background image

4

1 About this document

VEGACAL 66 • Foundation Fieldbus

30038-EN-200929

1  About this document

1.1 Function

This instruction provides all the information you need for mounting, 

connection and setup as well as important instructions for mainte-

nance, fault rectification, the exchange of parts and the safety of the 

user. Please read this information before putting the instrument into 

operation and keep this manual accessible in the immediate vicinity 

of the device.

1.2  Target group

This operating instructions manual is directed to trained personnel. 

The contents of this manual must be made available to the qualified 

personnel and implemented.

1.3  Symbols used

Document ID

This symbol on the front page of this instruction refers to the Docu-

ment ID. By entering the Document ID on www.vega.com you will 

reach the document download. 

Information, note, tip:

 This symbol indicates helpful additional infor-

mation and tips for successful work. 

Note:

 This symbol indicates notes to prevent failures, malfunctions, 

damage to devices or plants. 

Caution:

 Non-observance of the information marked with this symbol 

may result in personal injury. 

Warning:

 Non-observance of the information marked with this symbol 

may result in serious or fatal personal injury. 

Danger: 

Non-observance of the information marked with this symbol 

results in serious or fatal personal injury. 

Ex applications

This symbol indicates special instructions for Ex applications.

• 

List

The dot set in front indicates a list with no implied sequence.

1  Sequence of actions

Numbers set in front indicate successive steps in a procedure.

Battery disposal

This symbol indicates special information about the disposal of bat-

teries and accumulators.

Содержание VEGACAL 66

Страница 1: ...Operating Instructions Capacitive cable electrode for continuous level measurement VEGACAL 66 Foundation Fieldbus Document ID 30038...

Страница 2: ...ons 14 4 2 Mounting instructions 16 5 Connecting to power supply 19 5 1 Preparing the connection 19 5 2 Connection procedure 20 5 3 Wiring plan single chamber housing 20 5 4 Wiring plan double chamber...

Страница 3: ...2 Rectify faults 44 9 3 Exchanging the electronics module 45 9 4 How to proceed if a repair is necessary 46 10 Dismount 47 10 1 Dismounting steps 47 10 2 Disposal 47 11 Supplement 48 11 1 Technical d...

Страница 4: ...t ID By entering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successful work Note This...

Страница 5: ...lying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi ble for the trouble free operation o...

Страница 6: ...Installations in the US shall comply with the relevant requirements of the National Electrical Code ANSI NFPA 70 Installations in Canada shall comply with the relevant requirements of the Canadian El...

Страница 7: ...tes Information Optional instrument features are also described in this operating instructions manual The respective scope of delivery results from the order specification This operating instructions...

Страница 8: ...2 3 Fig 1 VEGACAL 66 cable version with plastic housing 1 Housing lid with integrated display and adjustment module optional 2 Housing with electronics 3 Process fitting The type label contains the mo...

Страница 9: ...via www vega com Search You can find the serial number on the inside of the instrument as well as on the type label on the outside The type label contains the serial number of the instrument With it y...

Страница 10: ...to a level proportional signal Power is supplied via the H1 Fieldbus A two wire cable according to Fieldbus specification serves as carrier of both power and digital data for multiple sensors This cab...

Страница 11: ...of the packaging material via specialised recycling companies Transport must be carried out in due consideration of the notes on the transport packaging Nonobservance of these instructions can cause...

Страница 12: ...ensors with HART protocol It is looped into the 4 20 mA HART signal cable The PLICSMOBILE T81 is an external GSM GPRS UMTS radio unit for transmission of measured values and for remote parameter adjus...

Страница 13: ...otective cover protects the sensor housing against soiling and intense heat from solar radiation Screwed flanges are available in different versions according to the following standards DIN 2501 EN 10...

Страница 14: ...30 without the use of any tools You can also install the display and adjustment module in four different positions each displaced by 90 Devices with threaded fitting are screwed into the process fitti...

Страница 15: ...e g covering the thread with teflon tape can interrupt the necessary electrical connection with metal vessels For this reason ground the probe on the vessel or use a conductive seal material Metal ve...

Страница 16: ...ossible to have the cable entries screwed in at the factory The free openings for the cable glands are therefore covered with red dust protection caps as transport protection Prior to setup you have t...

Страница 17: ...as measurement is then possible down to the bottom Caution It is not possible to measure on the gravity weight The measuring range of the probe ends at the upper edge of the gravity weight If the inst...

