Alarm Setup
•
Alarm Input Level & Alert Setup
Command: PWD:XXXX,ALMLEVELR:X,YY,ZZZZ,NNN%
XXXX Password
R
Alarm channel number
X
0 means disabled
1 means closed triggers alarm
2 means open triggers alarm
3 means both closed and open triggered alarm
YY
00 means alarm not reported to control centre
10 means alarm reported to control centre 1
01 means alarm reported to control centre 2
11 means alarm reported to control centre 1 and 2
ZZZZ
Selection of the alarm phone dial and alarm SMS
0 means no alarm report
1 means SMS only
2 means phone dial only
3 means SMS first, then phone dial
ZZZZ
4
th
phone number
3
rd
phone number
2
nd
phone number
1
st
phone number
NNN
Relay output control
0 means no relay output control
1 means relay output triggered by alarm
NNN
3
rd
relay output (not available)
2
nd
relay output (not available)
1
st
relay output
Example 1:
PWD:1234,ALMLEVEL2:1,01,1030,100#%
Password 1234
Alarm channel 2
Once the input is closed, the alarm will be triggered
Control centre 2 will be reported by SMS
Phone number 1
Phone number 2
Phone number 3
Phone number 4
Relay output 1
Relay output 2
Relay output 3
SMS message
No report
SMS message, then phone dial
No report
Triggered
No control (not available)
No control (not available)