Solar Pump Controller Manual
40
H-64
CVT adjust voltage bias
limitation
Range
:
0
~
10.0% Factory
setting
:
0.0%
These parameters make bus voltage keep between H-62*(H-63 - H-64) and H-62*(H-63 + H-64) at
CVT mode
H-65
Dry run protection limit current Range
:
0
~
1000.0A Factory
setting
:
0.0A
While it valid, F-22 enters to dry run protection state if C-03 current bigger than H-65 limit current
and judge if dry protection again after F-23 time.
Note: [H-32
~
H-65] only valid while solar pump control mode ( E-02 set to 10)
Monitorin
g code
Content
Units
Communi
cation
code
C-1 Frequency
reference
0.01Hz C01H
C-2 Output
frequency
0.01Hz C02H
C-3 Output
current
0.1A C03H
C-4 Input
power
0.1KW C04H
C-5
DC Bus voltage
V
C05H
C-6 Bus
current
0.1A C06H
C-7
PID give value or search frequency step (while E-02=10)
%
C07H
C-8
PID feedback or CVT base voltage(while E-02=10)
%
C08H
C-9 Module
temperature
℃
C09H
C-10
Accumulative operation time (accumulate while
frequency higher than 0, not time while 0speed or stop)
Hour C0AH
C-11 Running
duration
time
Min C0BH
C-12
Bus bar current
0.1A
C0CH
C-13
PID adjust frequency(minus can not show)
%
C0DH
C-14
Input terminals connect/disconnect status
See
below
diagram
C0EH
C-15
Input terminals connect/disconnect status
See
below
diagram
C0FH
C-16
Terminal VS1 input value
0.1V
C10H
C-17 Terminal
AS
input
value
0.1mA C11H
C-18
Terminal VS2 input value
0.1V
C12H
C-19
Terminal pulse input value
※
C13H
C-20 Counter
record
※
C14H
C-21
DC bus voltage
V
C15H