46
6 Set up with the display and adjustment module
VEGAPULS SR 68 • 4 … 20 mA/HART - two-wire
38294-EN-160707
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5. Save settings with
[OK]
To damp process-dependent measured value fluctuations, set an
integration time of 0 … 999 s in this menu item.
Depending on the sensor type, the factory setting is 0 s or 1 s.
In the menu item "
Current output mode
" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
In the menu item "
Current output Min./Max.
", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
Setup - Damping
Setup - Current output
mode
Setup - Current output
Min./Max.