12 Diagnostics and servicing
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
Error code
Cause
Rectification
F040
General hard-
ware error
Hardware error
Switch the instrument off and on
Carry out a reset
Send instrument for repair
Error code
Cause
Rectification
S007
Sensor input:
Type not com-
patible
Sensor type not
compatible
Search for sensor again and allocate
under "
Meas. loop - Input
"
S016
Adjustment:
Min./Max. ex-
changed
The min./max.
adjustment
points were ex-
changed.
Carry out the adjustment again, correct
the min. and max. values.
S017
Adjustment:
Span too small
Adjustment span
too small
Carry out a fresh adjustment and in-
crease the distance between min./max.
adjustment
S021
Scaling: Span
too small
Scaling span too
small
Carry out a fresh scaling, increase the
distance between min./max. scaling.
S022
Scaling: Scaling
value too large
Value for one
of the two scal-
ing points is too
large
Carry out the scaling again, correct the
min. and max. values.
S030
Measured value
not valid
The connect-
ed sensor is still
in the start-up
phase or is inter-
rupted
Check sensor
S053
Sensor measur-
ing range faulty
Sensor meas-
uring range was
not read cor-
rectly
Restart instrument
S062
Pulse priority too
small
Pulse priority too
small
Increase under "
Output
" the entry
"
Pulse output all
" so that max. one pulse
per second is output.
S110
Relay: Span too
small
Relay switching
points too close
together
Increase the difference between the two
relay switching points
S111
Relay: Switching
points inter-
changed
Relay switching
points inter-
changed
Change relay switching points for "
On/
Off
"
Out of specification