P
robable failures of the pumps can be processed in addition via the
digital inputs
.
W
ith this pump control
,
there are two di
ff
erent versions
:
l
P
ump control
1
:
T
he upper switching point determines the switch
-
o
ff
point for the relay
,
whereas the lower switching point
determines the switch
-
on point
l
P
ump control
2
:
T
he upper switching point determines the switch
-
on point for the relay
,
whereas the lower switching point
determines the switch
-
o
ff
point
T
wo pumps should empty the vessel when a certain level is reached
.
A
t
80
%
fi
lling
,
the pump with the shortest running time should switch
on
.
I
f the level nevertheless increases
,
a second pump should switch
on at
90
%
.
B
oth pumps should switch o
ff
again at
10
%
fi
lling
.
S
elect in the
DTM
navigation section the menu items
"
M
eas
.
loop
-
O
utputs
-
R
elay
"
.
l
S
et mode
"
P
ump control
2
"
for relay
1
and
2
.
l
E
nter the switching points for the concerned relays as follows
:
-
R
elay
1
upper switching point
=
80
.
0
%
-
R
elay
1
lower switching point
=
10
.
0
%
-
R
elay
2
upper switching point
=
90
.
0
%
-
R
elay
2
lower switching point
=
10
.
0
%
T
he function of pump control
2
is shown in detail in the following
diagram
.
T
he previously described example is used as a basis
.
Rel. 1: 80% On
On
Off
Off
On
Rel. 2: 90% On
Rel. 1, 2: 10% Off
10
30
20
20
15
t [h]
5
Rel. 1
Rel. 2
F
ig
.
12
:
E
xample of a pump control
2
W
ith a pump control
,
there is also the option of switching on pump
monitoring
.
F
or this
,
a return signal on the respective digital input is
required
.
T
he assignment of the digital inputs to the relais is preset
:
l
D
igital input
1
-
R
elay
1
l
D
igital input
2
-
R
elay
2
l
D
igital input
3
-
R
elay
3
E
xample
S
etup
VEGAMET
391
•
4
…
20
m
A
/
HART
signal conditioning instrument
43
8
A
pplication examples
36032
-
EN
-
091116