man button).

SW 2/2 = OFF

Motors OPEN the staircase smoke exhaust once the ventilation switch is pressed. (Factory setting).

Error indication and troubleshooting

There is an optical and acoustic error indication in the break-glass point. The green operation LED in the break-glass point 

and the control unit respectively are off. 

The yellow error LED in the break-glass point flashes and the corresponding yellow error LED in the control unit is on. In the 

break-glass point, an acoustic alarm sounds (pulsing).

Diagnosis / Monitoring in the control unit

LED on the printed 

circuit board

Functions 

are OK

Error

Diagnosis

Netz = Mains

(green)

ON

OFF

Check mains voltage and mains fuse.

Betrieb = Operation

(green)

ON

OFF

Check all functions.

Akku = Battery

(yellow)

OFF

Flashes in case of power failure or 

charging voltage below 26 V.

Is on in case of no battery or battery 

voltage below 19 V.

Check mains fuse and charging voltage.

Check battery, battery voltage and battery 

fuse.

Motorkreis = 

Motor circuit  

(yellow)

OFF

Flashes in case of interruption.

Check motor terminal module and motor 

fuse.

Hauptbedienstelle = 

Break-glass point

(yellow)

OFF

Flashes in case of interruption, is on 

in case of short-circuit.

Check wiring and jumper J1 in the last or 

only break-glass point.

If no break-glass point has been connec-

ted, insert a 10 kΩ resistor between termi-

nals 9 and 12.

Rauchmelder =  

Smoke detector

(yellow)

OFF

Flashes in case of interruption, is on 

in case of short-circuit.

Check wiring and the terminal module.

Note: The error indication from battery and motor circuits can appear with a time delay of about 8 sec.

Содержание KFC 100J

Страница 1: ...r VELUX Steuereinheit f r Rauchabzug KFC 100J ENGLISH Instructions for VELUX control unit for smoke exhaust KFC 100J 061 0 6 795 176 6 9 4 8 3 4 60 4 9 1 061 D1 4 3 59D5 F 1 42E38 538 9 6 0 6 1 6 6 6...

Страница 2: ...D5 75 59 D175 59D5 125 S 75 D125 5 59D5 5B 125 E 7C 1 59D5 C38 ECC 1 D1 41B4 59D5 C38 ECC 1 6UB 59D5 1D9 5 U25BC938D 59D5 Contents Cover sheet Contents Page 2 Important information Page 3 Functionalit...

Страница 3: ...lectronic equipment waste By sorting electrical and electronic equipment waste with this symbol you con tribute to reducing the volume of incinerated or buried waste and to reducing any negative impac...

Страница 4: ...s Once the staircase smoke exhaust has been closed the comfort ventilation functions are operational again After an alarm via an automatic detector blow out smoke or replace the detector before resett...

Страница 5: ...ditional modules optional Transmitting alarms and or error indications An alarm or an error indication can be transmitted potential free by inserting the alarm error indication module Multi error indi...

Страница 6: ...exhaust as long as the button on the ventilation switch is pressed and held dead man button SW 2 2 OFF Motors OPEN the staircase smoke exhaust once the ventilation switch is pressed Factory setting E...

Страница 7: ...a potential free fire alarm system contact at the smoke detector input fire alarm module insertion 8 24 V 100 mA on extra terminal Warning No 72 hour emergency power supply when in use Further techni...

Страница 8: ...5 D 95 1CD5B 9 59 5B T85 F 31 L U25B D95B5 General information Installation General information The back up batteries must be replaced every four years Retriggering the motors During the first 30 minu...

Страница 9: ...current of the control unit 4 8 A Maximum cable length always routed from the control unit to the last junction box Operation current Sum of all motor currents per group Cross section 3 x 1 5 mm 5 x...

Страница 10: ...Ventilation switches see cable length table Option transmission of wind rain alarm Option transmission of fire alarm Option transmission of multi error Option BUS 2 x 2 x O 8 mm or 5 x 1 5 mm 2 see c...

Страница 11: ...break glass point CLOSE CLOSE CLOSE Indicator OPEN Alarm Alarm Motor term module Only insert terminal mod ule in the last or only detector Only insert the motor ter minal module in the last or only mo...

Страница 12: ...e inserted in the last or only break glass point CLOSE CLOSE CLOSE Indicator OPEN Alarm Alarm Motor term module Only insert the motor ter minal module in the last or only motor Note If motors operate...

Страница 13: ...9 4 D538 9C385 N 45BE 75 F B2581 D5 Mains Mains Mains fuse 1 A slow Motor Smoke detector Temperature fuse 72 C Module 1 Module 3 Module 2 Motor fuse 5 A slow Operation Battery Motor Break glass point...

