30
9 Supplement
VEGACAP 67 • Two-wire
31317-EN-200929
Ʋ
Gravity weight
1800 g (64 oz)
Ʋ
Rod weight: ø 15 mm (0.591 in)
1400 g/m (15 oz/ft)
Ʋ
Cable weight: ø 8 mm (0.315 in)
400 g/m (4.3 oz/ft)
Sensor length (L)
Ʋ
Rod (ø 15 mm/0.591 in)
0.275 … 6 m (0.902 … 19.69 ft)
Ʋ
Cable (ø 8 mm/0.315 in)
0.53 … 40 m (1.74 … 131.23 ft)
Supporting tube length L1
0.2 … 5.6 m (0.656 … 18.37 ft)
Max. lateral load
10 Nm (7.4 lbf ft)
Max. tensile load (cable)
Ʋ
Ceramic partly insulated: ø 8 mm
(0.315 in)
10 KN (2248 lbf)
Max. torque (process fitting - thread)
80 Nm (58 lbf ft)
Torque for NPT cable glands and Conduit tubes
Ʋ
Plastic housing
max. 10 Nm (7.376 lbf ft)
Ʋ
Aluminium/Stainless steel housing
max. 50 Nm (36.88 lbf ft)
Measuring frequency
430 kHz
Output variable
Output
Two-wire output
Suitable controllers
VEGATOR 141, 142, 620, 621, 622
Output signal
> 4 … < 20 mA (not standardised)
Fault message
< 2.3 mA
Switching delay
Ʋ
When immersed
0.7 s
Ʋ
When laid bare
0.7 s
Ʋ
In the event of a fault
1 s
Measurement accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ
Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ
Relative humidity
45 … 75 %
Ʋ
Air pressure
+860 … +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)
Deviation due to strong, high-frequency
electromagnetic fields acc. to EN 61326
< 3 % of the adjusted measuring range
2)
Influence of the ambient temperature
< 0.15 %/10 K of the adjusted measuring range
3)
Ambient conditions
Ambient temperature on the housing
-40 … +80 °C (-40 … +176 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
2)
Distance from the process fittings to the set switching point.
3)
Distance from the process fittings to the set switching point.