65
9 Diagnosis, asset management and service
VEGAPULS 67 • Profibus PA
36533-EN-170405
Code
Text message
Reason
Rectification
DevSpec
Diagnosis Bits
F264
Installation/Setup
error
•
Adjustment not within the vessel
height/measuring range
•
Max. measuring range of the
instrument not sufficient
•
Check or correct installation
and/or parameter settings
•
Use an instrument with bigger
measuring range
Bit 10
F265
Measurement func-
tion disturbed
•
Sensor no longer carries out a
measurement
•
Operating voltage too low
•
Check operating voltage
•
Carry out a reset
•
Disconnect operating voltage
briefly
Bit 11
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text message
Reason
Rectification
DevSpec
Diagnosis Bits
C700
Simulation active
•
A simulation is active
•
Finish simulation
•
Wait for the automatic end after
60 mins.
Bit 19
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Code
Text message
Reason
Rectification
DevSpec
Diagnosis Bits
S600
Impermissible elec-
tronics temperature
•
Temperature of the electronics
in the non-specified range
•
Check ambient temperature
•
Insulate electronics
•
Use instrument with higher
temperature range
Bit 18
S601
Overfilling
•
Danger of vessel overfilling
•
Make sure that there is no
further filling
•
Check level in the vessel
Bit 20
The following table shows the error codes and text messages in the
status message "
Maintenance
" and provides information on causes
as well as corrective measures.
Code
Text message
Reason
Rectification
DevSpec
Diagnosis Bits
M500
Error during the re-
set "delivery status"
•
The data could not be restored
during the reset to delivery
status
•
Repeat reset
•
Load XML file with sensor data
into the sensor
Bit 13
M501
Error in the non-
active linearisation
table
•
Hardware error EEPROM
•
Exchanging the electronics
•
Send instrument for repair
Bit 14
Function check
Out of specification
Maintenance