Страница 14: ...control unit is connected to VELUX staircase smoke exhaust CSJ 1210 or VELUX stair case smoke exhaust exit CSJ 1211 the total system is to be considered as a machine which is not to be put into servi...

Страница 15: ...75 59 D175 59D5 125 S 75 D125 5 59D5 5B 125 E 7C 1 59D5 C38 ECC 1 D1 41B4 59D5 C38 ECC 1 6UB 59D5 1D9 5 U25BC938D 59D5 Inhaltsverzeichnis Deckblatt Inhaltsverzeichnis Seite 15 Wichtige Informationen S...

Страница 16: ...ist nach nationalen Bestimmungen zu entsorgen Das Produkt einschlie lich eventuell vorhandener Batterien Akkus wird als ein Elektro und Elektronikger t betrachtet und enth lt gef hrliche Materialien...

Страница 17: ...geltenden Vorschriften zu belegen Es sind nur Originalersatzteile zu verwenden Bei der j hrlichen Wartung m ssen die angeschlossenen Produkte gem ihren Anleitungen gepr ft werden Die Leiterplatte berw...

Страница 18: ...r Rauchableitung sind die L ftungsfunktionen wieder in Betrieb Nach Ausl sung durch einen auto matischen Melder den Melder vor der R ckstellung ausblasen bzw erneuern Anzeige Die rote Alarm LED in der...

Страница 19: ...ch Aufstecken des Alarm St rungsmoduls potentialfrei weitergeleitet werden Sammelst rung 1 x Wechslerkontakt max 60 V 1 A mit 3 poliger Anschlussklemme zur potentialfreien Weiterleitung an GLT usw Ala...

Страница 20: ...d nur ber LEDs angezeigt Werkseinstellung SW 2 2 ON Antriebe fahren nur solange AUF wie der L ftungstaster bet tigt wird Totmann SW 2 2 OFF Antriebe fahren AUF sobald der L ftungstaster bet tigt wird...

Страница 21: ...t 7 Ansteuerung durch potentialfreien BMA Kontakt am Rauchmeldereingang BMA Modul einsetzen 8 24 V 100 mA auf extra Klemme Achtung Bei Benutzung keine 72 Stunden Notstrom Weitere technische Daten Nenn...

Страница 22: ...85 G95 9 C 9 9 4 41B75CD5 D 95 1CD5B 9 59 5B T85 F 31 L U25B D95B5 Allgemein Montage Allgemein Die Notstromakkus sind alle 4 Jahre auszuwechseln Nachtriggern der Antriebe W hrend der ersten 30 Minuten...

Страница 23: ...Melders zum ffnen der Rauchabzugsanlage f hrt Die Verlegeart Unterputz stellt keine zugelassene Verlegeart zum Erreichen eines Funktionserhaltes in Anlehnung an die DIN 4102 Teil 12 dar Der Funktions...

Страница 24: ...Kabell ngentabelle Option Weiterleitung Wind Regenmeldung Option Weiterleitung RWA Ausl sung Option Weiterleitung Sammelst rung Option BUS 2 x 2 x O 8 mm oder 5 x 1 5 mm 2 E30 s Kabell ngentabelle Au...

Страница 25: ...edienstelle gesetzt werden ZU ZU ZU Anzeige AUF Alarmausl sung RWA Ausl sung Motor Endmodul Aktives Endmodul nur im letzten oder einzigen Melder einsetzen Motor Endmodul nur im letzten oder einzigen A...

Страница 26: ...Jumper Achtung Jumper J1 muss in der letzten oder einzigen Hauptbedienstelle gesetzt werden ZU ZU ZU Anzeige AUF Alarmausl sung RWA Ausl sung Motor Endmodul Motor Endmodul nur im letzten oder einzige...

Страница 27: ...5C38B592E 75 C9 4 D538 9C385 N 45BE 75 F B2581 D5 Netz Netz Netz sicherung 1 A tr ge Motor Rauchmelder Temperatursichering 72 C Modul 1 Modul 3 Modul 2 Motorsicherung 5 A tr ge Betrieb Akku Motor Haup...

Страница 28: ...Steuereinheit an eine VELUX Rauchableitung f r Treppenh user CSJ 1210 oder CSJ 1211 angeschlos sen ist wird das Gesamtsystem als eine Maschine betrachtet die erst dann bet tigt werden darf wenn sie na...

Страница 29: ......

Страница 30: ...30 VELUX...

Страница 31: ......

Страница 32: ...RADEMARKS USED UNDER LICENCE BY THE VELUX GROUP AT VELUX sterreich GmbH 02245 32 3 50 BE VELUX Belgium 010 42 09 0 CH VELUX Schweiz AG 062 289 44 45 DE VELUX Deutschland GmbH 040 54 70 70 FR VELUX Fra...

Отзывы: