Overfill Alarm Relay
The console has one dry contact relay output that closes when an overfill alarm is activated. You can connect an
external audible/visual warning device to this relay. Connect the two wires from the external warning device to the
either of the two overfill relay terminals (J5) [see Figure 23].
Important! Note these Output Relay Connection Restrictions:
• Output relays can not be connected to a device that draws more than 2 amperes of current.
• Output power - output relay contact, resistive load - 120/240 Vac, 2 A max.
Alarm relays cannot be used for flow control. Alarm relays provide only a momentary closure and cannot actuate
flow control devices such as valves and pump motor relays for extended periods of time.
Figure 23. Connecting Output Relay to Console
Legend for numbered boxes
1
Connect one wire from relay to top terminal of J6 (no polarity)
2
Connect second wire from relay to lower terminal of J6 (no polarity)
3
Power area of console
4
Intrinsically safe area of console (under cover)
J5
J6