3.4. Electromagnetic compatibility
• IEC 60255-22-1:
- Damped wave 1 MHz
2.5 kV; 1 kV
• IEC 60255-22-2:
- Electrostatic discharges
8 kV
(IEC 61000-4-2, class IV)
• IEC 60255-22-3:
- Radiated fields
10 V/m
(IEC 61000-4-3, class III)
• IEC 60255-22-4:
- Bursts - Fast transients
2 kV
(IEC 61000-4-4)
• IEC 61000-4-5:
- Overvoltage pulses
4 kV; 2 kV
• IEC 61000-4-6:
- Induced radiofrequency
150 kHz...80 MHz
signals (EN 50082-2)
• IEC 61000-4-8:
- Magnetic fields
30 A/m; 50 Hz
(EN 50082-2)
• IEC 61000-4-12:
- Sinusoidal damped wave
2 kV; 1 kV
• EN 50081-2/55011:
- Radiated emissions Group 1, 150 kHz...30 MHz
Class A
3.5. Climatic tests
• IEC 60068-2-1:
- Slow changes. Cold
- 40 °C; 960 min
• IEC 60068-2-2:
- Slow changes. Heat
+ 60 °C; 120 min
+ 70 °C; 960 min
• IEC 60068-2-30:
- Damp heat cycles
+ 40 °C; 92%;
5760 min
3.6. Mechanical tests
• IEC 60255-21-1:
- Sinusoidal vibration. Response 10-150 Hz; 1 g
- Sinusoidal vibration. Endurance 10-150 Hz; 2 g
• IEC 60255-21-2:
- Impacts. Response
11 ms; 5 g
• Impact. Endurance
11 ms; 15 g
• Shock. Endurance
16 ms; 10 g