Страница 18: ...18 4 Mounting VEGACAL 66 Foundation Fieldbus 30038 EN 200929 Fig 7 Inflowing medium...

Страница 19: ...cording to the Fieldbus specification In particular make sure that the bus is termi nated with suitable terminating resistors Metric threads In the case of instrument housings with metric thread the c...

Страница 20: ...pprox 1 cm 0 4 in of insulation from the ends of the individual wires 5 Insert the cable into the sensor through the cable entry 6 Lift the opening levers of the terminals with a screwdriver see follo...

Страница 21: ...ind plug with version IP66 IP68 1 bar for Aluminium and stainless steel I C 5 1 2 4 3 Display Typ 1 2 5 6 7 8 Bus Sim Fig 10 Electronics and connection compartment single chamber housing 1 Spring load...

Страница 22: ...4 Wiring plan double chamber housing The following illustrations apply to the non Ex as well as to the Ex ia version 1 2 3 4 5 Fig 12 Double chamber housing 1 Housing cover connection compartment 2 B...

Страница 23: ...or display and adjustment module 3 Interface for service 4 Internal connection cable to the connection compartment 5 Ground terminal for connection of the cable screening 1 2 3 Display 1 2 I2C Fig 14...

Страница 24: ...g cover connection compartment 2 Blind plug or plug M12 x 1 for VEGADIS 81 optional 3 Housing cover electronics compartment 4 Filter element for air pressure compensation 5 Cable gland 1 3 2 Display 1...

Страница 25: ...ly and cable screen 2 Ground terminal for connection of the cable screening 1 1 2 Fig 19 Wiring plan Ex d ia double chamber housing 1 Voltage supply signal output 5 6 Wiring plan version IP66 IP68 1 b...

Страница 26: ...Insert display and adjustment module The display and adjustment module can be inserted into the sensor and removed again at any time It is not necessary to interrupt the voltage supply Proceed as foll...

Страница 27: ...list entry Select editing position key Change value of the parameter ESC key Interrupt input Jump to next higher menu The instrument is operated via the four keys of the display and adjustment module...

Страница 28: ...l cannot be emptied or filled completely you can carry out the adjustment also with two known levels for example with 10 and 90 The difference between the empty and full adjustment values should be as...

Страница 29: ...adjustment is displayed Min adjustment 0 00 0 0 pF 54 5 pF 3 Prepare the adjustment value for editing with OK Move to the selection window with OK Min adjustment Accept current measured value Accept E...

Страница 30: ...be longer and the sensor will react to measured value changes with a delay In general a period of a few seconds is sufficient to smooth the measured value display Damping 0 s Enter the requested param...

Страница 31: ...o maintain the function of the device the lighting is temporarily switched off if the power supply is insufficient Backlight In the default setting the lightning is switched off The respective min and...

Страница 32: ...tput This allows you to test the signal path e g through connected indicating instruments or the input card of the control system The following simulation variables are available Percent Current Press...

Страница 33: ...icator The min and max values are reset to the actual value The sensor is already set to the ordered national language In this menu item you can change the language The following languages are availab...

Страница 34: ...ted Measuring principle Signal output Copy sensor data Copy sensor data In this menu item the PIN is activated deactivated permanently Entering a 4 digit PIN protects the sensor data against unauthori...

Страница 35: ...ce ID Sensor TAG Device ID max 32 characters Sensor TAG PD_TAG max 32 characters Sensor details e g approval process fitting seal measuring cell measuring range electronics housing cable entry plug ca...

Страница 36: ...hed on Diagnostics Basic adjustment 3 Display Diagnostics Service Info Peak value indicator 3 1 Capacit min 65 7 pF Capacit max 782 4 pF Sensor status 3 2 OK Trend recording 3 3 Presentation of the tr...

Страница 37: ...5 4 05 March 2012 Sensor characteristics 5 5 Display now 6 6 Saving the parameterisation data We recommended writing down the adjustment data e g in this op erating instructions manual and archiving t...

Страница 38: ...ensor via the interface adapter VEGACONNECT 1 USB cable to the PC 2 Schnittstellenadapter VEGACONNECT 3 Sensor 1 2 3 4 OP EN TWIST USB LO CK Fig 24 Connection via interface adapter VEGACONNECT externa...

Страница 39: ...t all described functions are included in older firmware versions You can download the latest instrument software from our homepage A description of the update procedure is also available in the Inter...

