Functionality

Important

Smoke exhaust systems must be serviced at least once a year by qualified personnel. As a reminder that mainte-

nance is due, the break-glass point is equipped with an automatic optical and acoustic maintenance alarm  

(see page 6).

Activation of fire alarm

Break-glass point

 

Break the glass cover and press the red button in the break-glass point. The staircase smoke exhaust is opened. An acoustic 

alarm (continuous) sounds from the break-glass point. 

All comfort ventilation functions are blocked.

 

Indication:

 The red alarm LED in the control unit and the red alarm LED in the break-glass point are on.

Smoke detector / temperature detector 

In the event of smoke development/high temperatures, this will result in automatic opening of the staircase smoke exhaust. 

An acoustic alarm (continuous) sounds in the break-glass point.  

All comfort ventilation functions are blocked. 

Indication: 

The red alarm LED in the control unit, the red alarm LED in the break-glass point and the red alarm LED in the 

activated automatic detector are on. 

Fire alarm system

 

The smoke detector input is used to trigger an alarm via a fire alarm system. Therefore, no smoke detectors should be con-

nected to the control unit.

 

This requires a potential-free normally open contact from the fire alarm system and the external 

alarm module (FAM monitoring module). 

After triggering the system, an acoustic alarm (continuous) sounds in the break-glass point.  

All comfort ventilation functions are blocked. 

Indication:

 The red alarm LED in the control unit and the red alarm LED in the break-glass point are on.

 

Resetting fire alarm

 

Press the RESET-button in the break-glass point or in the control unit. The acoustic alarm in the break-glass point stops.

Once the staircase smoke exhaust has been closed, the comfort ventilation functions are operational again. (After an alarm 

via an automatic detector, blow out smoke or replace the detector before resetting).

 

Indication: 

The red alarm LED in the control unit, the red alarm LED in the break-glass point and the red alarm LED in the 

activated automatic detector are off. 

Alarm triggered by high temperatures

 

If the inside temperature of the control unit rises above 72 °C, an error is displayed. An acoustic alarm (pulsing) sounds in 

the break-glass point. 

Indication:

 The yellow error LED in the break-glass point flashes. The green operation LED in the break-glass point and in 

the control unit respectively are off.

Note: 

The built-in temperature detector is irreversibly destroyed. The printed circuit board must be replaced.

Alarm triggered by error message 

If this function is activated (SW2/1 = ON, see page 6), an alarm triggers in case of high temperatures or a circuit error in 

either the motor, smoke detector or break-glass point. An acoustic alarm (continuous) sounds in the break-glass point. An 

error in the mains or battery circuits does not trigger an alarm. 

Indication:

 The red alarm LED in the control unit and the red alarm LED in the break-glass point are on.  

The yellow error LED in the break-glass point and the corresponding yellow error LED in the control unit flash.  

The green operation LED in the break-glass point and the control unit respectively are off.

Connecting control units

 

The control units can be connected using a monitored 2-core cable from the alarm/error module of the principal control unit 

to the smoke detector inputs of the additional control units.  

An error in the connected control units is detected via the 2-core cable. 

The error is only indicated in the control unit concerned and in the break-glass point of the principal control unit. There must 

be an alarm/error module in every control unit (see page 6).

Содержание KFC 100J

Страница 1: ...r VELUX Steuereinheit f r Rauchabzug KFC 100J ENGLISH Instructions for VELUX control unit for smoke exhaust KFC 100J 061 0 6 795 176 6 9 4 8 3 4 60 4 9 1 061 D1 4 3 59D5 F 1 42E38 538 9 6 0 6 1 6 6 6...

Страница 2: ...D5 75 59 D175 59D5 125 S 75 D125 5 59D5 5B 125 E 7C 1 59D5 C38 ECC 1 D1 41B4 59D5 C38 ECC 1 6UB 59D5 1D9 5 U25BC938D 59D5 Contents Cover sheet Contents Page 2 Important information Page 3 Functionalit...

Страница 3: ...lectronic equipment waste By sorting electrical and electronic equipment waste with this symbol you con tribute to reducing the volume of incinerated or buried waste and to reducing any negative impac...

Страница 4: ...s Once the staircase smoke exhaust has been closed the comfort ventilation functions are operational again After an alarm via an automatic detector blow out smoke or replace the detector before resett...

Страница 5: ...ditional modules optional Transmitting alarms and or error indications An alarm or an error indication can be transmitted potential free by inserting the alarm error indication module Multi error indi...

Страница 6: ...exhaust as long as the button on the ventilation switch is pressed and held dead man button SW 2 2 OFF Motors OPEN the staircase smoke exhaust once the ventilation switch is pressed Factory setting E...

Страница 7: ...a potential free fire alarm system contact at the smoke detector input fire alarm module insertion 8 24 V 100 mA on extra terminal Warning No 72 hour emergency power supply when in use Further techni...

Страница 8: ...5 D 95 1CD5B 9 59 5B T85 F 31 L U25B D95B5 General information Installation General information The back up batteries must be replaced every four years Retriggering the motors During the first 30 minu...

Страница 9: ...current of the control unit 4 8 A Maximum cable length always routed from the control unit to the last junction box Operation current Sum of all motor currents per group Cross section 3 x 1 5 mm 5 x...

Страница 10: ...Ventilation switches see cable length table Option transmission of wind rain alarm Option transmission of fire alarm Option transmission of multi error Option BUS 2 x 2 x O 8 mm or 5 x 1 5 mm 2 see c...

