5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic differential pressure

46332-EN-160212

5  Set up with the display and adjustment 

module

5.1  Parameter adjustment - Quick setup

To quickly and easily adapt the sensor to the application, select 

the menu item "

Quick setup

" in the start graphic on the display and 

adjustment module.

Carry out the following steps in the sequence specified below. The 

presettings apply to all applications.
You can find "

Extended adjustment

" in the next sub-chapter.

1. Measurement loop name

In the first menu item you assign a suitable measurement loop name. 

Permitted are names with max. 19 characters.

2. Application

In this menu item you activate/deactivate the slave sensor for elec

-

tronic differential pressure and select the application.

Note:

It is absolutely necessary to activate the slave sensor in advance to 

have the applications displayed in the electronic differential pressure 

measurement menus.

3. Units

In this menu item you determine the adjustment and temperature 

units of the instrument. Depending on the selected application in the 

menu item "

Application

", different adjustment units are available.

4. Unit, static pressure

In this menu item, you determine the unit of the static, i.e. superim

-

posed pressure.

5. Position correction

In this menu item you compensate the influence of the installation 

position of the instrument (offset) on the measured value.

6. Min. adjustment

In this menu item you carry out the min. adjustment for level.

Enter the percentage value and the corresponding pressure value for 

the min. level.

7. Max. adjustment

In this menu item you carry out the max. adjustment for level.

Presettings

Quick setup - Level meas-

urement

Содержание VEGABAR 82

Страница 1: ...Quick setup guide Pressure transmitter with ceramic measuring cell VEGABAR 82 Slave sensor for electronic differential pres sure Document ID 46332...

Страница 2: ...4 2 Single chamber housing 10 4 3 Connection example 11 5 Set up with the display and adjustment module 5 1 Parameter adjustment Quick setup 12 5 2 Parameter adjustment Extended adjustment 15 6 Suppl...

Страница 3: ...fill or damage to system components through incorrect mounting or adjustment Also the pro tective characteristics of the instrument can be influenced 1 4 General safety instructions This is a high tec...

Страница 4: ...er related higher than the permissible pressure range of the process fitting is installed 1 7 Environmental instructions Protection of the environment is one of our most important duties That is why w...

Страница 5: ...ID numbers instrument documentation 14 Reminder to observe the instrument documentation The type label contains the serial number of the instrument With it you can find the following instrument data...

Страница 6: ...the following functions Ventilation of the electronics housing Atmospheric pressure compensation with relative pressure meas uring ranges Turn the housing so that the filter element points downward a...

Страница 7: ...s can result see following examples Data Application Level measurement Medium Water Vessel height 12 m hydrostatic pressure 12 m x 1000 kg m3 x 9 81 m s2 117 7 kPa 1 18 bar Superimposed pressure 1 bar...

Страница 8: ...Nominal measuring range Slave 1 bar Turn Down 1 bar 0 050 bar 20 1 The measuring result level pressure difference as well as measured value Slave static or superimposed pressure are outputted by the...

Страница 9: ...block is pluggable and can be removed from the electronics To do this lift the terminal block with a small screwdriver and pull it out When reinserting the terminal block you should hear it snap in Yo...

Страница 10: ...the supplied cable gland 10 Connection cable to Master see steps 3 to 8 11 Screw the housing lid back on The electrical connection is finished 4 2 Single chamber housing The following illustration app...

Страница 11: ...g 5 Connection example electronic differential pressure 1 Master sensor 2 Slave sensor 3 Connection cable 4 Supply and signal circuit Master sensor Connection between master and sensor is carried out...

Страница 12: ...ifferential pressure and select the application Note It is absolutely necessary to activate the slave sensor in advance to have the applications displayed in the electronic differential pressure measu...

Страница 13: ...low Enter the percentage value and the corresponding pressure value for the max flow 7 Linearization In this menu item you select the characterics of the output signal The quick setup for flow measure...

Страница 14: ...you carry out the max adjustment for density Enter the percentage value and the corresponding density value for the max density The quick setup for density measurement is finished 4 Unit static pressu...

Страница 15: ...u item you carry out the min adjustment for level Enter the percentage value and the corresponding pressure value for the min level 8 Max adjustment In this menu item you carry out the max adjustment...

Страница 16: ...the menu Setup for electronic differential pressure measurement are described in detail Depending on the selected application different sections are relevant Information Further menu items of the menu...

Страница 17: ...rent output in Displayed value 2 Ceramic measuring cell Measuring cell tempera ture in C Metallic measuring cell Electronics temperature in C Display format 1 and 2 Number of positions after the decim...

Страница 18: ...ent output Meas vari able Lin percent Level Current output Adjustment 0 100 correspond to 4 20 mA HART mode Address 0 DP flow ele ment Unit m3 s Adjustment 0 00 correspond to 0 00 m3 s 100 00 1 m3 s M...

Страница 19: ...d terminals Massive wire stranded wire 0 2 2 5 mm AWG 24 14 Stranded wire with end sleeve 0 2 1 5 mm AWG 24 16 Interface to the Master sensor Data transmission Digital I C Bus Connection cable to the...

Страница 20: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: