Solar Pump Controller Manual
33
H-12
PID controller given
signal source
0:Keyboard potentiometer
1:PID keyboard number given
2:Exterior terminal VS1: 0
~
10V
3:Exterior terminal AS: 4
~
20mA
4:Exterior terminal VS2
(Bipolar Failure)
5:Exterior terminal pulse signal
6:RS485 interface setting
7:Max power voltage setting
7
〇
30CH
H-13
PID controller
feedback signal
source
0:Exterior terminal VS1: 0
~
10V
1:Exterior terminal AS: 4
~
20mA
2:Exterior terminal VS2
(bipolar failure)
3:Exterior terminal pulse signal
4: Bus voltage feedback
4
●
30DH
H-14 Start
frequency
0.00Hz
~
upper limit frequency
15.00
●
30EH
H-15
Start frequency
duration
0.0
~
6500.0s 10.0
●
30FH
H-16
PID keyboard
number given
0.0
~
100.0% 50.0
●
310H
H-17
Feedback channel
gain
0.01
~
5.00 1.00
●
311H
H-18
Sensor maximum
measuring range
1.0
~
100.0
100.0
●
312H
H-19 Proportion gain P
0.1
~
100.0 20.0
●
313H
H-20 integral time I
0.1
~
100.0 second
2.0
●
314H
H-21 Differential gain D
0.0
~
10.0
0.0
●
315H
H-22 Sampling
period
0.01
~
60.00 second
0.10
●
316H
H-23
PID control
deviation limit
0.0
~
20.0% 0.0
●
317H
H-24 Start
Threshold
0.0%
~
dormancy threshold
0.0
●
318H
H-25
Dormancy
Threshold
Start threshold
~
100.0%
100.0
●
319H
H-26
Alarm upper limit
value
Alarm lower limit value
~
100.0%
100.0
●
31AH
H-27
Alarm lower limit
value
0.0%
~
alarm upper limit value
0.0
●
31BH
H-28
Sensor
disconnection
detection values
0.0
~
20.0% 0.0
●
31CH