38294-EN-160707
value memory as well as event memory remain untouched. The
linearisation is set to linear.
False signal suppression:
Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values, measured value:
Resetting of the measured min. and
max. distances to the actual measured value.
The following table shows the default values of the instrument. De-
pending on the instrument version, not all menu items are available or
some may be differently assigned:
Menu
Menu item
Default value
Setup
Measurement loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Application
Storage tank
Silo
Vessel form
Vessel bottom, dished form
Vessel top, dished form
Vessel height/Measur-
ing range
Recommended measuring range, see "
Technical data
"
in the supplement
Min. adjustment
Recommended measuring range, see "
Technical data
"
in the supplement
Max. adjustment
0,000 m(d)
Damping
0.0 s
Current output mode
4 … 20 mA, < 3.6 mA
Current output Min./Max.
Min. current 3.8 mA, max. current 20.5 mA
Lock adjustment
Released
Display
Language
Like order
Displayed value
Distance
Display unit
m
Scaling size
Volume
l
Scaling
0.00 lin %, 0 l
100.00 lin %, 100 l
Backlight
Switched on
Additional adjustments
Distance unit
m
Temperature unit
°C
Probe length
Length of the standpipe Ex factory
Linearisation curve
Linear
HART mode
Standard
Address 0