Solar Pump Controller Manual
34
H-29
Sensor
disconnection alarm
operation selection
0:Continued operation
1:Close-down
0
●
31DH
H-30
Upper limit
demarcative values
Lower limit demarcative values
~
100.0%
100.0
●
31EH
H-31
lower limit
demarcative value
0.0%
~
Upper limit demarcative
values
0.0
●
31FH
H-32
Lowest run
frequency
0.00Hz
~
300.00Hz
20.00
●
320H
H-33
Lowest run
frequency duration
0.1
~
6500.0s 10.0
●
321H
H-34 Stop and wait time
0.1
~
6500.0s 30.0
●
322H
H-35
Automatic
dormancy voltage
0
~
1000V
※
●
323H
H-36
Renew voltage in
dormancy
0
~
1000V
※
●
324H
H-37
Max MPPT voltage
setting
0
~
1000V
※
●
325H
H-38
Min MPPT voltage
setting
0
~
1000V
※
●
326H
H-39
MPPT voltage
search interval
0.1
~
6500.0s 0.0
●
327H
H-40
MPPT voltage step
length
compensation
0
~
10.00Hz
1.00
●
328H
H-41 MPPT sample cycle
0.01
~
6500.00s 0.05
●
329H
H-42 Search repeat times 0
~
100 2
●
32AH
H-43
DC current detect
measuring range
0
~
1000.0A
0.0A
●
32BH
H-44
Smallest power
change value can
be identified
0
~
1000.0w 2.0w
●
32CH
H-45 Pump power
0
~
100.0KW
※
●
32DH
H-46
Search power
change value
0
~
1000W 10
●
32EH