Страница 40: ...able on CD from the agency serving you 7 3 Parameter adjustment with AMS and PDM For VEGA sensors instrument descriptions for the adjustment programs AMS and PDM are available as DD or EDD The instru...

Страница 41: ...Off Fig 26 Activate Bluetooth 1 Bluetooth switch On Bluetooth active Off Bluetooth not active The security concept of Bluetooth operation absolutely requires that the default setting of the sensor PIN...

Страница 42: ...n For access authentication with Bluetooth the modi fied PIN is still effective Information Bluetooth communication functions only if the actual sensor PIN dif fers from the default setting 0000 8 2 C...

Страница 43: ...isplayed For the first connection the operating device and the sensor must authenticate each other After successful authentication the next con nection functions without authentication For authenticat...

Страница 44: ...ocedure is described below Further comprehensive diagnostics can be carried out on a PC with the software PACTware and the suitable DTM In many cases the causes can be determined and the faults rectif...

Страница 45: ...ing of intrinsically safe circuits must be observed Error Cause Rectification E013 no measured value avail able Probe insulation damaged short circuit due to per meating conductive medium Exchange the...

Страница 46: ...find a suit able electronics module in the following overview The oscillators differ only in their signal output and are suitable for all series 60 sensors The following types are available CL E60 H 4...

Страница 47: ...y spe cialised recycling companies We use recyclable materials and have designed the electronics to be easily separable WEEE directive The instrument does not fall in the scope of the EU WEEE directiv...

Страница 48: ...d PTFE Gravity weight 316L Screening tube 316L Materials non wetted parts Probe cable fully PTFE insulated 8 mm 0 315 in 316L Plastic housing Plastic PBT Polyester Aluminium die cast housing Aluminium...

Страница 49: ...hannel 1 Primary value Channel 2 Secondary value 1 Channel 3 Secondary value 2 Transmission rate 31 25 Kbit s Current value 10 mA 0 5 mA Damping 63 of the input variable 0 999 s adjustable Input varia...

Страница 50: ...mperature 1 Process temperature 2 Ambient temperature Dielectric constant 1 5 Electromechanical data version IP66 IP67 and IP66 IP68 0 2 bar Options of the cable entry Cable entry M20 x 1 5 NPT Cable...

Страница 51: ...n window Polyester foil Voltage supply Operating voltage 9 32 V DC Operating voltage UB with lighting switched on 12 32 V DC Power supply by max number of sensors 32 Potential connections and electric...

Страница 52: ...Protection class II IEC 61010 1 Approvals Instruments with approvals can have different technical specifications depending on the version For that reason the associated approval documents of these in...

Страница 53: ...ALE DIRECT INDIRECT INDIRECT SQRT pF Lin Primary Value Secondary Value 2 Secondary Value 1 AI 2 AI 1 TB Sensor_Value min max adjustment Linearization Channel 1 Primary Value Channel 2 Secondary Value...

Страница 54: ...NNEL 1 is selected The unit is defined in primary_value_unit primary_value_unit Selected unit code for primary_value secondary_value_1 This is the process value after adjustment with the status of the...

Страница 55: ...d point of the sensor_value It refers to cal_ level_hi The unit is defined in sensor_range Units Index Calibration Lowest Point Min Max adjustment this is the lower calibrated point of the sensor_valu...

Страница 56: ...9 mm 2 72 79 mm 3 11 112 mm 4 41 M20x1 5 NPT 84 mm 3 31 M16x1 5 112 mm 4 41 M20x1 5 NPT 1 2 79 mm 3 11 Fig 31 Housing versions in protection IP66 IP67 with integrated display and adjustment module the...

Страница 57: ...2 L G 1 G 1 56 mm 2 21 12 mm 0 47 20 mm 0 79 36 mm 1 42 30 mm 1 18 22 mm 0 87 1 2 Fig 33 VEGACAL 66 threaded version G1 ISO 228 T1 L Sensor length see chapter Technical data 1 Gravity weight Process f...

Страница 58: ...nt VEGACAL 66 Foundation Fieldbus 30038 EN 200929 16 mm 0 63 27 mm 1 06 L 7 mm 0 28 Fig 34 VEGACAL 66 screening tube for example against strong condensation L Length of the screening tube see chapter...

Страница 59: ...nen unter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas...

Страница 60: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: