background image

VEGALOG 571

21

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

Pos. A

Pos. A

Pos. A

Product description

Application:

Flow measurement

Sensor:

Hydrostatic pressure transmitters
Ultrasonic sensors
Radar sensors

Mode:

Standard

Option:

none

Parameter:

Flow

Application:

Distance measurement

Sensor:

Ultrasonic sensors
Radar sensors

Mode:

Standard

Option:

none

Parameter:

Distance

Application:

Level detection

Sensor:

Capacitive electrodes
Vibrating level switch

Mode:

Standard

Option:

none

Parameter:

Level

Application:

Connection of a switching contact

Sensor:

External switching contact

Mode:

Standard

Option:

none

Parameter:

Switching condition

Application:

Connection of a 4 … 20 mA-instrument

Sensor:

4 … 20 mA-instrument (active)

Mode:

Standard

Option:

none

Parameter:

Current

Application:

Temperature measurement

Sensor:

0/4 … 20 mA-instrument
Temperature of VBUS-sensors (multi-sensor)

Mode:

Standard temperature measurement

Option

0 … 20 mA-instrument
4 … 20 mA-instrument

Parameter:

Temperature

Distance measurement

Level detection

Connection of an external switch-
ing contact

Connection of a 4␣ …␣ 20␣ mA-
instrument

Flow measurement

4 … 20 mA

Pos. A

Pos. A

Содержание VEGALOG 571

Страница 1: ...Level and Pressure in out Operating Instructions VEGALOG 571 on on on PC on VEGALOG 1 2 3 4 5 6 7 8 9 10 571 CPU VEGALOG 571 EA VEGALOG 571 EV VEGALOG 571 AR...

Страница 2: ...Mounting in carrier 25 2 3 Selection of the plug position 26 2 4 Coding 26 2 5 Co ordination 27 3 Electrical connection 3 1 General connection instructions 28 3 2 Coupling of the carriers 29 3 3 Inter...

Страница 3: ...s not take responsibility Note Ex area Please note the approval documents attached yellow binder and especially the included safety data sheet 4 Set up 4 1 Indicating and adjustment elements 38 4 2 Ad...

Страница 4: ...signal 0 4 20 mA as voltage signal 0 2 10 V as relay transistor contact as digital signal RS 232 interface Adjustment surface The adjustment of VEGALOG 571 is made by a PC connected via an RS 232 cabl...

Страница 5: ...ement loop Product description DCS components DCS telegram to VEGA COM 557 Functional components Parameter for meas loop 1 meas loop 2 meas loop 255 Input components Analogue inputs current inputs 0 2...

Страница 6: ...on the number of measurement loops CPU cards in different performances of up to 15 30 60 or 255 measurement loops are available The CPU reads cyclically measured values from the peripheral cards with...

Страница 7: ...n of different VBUS sensors via common two wire line This means that a transmission is avail able which is not only optimally adapted to the conditions of the level measurement but also has increased...

Страница 8: ...rovides 10 relay outputs with floating spdt The following instruments can be connected acoustic or optic signallers magnet valves contactors etc The AR card is suitable for the output of level individ...

Страница 9: ...d can be used exclu sively to provide the data of VEGALOG to the visualisation software Visual VEGA VV For this purpose the communication card is also available without interface converter function Ad...

Страница 10: ...nologies Electrical protective measures Protection not mounted IP 00 in carrier BGT LOG 571 front side completely equipped IP 40 upper and lower side IP 20 wiring side IP 00 Protection class I in carr...

Страница 11: ...ectrodes hydrostatic pressure transmitters vibrating level switches conductive electrodes process and differential pressure transmitters Further connection possibilities external current sources 0 20...

Страница 12: ...asonic sensors radar sensors Sensor supply voltage 3 x 24 V DC 1 A short circuit proof for 5 sensors each Connection line 2 wire screening recommended Line length max 1000 m 1 Resistance per conductor...

Страница 13: ...V Common potential between current outputs GND Indicating elements LED in front facia green on mains voltage on red fault signal AD card DISBUS output Number 1 output Function digital transmission of...

Страница 14: ...cc to VDE 0106 from relays to the power supply and part 1 LOGBUS connection reference voltage 250 V isolation resistance 2 3 kV Galvanic isolation between among relays reference voltage 250 V isolatio...

Страница 15: ...ecommended Line length max 1000 m Meas data input LOGBUS Data transmission LOGBUS digital data transmission Connection line connection via BUS plug PC interface Interface standard RS 232 C Line length...

Страница 16: ...gulations of EMVG 89 336 EWG and NSR 73 23 EWG The conformity has been judged acc to the following standards VEGASTAB 593 594 VEGASTAB 593 60 EMVG Emission EN 50 081 1 EN 50 081 1 Susceptibility EN 50...

Страница 17: ...0 Power supply Input voltage Unom 230 V AC 196 264 V 50 60 Hz 110 V AC 94 127 V 50 60 Hz 120 V AC 102 138 V 50 60 Hz Input current effective 230 V max 0 5 A 110 V 120 V max 1 0 A Fuse 5 x 20 mm in the...

Страница 18: ...other module cards of VEGALOG CPU card 162 100 5 5 128 4 25 4 5 TE 9 on 571 CPU PC VEGALOG Multipoint connector 100 x 160 x 1 5 European size Multiple plug LOGBUS plug Power supply card VEGASTAB Produ...

Страница 19: ...easurement loop Click in the main window of VVO on Configuration point to Measurement loop and click on New Then confirm the adjustment a new application with OK In the next window Create new measure...

Страница 20: ...eal value correction Zero point correction Density correction Parameter Level Application Gauge measurement Sensor Hydrostatic pressure transmitters Ultrasonic sensors Radar sensors Mode Standard Opti...

Страница 21: ...Level Application Connection of a switching contact Sensor External switching contact Mode Standard Option none Parameter Switching condition Application Connection of a 4 20 mA instrument Sensor 4 2...

Страница 22: ...o point correction Real value correction Density correction Parameter Level Density Not corrected level Application Level difference Sensor Ultrasonic sensors Radar sensors Mode Difference Option Real...

Страница 23: ...y measurement Sensor Hydrostatic pressure transmitters Process pressure transmitters Mode Standard Option Zero point correction Parameter Density Level Not corrected level Application Arithmetic measu...

Страница 24: ...value e g 40 Real value correction Density correction incorrect course of measured values incorrect course of measured values higher density measured value too high lower density measured value too lo...

Страница 25: ...arrier are mounted one above the other when more than 2 5 W TE are consumed in the carrier when there is no air circulation in the range of the carrier Mounting 2 2 Mounting in carrier The carrier BGT...

Страница 26: ...stem avoids inter changing among the different module cards in the carrier It consists of two coded pins in the multipoint connector in the carrier two holes in the multiple plug of the appro priate c...

Страница 27: ...r supply used Mounting 1 2 3 4 5 6 7 8 910111213141516 17181920212223242526272829303132 Module no Card max power re TE no quirement W 1 5 2 10 3 15 4 20 5 25 6 30 7 35 8 40 9 45 10 50 11 55 12 60 13 6...

Страница 28: ...e neces sary wire cross sections must be main tained if overvoltages are expected we recom mend a sensors electronic with integral overvoltage protection or the installation of VEGA overvoltage arrest...

Страница 29: ...le hook switch for termination resistor slide switch Configuration with one rack Hook switch closed Slide switch position M Configuration with two racks Rack 1 Hook switch closed Slide switch position...

Страница 30: ...nic radar sensors or pressure transmitters max 5 ultrasonic radar sensors or pressure transmitters max 5 ultrasonic radar sensors or pressure transmitters Note All 10 sensor inputs z14 z32 are connect...

Страница 31: ...6 8 4 Supply voltage Supply voltage Supply voltage Note The connections z14 z32 are connected broken line Relay output 1 d14 b14 z14 2 d16 b16 z16 3 d18 b18 z18 4 d20 b20 z20 5 d22 b22 z22 6 d24 b24 z...

Страница 32: ...ne common power supply unit with additional voltage the connected sensors are galvanically connected among each other Each branch with max five sensors is short circuit proof The integral current limi...

Страница 33: ...5 10 15 20 25 1000 900 800 700 600 500 400 300 200 100 0 0 5 10 15 20 25 For graphic determination the following pro cedure is recommended consider each branch separately determine the power consumpti...

Страница 34: ...ts an own line pair not rec ommended VEGALOG 571 with EV card VEGALOG 571 with EV card VEGALOG 571 with EV card Line length up to 1000 m Line length up to 1000 m Line length max 100 m per sensor 3 7 S...

Страница 35: ...s well as the used sepa rating facility must only be mounted out side the Ex area a separating wall must be added between connection parts of intrinsically and not intrinsically safe circuits so that...

Страница 36: ...V Ex EV card Ultrasonic or radar on VEGALOG 571 EV 11 12 1 2 ia Trennbarriere Typ 145 Ausgang Zone 0 Eingang Ex area Not Ex area Pressure transmitter EA card Safety barrier type 145 The sum of the inn...

Страница 37: ...0 1nF searched Determination of the line data Lint 1 mH 0 065 mH 0 13 mH 0 805 mH Cint 580 nF 0 nF 1nF 579 nF Calculation of the line length 0 805 mH l m 1 238 m 0 65 H 579 nF l m 4 825 m 120 pF Consi...

Страница 38: ...fication of the min max adjustment the integration time etc The already configured measuring system is now optimally adapted to the appli cation Configuration of VEGALOG The plug position for the indi...

Страница 39: ...X In this window you can modify sensor desig nations Sensor TAG and enter serial num bers manually Click on the appropriate sensor and then click on Configure Your VEGALOG is now shown in your con fig...

Страница 40: ...s of the CPU e g a total power loss of the CPU With Quit you return to the main window of VVO Create new measurement loops A number of applications can be created in VEGALOG with the adjustment softwa...

Страница 41: ...rd 4 ana logue inputs input no 2 If you now click on Info you see to which card terminals the sensor must be connected With OK you return to the window Create new measure ment loop Sensor configuratio...

Страница 42: ...is possible to undo this co ordination When you have finished the current outputs click on OK Proceed in the same way for the other outputs It is also possible to adjust the mode standard reset of ala...

Страница 43: ...an click on the functions relevant for your measurement loop e g when you have a measurement loop with VBUS sensor then only the button Sensor optimisation is active Move through the functions Adjustm...

Страница 44: ...rief communication problems up to 1 sec on the LOGBUS do not effect the status indi cation Hardware failure Permanent lighting of the red LED means a hardware failure 5 3 Failure removal In order to d...

Страница 45: ...then possible Furthermore levels and fault signals are displayed 6 2 Communication By means of the interface converter VEGA COM 557 measured data and status infor mation of the CPU and the peripheral...

Страница 46: ...lly via VEGACON NECT VEGASON VEGAPULS via VEGACON NECT to the signal line or on the sensor Supplement 6 3 Components for configuration LOGBUS PLC DCS PC DISBUS 2 Visual VEGA Visualisation software for...

Страница 47: ...EGACOM 557 5 VEGACONNECT 2 Connection cable interface converter be tween VEGA instruments pressure transmit ters VEGASON VEGAPULS VEGAMET and a PC in conjunction with the adjustment software VEGA Visu...

Страница 48: ...lding 505 Yardley PA 19067 7706 Tel 215 321 6012 Fax 215 321 6067 Tech Support Toll Free 866 DrLevel or 888 NIVELCO Email info DrLevel com or info hitechtech com Web Site www DrLevel com or www hitech...

Отзывы: