3. Technical specifications
3.1. Rated values
• Line voltage:
- Detection values
3.5...36 kV
- Measurement tolerance
± 10 %
• Indication time:
- Time delay
50, 100 ms
- Time tolerance
± 10 ms
• Frequency:
50 Hz; 60 Hz
• Output contacts:
- Voltage
380 V
ac
, 230 V
dc
- Current
16 A (ac)
- Switching power
500 VA
(resistive load)
• Power supply voltage:
- AC
17 V...260 V
- DC
17 V...360 V
- Consumption
< 2.5 W
• Temperature:
- Operation
- 40 °C...+ 60 °C
- Storage
- 40 °C...+ 70 °C
3.2. Mechanical design
• IP rating:
- Case IP47
- Terminals IP2X
- In cubicle
IP3X
• Dimensions:
- See attached diagram
100 x 180 x 40 mm
• Weight:
0.3 kg
• Connection:
- Cable/Terminal
0.5...2.5 mm
2
3.3. Insulation tests
• IEC 60255-5:
- Insulation resistance
500 V
dc
: > 0,7 GW
- Dielectric rigidity
2 kV
ac
; 50 Hz;
1 min
• Voltage pulses:
- Standard
5 kV; 1.2/50 µs;
0.5 J
- Differential
1 kV; 1.2/50 µs;
0.5 J