9 Diagnosis, asset management and service
VEGAPULS SR 68 • 4 … 20 mA/HART - two-wire
38294-EN-160707
Code
Text message
Cause
Rectification
DevSpec State in CMD
48
F125
Impermissible electronics
temperature
– Temperature of the
electronics in the non-
specified range
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
Bit 7 of Byte 0…5
F260
Error in the calibration
– Error in the calibration
carried out in the factory
– Error in the EEPROM
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 8 of Byte 0…5
F261
Error in the instrument set-
tings
– Error during setup
– False signal suppression
faulty
– Error when carrying out
a reset
– Repeat setup
– Carry out a reset
Bit 9 of Byte 0…5
F264
Installation/Setup error
– Adjustment not within
the vessel height/meas-
uring range
– Max. measuring range
of the instrument not
sufficient
– Check or correct instal-
lation and/or parameter
adjustment
– Use an instrument with
bigger measuring range
Bit 10 of Byte 0…5
F265
Measurement function dis-
turbed
– Sensor no longer carries
out a measurement
– Operating voltage too
low
– Check operating voltage
– Carry out a reset
– Disconnect operating
voltage briefly
Bit 11 of Byte 0…5
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text message
Cause
Rectification
DevSpec State in CMD
48
C700
Simulation active
– A simulation is active
– Finish simulation
– Wait for the automatic
end after 60 mins.
"Simulation Active" in
"Standardized Status 0"
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Code
Text message
Cause
Rectification
DevSpec State in CMD
48
S600
Impermissible electronics
temperature
– Temperature of the
electronics in the non-
specified range
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
Bit 5 of Byte 14…24
Function check
Out of specification