15
5 Set up with the display and adjustment module
VEGABAR 82 • Slave sensor for electronic differential pressure
46332-EN-160212
The quick setup for interface measurement is finished.
4. Unit, static pressure
In this menu item, you determine the unit of the static, i.e. superim
-
posed pressure.
5. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) on the measured value.
6. Distance
In this menu item, you enter the installation distance between master
and slave sensor.
7. Min. adjustment
In this menu item you carry out the min. adjustment for level.
Enter the percentage value and the corresponding pressure value for
the min. level.
8. Max. adjustment
In this menu item you carry out the max. adjustment for level.
Enter the percentage value and the corresponding pressure value for
the max. level.
The quick setup for density-compensated level measurement is
hence finished.
5.2 Parameter adjustment - Extended adjustment
For technically demanding measuring points, you can carry out
extended settings in "
Extended adjustment
".
The main menu is divided into five sections with the following func
-
tions:
Setup:
Settings, e.g., for measurement loop name, application, units,
position correction, adjustment, signal output
Quick setup - density-
compensated level meas-
urement
Main menu