23
7 Set up with the integrated display and adjustment unit
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
When the [+] and [->] keys are pressed quickly, the edited value,
or the cursor, changes one value or position at a time. If the key is
pressed longer than 1 s, the value or position changes continuously.
Approx. 60 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with [OK] will not be saved.
7.2 Display
The measured value display shows the digital display value, the
measuring loop name ( measurement loop TAG) and the unit. In addi-
tion, an analogue bargraph can be displayed. Up to three measured
value windows with different measured values can be configured. If
pump control is activated, an additional status bar with display of the
assigned pumps is available.
Measured values are displayed according to the following presenta-
tion:
1
2
3
4
5
6
7
TAG-No. 1
%
47.8
1 2
Fig. 11: Example measured value indication (measured value with bargraph)
1 Measurement loop name
2 Measured value
3 Unit
4 Status message acc. to NAMUR NE 107
5 Status bar for pump control
6 Bargraph measured value
7 Display active measured value window
The menu items are displayed according to the following presentation:
1
2
Max. adjustment
Sensor value at 100% :
Actual measured sensor value :
19.970
mA
20.000
mA
Fig. 12: Menu item display (example)
1 Sensor measured value at 100 %
2 Current sensor measured value
Time functions
Measured value indica-
tion
Menu item display