17
5 Connecting to power supply
VEGAMET 862 • 4 … 20 mA/HART
58867-EN-200312
5.4 Connecting
The voltage supply and inputs and outputs are connected via the
spring-loaded terminals.
Information:
Solid cores as well as flexible cores with wire end sleeves are
inserted directly into the terminal openings. In case of flexible cores
without end sleeves, a small screwdriver must be pressed into the
rectangular opening so that the terminal opening is then free. When
the screwdriver is pulled out, the terminals are closed again.
You can find further information on the max. wire cross-section in the
technical data.
Connect the device as described in the following wiring plan.
5.5 Wiring plan
1
2
3
1
2
3
4
212223
91 92
L N
+ -
+ - + - + -
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78
41 42 43 44 45 46
1 2 3
4 5 6
242526 272829303132
Power
6
5
4
3
2
1
Sensor 1
Relay Output
Current Output
Digital IN
Sensor 2
5
1
2
3
6
7
4
8
Fig. 6: Wiring plan VEGAMET 862
1 Voltage supply of the controller
2 Relay outputs 1 … 6
3 Current outputs 1 … 3
4 Sensor inputs 1/2 (active/passive)
5 Digital inputs 1 … 4
6 Ground terminal for protective conductor
7 Ground terminal for cable screening
8 Ground terminal for potential equalization
Connection technology
Connecting