Страница 11: ...break glass point CLOSE CLOSE CLOSE Indicator OPEN Alarm Alarm Motor term module Only insert terminal mod ule in the last or only detector Only insert the motor ter minal module in the last or only mo...

Страница 12: ...e inserted in the last or only break glass point CLOSE CLOSE CLOSE Indicator OPEN Alarm Alarm Motor term module Only insert the motor ter minal module in the last or only motor Note If motors operate...

Страница 13: ...9 4 D538 9C385 N 45BE 75 F B2581 D5 Mains Mains Mains fuse 1 A slow Motor Smoke detector Temperature fuse 72 C Module 1 Module 3 Module 2 Motor fuse 5 A slow Operation Battery Motor Break glass point...

Страница 14: ...control unit is connected to VELUX staircase smoke exhaust CSJ 1210 or VELUX stair case smoke exhaust exit CSJ 1211 the total system is to be considered as a machine which is not to be put into servi...

Страница 15: ...75 59 D175 59D5 125 S 75 D125 5 59D5 5B 125 E 7C 1 59D5 C38 ECC 1 D1 41B4 59D5 C38 ECC 1 6UB 59D5 1D9 5 U25BC938D 59D5 Inhaltsverzeichnis Deckblatt Inhaltsverzeichnis Seite 15 Wichtige Informationen S...

Страница 16: ...ist nach nationalen Bestimmungen zu entsorgen Das Produkt einschlie lich eventuell vorhandener Batterien Akkus wird als ein Elektro und Elektronikger t betrachtet und enth lt gef hrliche Materialien...

Страница 17: ...geltenden Vorschriften zu belegen Es sind nur Originalersatzteile zu verwenden Bei der j hrlichen Wartung m ssen die angeschlossenen Produkte gem ihren Anleitungen gepr ft werden Die Leiterplatte berw...

Страница 18: ...r Rauchableitung sind die L ftungsfunktionen wieder in Betrieb Nach Ausl sung durch einen auto matischen Melder den Melder vor der R ckstellung ausblasen bzw erneuern Anzeige Die rote Alarm LED in der...

Страница 19: ...ch Aufstecken des Alarm St rungsmoduls potentialfrei weitergeleitet werden Sammelst rung 1 x Wechslerkontakt max 60 V 1 A mit 3 poliger Anschlussklemme zur potentialfreien Weiterleitung an GLT usw Ala...

Страница 20: ...d nur ber LEDs angezeigt Werkseinstellung SW 2 2 ON Antriebe fahren nur solange AUF wie der L ftungstaster bet tigt wird Totmann SW 2 2 OFF Antriebe fahren AUF sobald der L ftungstaster bet tigt wird...

Страница 21: ...t 7 Ansteuerung durch potentialfreien BMA Kontakt am Rauchmeldereingang BMA Modul einsetzen 8 24 V 100 mA auf extra Klemme Achtung Bei Benutzung keine 72 Stunden Notstrom Weitere technische Daten Nenn...

Страница 22: ...85 G95 9 C 9 9 4 41B75CD5 D 95 1CD5B 9 59 5B T85 F 31 L U25B D95B5 Allgemein Montage Allgemein Die Notstromakkus sind alle 4 Jahre auszuwechseln Nachtriggern der Antriebe W hrend der ersten 30 Minuten...

Страница 23: ...Melders zum ffnen der Rauchabzugsanlage f hrt Die Verlegeart Unterputz stellt keine zugelassene Verlegeart zum Erreichen eines Funktionserhaltes in Anlehnung an die DIN 4102 Teil 12 dar Der Funktions...

Страница 24: ...Kabell ngentabelle Option Weiterleitung Wind Regenmeldung Option Weiterleitung RWA Ausl sung Option Weiterleitung Sammelst rung Option BUS 2 x 2 x O 8 mm oder 5 x 1 5 mm 2 E30 s Kabell ngentabelle Au...

Страница 25: ...edienstelle gesetzt werden ZU ZU ZU Anzeige AUF Alarmausl sung RWA Ausl sung Motor Endmodul Aktives Endmodul nur im letzten oder einzigen Melder einsetzen Motor Endmodul nur im letzten oder einzigen A...

Страница 26: ...Jumper Achtung Jumper J1 muss in der letzten oder einzigen Hauptbedienstelle gesetzt werden ZU ZU ZU Anzeige AUF Alarmausl sung RWA Ausl sung Motor Endmodul Motor Endmodul nur im letzten oder einzige...

Страница 27: ...5C38B592E 75 C9 4 D538 9C385 N 45BE 75 F B2581 D5 Netz Netz Netz sicherung 1 A tr ge Motor Rauchmelder Temperatursichering 72 C Modul 1 Modul 3 Modul 2 Motorsicherung 5 A tr ge Betrieb Akku Motor Haup...

Страница 28: ...Steuereinheit an eine VELUX Rauchableitung f r Treppenh user CSJ 1210 oder CSJ 1211 angeschlos sen ist wird das Gesamtsystem als eine Maschine betrachtet die erst dann bet tigt werden darf wenn sie na...

Страница 29: ......

Страница 30: ...30 VELUX...

Страница 31: ......

Страница 32: ...RADEMARKS USED UNDER LICENCE BY THE VELUX GROUP AT VELUX sterreich GmbH 02245 32 3 50 BE VELUX Belgium 010 42 09 0 CH VELUX Schweiz AG 062 289 44 45 DE VELUX Deutschland GmbH 040 54 70 70 FR VELUX Fra...

Отзывы: